Ultra Compact Intelligent Circuit Breaker CBRM5E from China Suppliers and Factory - Fast Auto-Reclosing, Smart Grid Ready
Main functions and features Product model and meaning
Main functions and features
Operating environment
Classification and functions of circuit breakers
| Functional classification | Conventional type | Metering type | Photovoltaic type | |
|---|---|---|---|---|
| Protection function | Overload protection | ● | ● | ● |
| Short circuit protection | ● | ● | ● | |
| Automatic reclosing | ● | ● | ● | |
| Open phase protection | ● | ● | ● | |
| Overvoltage protection | ● | ● | ● | |
| Undervoltage protection | ● | ● | ● | |
| Null line loss protection | ● | ● | ● | |
| Over/Under-frequency protection | ● | ● | ● | |
| Power outage protection | ● | ● | ● | |
| Phase sequence protection | ● | ● | ● | |
| Islanding protection | ○ | ○ | ● | |
| Overtemperature protection | △ | △ | ● | |
| Power quality monitoring and protection | ○ | △ | ● | |
| Measurement display | Three-phase operating voltage | ● | ● | ● |
| Three-phase operating current | ● | ● | ● | |
| Active power | ○ | ● | ● | |
| Reactive power | ○ | ● | ● | |
| Apparent power | ○ | ● | ● | |
| Voltage imbalance | ○ | ● | ● | |
| Current imbalance | ○ | ● | ● | |
| Performance setting | Long delay of overload | ● | ● | ● |
| Short delay of short circuit | ● | ● | ● | |
| Instantaneous short circuit | ● | ● | ● | |
| Overvoltage protection value | ● | ● | ● | |
| Undervoltage protection value | ● | ● | ● | |
| Time and date | ● | ● | ● | |
| Protecting enabling and disabling | ● | ● | ● | |
| Open phase protection value | ● | ● | ● | |
| Over/Under-frequency protection value | ○ | ● | ● | |
| Voltage imbalance protection value | ○ | ● | ● | |
| Current imbalance protection value | ○ | ● | ● | |
| Information query and display (Action records and fault records) | ● | ● | ● | |
| Communication function | RS-485/ Modbus | ● | ● | ● |
| Carrier | △ | △ | △ | |
| Bluetooth | △ | ● | ● | |
| Topology | △ | △ | △ | |
Main technical parameters
| Specification and model | 125 | 250 | 400 | 630 | |
| Rated current of frame size (A) | 125 | 250 | 400 | 630 | |
| Number of poles | 3P/4P | ||||
| Rated operating voltage Ue (V) | AC 400/50HZ | ||||
| Rated insulation voltage Ui (V) | 1000 | ||||
| Rated impulse withstand voltage Uimp (V) | 8000 | ||||
| Flashover distance (mm) | ≥50 | ≥100 | |||
| Limit short-circuit breaking capacity Icu (kA) | 25(S) 36(L) 50(M) | 36(S) 35(L) 50(M) | 35(S) 65(L) 70(M) | 50(S) 65(L) 70(M) | |
| Operating short-circuit breaking capacity Ics (kA) | 20(S) 25(L) 35(M) | 25(S) 35(L) 35(M) | 35(S) 42(L) 50(M) | 50(S) 50(L) 70(M) | |
| Rated short-time withstand current Icw (kA)/s | 1.5 | 3 | 5 | 8 | |
| Automatic closing time (s) | ≤2s | ||||
| Operating performance (times) | Power on | 1500 | 1000 | 1000 | 1000 |
| No power supply | 8500 | 7000 | 4000 | 4000 | |
| Total number of times | 10000 | 8000 | 5000 | 5000 | |
| Overload and short circuit characteristics | Three-section protection, electronically adjustable; for details, please refer to "Protection characteristics description" | ||||
| Overvoltage protection value (V) | Set value (231~330) / Default value 275V | ||||
| Undervoltage protection value (V) | Set value (88~209) / Default value 145V | ||||
| Open phase protection value (V) | Set value (10~130) / Default value 30V | ||||
| Control delay time (ms) | ≤40ms | ||||
| Communication delay time (ms) | ≤200ms | ||||
Measurement accuracy class
| Accuracy | Allowable error |
|---|---|
| Current accuracy | ±0.5%、 ±1.0% |
| Voltage accuracy | ±0.5%、 ±1.0% |
| Active power accuracy | ±1.0%、 ±1.5%、 2.0%、 2.5% |
| Reactive power accuracy | ±1.0%、 ±1.5%、 2.0%、 2.5% |
Note: The temperature detection point is located near the incoming and outgoing wiring terminals.
Passive islanding protection
The passive inspection method mainly detects whether the system is in an islanding state by detecting the amplitude, frequency, phase position, and harmonic content of the common point voltage at the output terminal of the inverter, mainly including overvoltage/undervoltage protection, overfrequency/underfrequency protection, phase change detection, harmonic detection, etc. The setting values of passive islanding detection criteria;
Voltage amplitude swing (dUisl): 0.1~0.9Un, OFF; voltage frequency swing (dFisl): 0.5~25Hz, OFF;
Voltage phase swing (dPHisl): 1~60°, OFF; voltage waveform distortion swing (dUTHDisl): 0.5~30%, OFF;
The delay action characteristic is a fixed time limit, and tPis setting range is 0.01-9.99s;
The passive islanding protection action should meet the requirements in Table 8.
Protection characteristics description
Overload long delay protection
The circuit breaker should provide overload and short-circuit protection, photovoltaic power generation system islanding protection and power quality monitoring protection. The setting values of all protection functions should support remote configuration.
1. Range of overcurrent long delay setting value (Ir)
Range of current setting value (Ir): 0.4~1In, OFF. OFF means it can be turned off, that is, turning off the protection function. The delay action characteristic is the IEC standard inverse time limit curve, Kfactor=0.14, αfactor=0.02, Lfactor=0, I=set current, Is=rated current:
Tms setting range: 1-10s.
The overcurrent long delay protection action should meet the requirements in Table 1.
Comparison Table of Overcurrent Long Delay Protection Actions (Table 1)
| Long delay action current (Ir1) | Action |
|---|---|
| ≤Ir | Normal operation |
| 1Ir~1.5Ir | Continuously observe for 10 minutes, actively report overload alarm and record the data; after 10 minutes, the current still exceeds the standard limit |
| ≥1.5Ir | Observe continuously for 5 minutes. If the current still exceeds the standard limit after 5 minutes, cut off the grid connection point and report it |
Note: 1.3Ir is a conservative value, and the time and current values are set in the switch body.
Action characteristics
1. Range of overcurrent short delay setting value (Isd)
Range of short-time action current (Isd): 1.5~5Ir, OFF. OFF means it can be turned off, that is, turning off the protection function. The delay action characteristic is a fixed time limit, and the setting range of tlsd is 1-10s. The overcurrent short delay protection action should meet the requirements in Table 2.
Comparison Table of Overcurrent Short Delay Protection Action (Table 2)
| Short delay action current (Isd) | Action |
|---|---|
| ≤k1Ir | Normal operation |
| k1Ir~k2Ir | Normal operation; actively report overcurrent alarms and record the data |
| ≥k2Ir | Continuously observe for tlsd time, and if the current still exceeds the standard limit after tlsd time, cut off the grid connection point and report it |
Note: k1, k2=1.5~5Ir, k1<k2; the time and current values are set in the switch body.
2. Range of rated short-time breaking current setting value (Ii).
Range of rated instantaneous short-circuit current setting value (Ii): 2~12Ir, OFF. OFF means it can be turned off, that is, turning off the protection function. The breaking current protection action should meet the requirements in Table 3.
Comparison Table of Short-circuit Current Protection Action (Table 3)
| Short-circuit current | Action |
|---|---|
| ≥ 5~8Ir | Cut off the grid connection point in 0.2 seconds and report it |
3. The protection characteristic curve of three-section protection is shown in the following figure:
Overvoltage protection
Range of overvoltage protection voltage setting value (Uov) is 1.05~1.5Un. OFF means it can be turned off, that is, turning off the protection function. The delay action characteristic is a fixed time limit, and the setting range of tUov is 1-9999s. The overvoltage protection action should meet the requirements in Table 5.
Comparison Table of Overvoltage Protection Action (Table 5)
| Maximum value of three-phase voltage | Action |
|---|---|
| ≤ 234.5V | Normal operation |
| > 234.5V | Cut off the grid connection point after 2s and report it |
| Note: 1. OFF means it can be turned off, that is, turning off the protection function. 2. While monitoring the changes in voltage amplitude, also monitor the changes in voltage frequency. If the voltage frequency remains basically unchanged, use the above criteria for overvoltage protection. |
|
Undervoltage protection
The molded case circuit breakers do not have such function. Range of undervoltage protection voltage setting value (Uuv) is 0.4~0.95Un. OFF means it can be turned off, that is, turning off the protection function. The delay action characteristic is a fixed time limit, and the setting range of tUuv is 1-9,999s. The undervoltage protection action should meet the requirements in Table 6.
Comparison Table of Undervoltage Protection Action (Table 6)
| Minimum value of three-phase voltage | Action |
|---|---|
| ≥ 187V | Normal operation |
| < 187V | Cut off the grid connection point after 2s and report it |
| Note: 1. OFF means it can be turned off, that is, turning off the protection function. 2. While monitoring the changes in voltage amplitude, also monitor the changes in voltage frequency. If the voltage frequency remains basically unchanged, use the above criteria for overvoltage protection. |
|
Terminal and contact overtemperature protection
Range of terminal and contact overtemperature protection setting value (Tem): 80~160℃, OFF. OFF means it can be turned off, that is, turning off the protection function. The delay action characteristic is a fixed time limit, and tTem setting range is 1-9,999s. The terminal and contact overtemperature protection action should meet the requirements in Table 7.
Comparison Table of Terminal and Contact Overtemperature Protection Action (Table 7)
| Terminal and contact temperature | Action |
|---|---|
| ≤ 60℃ | Normal operation |
| 60℃~90℃ | Normal operation; actively report terminal and contact overtemperature alarms and record the data |
| ≥ 90℃ | Continuously observe for 60s. If the temperature of the terminal and contact still exceeds the standard limit after 60s, cut off the grid connection point and report it |
| ≥ 110℃ | Cut off the grid connection point after 0.2s and report it |
Passive islanding protection
The passive inspection method mainly detects whether the system is in an islanding state by detecting the amplitude, frequency, phase position, and harmonic content of the common point voltage at the output terminal of the inverter, mainly including overvoltage/undervoltage protection, overfrequency/underfrequency protection, phase change detection, harmonic detection, etc. The setting values of passive islanding detection criteria;
Voltage amplitude swing (dUisl): 0.1~0.9Un, OFF; voltage frequency swing (dFisl): 0.5~25Hz, OFF;
Voltage phase swing (dPHisl): 1~60°, OFF; voltage waveform distortion swing (dUTHDisl): 0.5~30%, OFF;
The delay action characteristic is a fixed time limit, and tPis setting range is 0.01-9.99s;
The passive islanding protection action should meet the requirements in Table 8.
Comparison Table of Passive Islanding Protection Action (Table 8)
| Fluctuation value of criteria | Action |
|---|---|
| Voltage amplitude swing or swing range | If the voltage amplitude swing range exceeds 20V or the swing exceeds the range of [187V, 234.5V] within 100ms, it is judged as an island |
| Voltage frequency swing or swing range | If the voltage frequency swing range exceeds 0.2Hz or the swing exceeds the range of [49.5Hz~50.2Hz] within 100ms, it is judged as an island |
| Note: 1. The swing range refers to the difference between the maximum and minimum swing values within a certain period of time; 2. The above criteria are mainly based on voltage frequency swing, supplemented by voltage amplitude swing. When the voltage frequency swing criterion is established, cut off the grid connection point within 2s and report it. |
|
Power generation quality monitoring and protection
The monitoring and protection actions of power generation current harmonics should meet the requirements in Table 9.
Comparison Table of Current Harmonics and Protection Action (Table 9)
| Total current distortion | Action |
|---|---|
| ≤5% | Normal grid connection |
| >5% | Continuously observe for 60s, and if the harmonic wave still exceeds the standard limit after 60 seconds, cut off the grid connection point and report it |
| Note: OFF means it can be turned off, that is, turning off the protection function. | |
Monitoring and protection of power generation current three-phase imbalance (applicable to three-phase grid connection)
The three-phase imbalance protection action of power generation current should meet the requirements in Table 10.
Negative sequence three-phase current imbalance ratio and protection action (Table 10)
| Three phase current imbalance ratio | Action |
|---|---|
| ≤ 2% | Normal grid connection |
| > 2% | Continuously observe for 60s, and if the imbalance ratio still exceeds the standard limit after 60 seconds, cut off the grid connection point and report it |
| Note: OFF means it can be turned off, that is, turning off the protection function. | |
Undervoltage protection function
When the phase voltage of the line is lower than the undervoltage protection set value, the circuit breaker will trip for protection. After the line voltage returns to normal, the circuit breaker can be automatically closed and activated. The range of undervoltage protection setting value is 88V~209V, the factory setting is 187V, and users can set or turn off the protection themselves.
Open phase protection function
When the phase of the outgoing line of the power end of the line is open, the circuit breaker will trip for protection. After the line voltage returns to normal, the circuit breaker can be automatically closed and activated. The range of open phase protection set value is 10V~130V, the factory setting is 30V, and users can set or turn off the protection themselves.
Automatic reclosing
When the line voltage value exceeds the limit and the circuit breaker trips, the circuit breaker will be automatically reclosed 5s later after the line voltage returns to normal, but manual closing is not limited by time.
External control or dynamic protection function
Note: S1 is passive dry node; When the product is put into use and there is no external control, S1 needs to be shorted or the external control function of the software needs to be turned off.
Cost control function
This product can be connected to a cost control meter and be used as an external circuit breaker for an energy meter. It is compatible with pulse type and level type cost control meters. This function requires configuring the switch to cost control mode and turning it on, and only when the cost control is enabled, can it be used. When it is working in cost control mode, the dynamic protection function can automatically exit, and when there is no energy meter cost control signal, it cannot be manually or automatically closed. If it is closed by force, the product will be automatically disconnected.
Overall and installation dimensions - 3P
| Model | Overall dimensions (mm) | Installation dimensions (mm) | Dimensions of wiring block (mm) | Mounting screw | Model | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| L | L1 | L2 | L3 | W1 | W2 | H | H1 | H2 | a | b | d | A | B | C | t1 | t2 | h1 | h2 | M | ||
| CBRM5E-125CYJ/4 | 150 | 108.7 | 24.7 | 88.7 | 60 | 92 | 120 | 117 | 65.5 | 30 | 129 | Φ4.5 | 18 | 17 | 8.5 | 3 | 3 | 23 | 26 | M8x20 | M4x45 |
| CBRM5E-250CYJ/4 | 165 | 109 | 30.5 | 99 | 70 | 107 | 120 | 117 | 69.5 | 35 | 126 | Φ4.5 | 22 | 21 | 10.5 | 3 | 3 | 24 | 24 | M8x20 | M4x45 |
| CBRM5E-400CYJ/4 | 258 | 177 | 40.5 | 148 | 96 | 150 | 160 | 157 | 98.5 | 44 | 195 | Φ7 | 33 | 28.5 | 16.5 | 5 | 4 | 36.5 | 37.5 | M10X35 | M5X100 |
| CBRM5E-630CYJ/4 | 270 | 177 | 46.5 | 145.8 | 116 | 182 | 163.5 | 160.5 | 102 | 58 | 200 | Φ7 | 44 | 30.5 | 17.7 | 6 | 6 | 41.5 | 43.5 | M12x35 | M6x65 |
Overall and installation dimensions - 4P
| Model | Overall dimensions (mm) | Installation dimensions (mm) | Dimensions of wiring block (mm) | Mounting screw | Model | |||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| L | L1 | L2 | L3 | W | W1 | W2 | H | H1 | H2 | a | b | d | A | B | C | t1 | t2 | h1 | h2 | M | ||
| CBRM5E-125CYJ/4 | 150 | 108.7 | 24.7 | 88.7 | 122 | 30 | 92 | 120 | 117 | 65.5 | 30 | 129 | Φ4.5 | 18 | 17 | 8.5 | 3 | 3 | 23 | 26 | M8x20 | M4x45 |
| CBRM5E-250CYJ/4 | 165 | 109 | 30.5 | 99 | 142 | 35 | 107 | 120 | 117 | 69.5 | 35 | 126 | Φ4.5 | 22 | 21 | 10.5 | 3 | 3 | 24 | 24 | M8x20 | M4x45 |
| CBRM5E-400CYJ/4 | 258 | 177 | 40.5 | 148 | 198 | 48 | 150 | 160 | 157 | 98.5 | 44 | 195 | Φ7 | 33 | 28.5 | 16.5 | 5 | 4 | 36.5 | 37.5 | M10X35 | M5X100 |
| CBRM5E-630CYJ/4 | 270 | 177 | 46.5 | 145.8 | 240 | 58 | 182 | 163.5 | 160.5 | 102 | 58 | 200 | Φ7 | 44 | 30.5 | 17.7 | 6 | 6 | 41.5 | 43.5 | M12x35 | M6x65 |

CBRM5EL Automatic Reclosing MCCB
CBRM3EL Remote Reclosing MCCB
CBRM5E Intelligent MCCB
CBRM5EKd Electronic MCCB
CBRM5Kd Compact MCCB
CBRM5K Lockable MCCB