CBRM5EL Compact Automatic Reclosing Circuit Breaker with Residual Current Protection(MCCB)

The series residual current circuit breaker has a rated insulation voltage of 1000V, suitable for three-phase AC systems with 50Hz frequency, 400V rated voltage and rated current up to 630A. In the distribution network, the four-wire neutral point is directly grounded. It provides indirect contact protection, prevents fire hazards caused by ground fault current due to equipment insulation damage, and distributes electrical energy to protect lines and power equipment from hazards such as overload, undervoltage, short circuit and single-phase grounding faults.‌

    Residual Current Protection (RCD) Circuit Breaker (Smart Reclosing)

    Product Model and Meaning

    ScreenShot_2026-08-07_141642_464.png

    Meets standards

    The product meets the following standards.
    GB/T14048.1-2012 Low voltage switchgear and control equipment Part 1: General principles;
    GB/T14048.2-2008 Low-voltage switchgear and control equipment Part 2: Circuit breakers;
    GB/T1770 1-2008 <Equipment circuit breakers>.

    Main functions and features

    Adopt high-performance 32-bit ARM microprocessor, real-time signal processing and intelligent control; LCD Chinese display, user-friendly interface, easy operation;
    The residual current (leakage current) protection can be adjusted online, and has the function of reclosing;
    Real-time monitoring and tracking of the residual current of the line, automatic adjustment of the range, to ensure the operation rate and reliability of the product;
    Three-stage protection, long delay, short delay and instantaneous, using electronic trip, independent of power supply voltage;
     It has high breaking capacity and ensures the reliability of line short circuit protection. Overvoltage protection, undervoltage protection, phase loss protection;
    The residual current of the line, the three-phase power supply voltage and the load current are displayed in real time;
    Protective functions and parameters can be set and modified online.
    Trip types (residual current, lockout, overload, undervoltage, overvoltage, phase loss) are identified, displayed, and can be stored, queried, and deleted;
    The network has communication function, which can realize remote signal, remote measurement, remote control and remote adjustment.
    Plug-and-play lightning protection module (optional).
    Supports infrared communication (optional).

    Key technical specifications

    Specifications and models

    CERM5EL-125CY
    CBRM5EL-125CS

    CERM5EL-250CY
    CRRM5EL-250CS

    CBRM5EL-400CY
    CBRM5EL-400CS

    CBRM5EL-630CY
    CRRM5EL-630CS

    Rated current of the shell frame class (A)

    125

    250

    400

    630

    Number of poles

    3P+N

    3P+N

    3P+N

    3P+N

    Rated working voltage Ue (V)

    AC 400/50HZ

    Rated insulation voltage Ui(V)

    1000

    Rated impulse withstand voltage Uimp(V)

    8000

    Arc Distance(mm)

    <=50

    <=100

    Maximum short-circuit breaking capacity (lcu, kA)

    50

    65

    85

    Operating short-circuit breaking capacity (les, kA)

    35

    42

    65

    Rated residual short-circuit breaking capacity Im (kA)

    12.5

    16.25

    21.25

    Rated short-time withstand current (LCW) in kA/s

    1.5

    3

    5

    8

    Residual Curent Operating Characteristic

    AC type

    Rated residual operating current In (mA)

    50/100/200/300/400/500/600/800
    MCU auto-tracking or manual setting

    100/200/300/400/500
    600/800/1000 MCU
    MCU auto-tracking or manual setting)

    Residual Operating Time Characteristic

    Time-delay type / Non-time-delay type

    Delay-type limit non-drive time (s)

    0.06:21n

    Break-time(s)

    In≤≤0.5;21n≤0.2:51n≤0.15

    Automatic reclosing time (s)

    20-60

     

     

     

    Operation performance (times)

    Set up an electric circuit

    1500

    1000

    1000

    No power

    8500

    7000

    4000

    Total

    10000

    8000

    5000

    Overload and short-circuit characteristics

    Three stage protection with electronic adjustment, See "Protection Characteristics" for details.

    Over-voltage protection value (V)

    Set value (250~300)±5%

    Under-voltage protection value (V)

    Set value (145-200)±5%

    Control delay time (ms)

    ≤40ms

    Communication delay (ms)

    ≤200ms

    Protection feature description

    ◆Overload and long delay protection
    Action value range
    Table 1:Overload Long Delay Parameter Settings

    Parameter

    Shroud current

    Set value

    Factory set value

    Action set-point Irl

    125

    50A、63A、80A、100A、125A

    125A

    250

    100A、125A、140A、160A、180A、200A、225A、250A

    250A

    400

    160A、180A、200A、225A、250A、315A、350A、400A

    400A

    630

    250A、315A、350A、400A、500A、630A

    630A

    Delay time setting value tL

    3s,4s,6s,8s, 10s,12s,16s, 18s, OFF

    12s

    ◆Performance characteristic
    Table 2: Protection Action Characteristics

    Ambient temperature

    Current name

    Set current multiplier

    Appointed time

    +40℃

    Conventional non tripping current

    1.051r1

    ≥2h

    Conventional tripping current

    1.3Ir1

    <2h

    ◆Time-delay characteristics
    The overload protection is based on the inverse time characteristic.
    The delay time is calculated as T=(6lrl/l) x L, with a tolerance of+10%.Here,T represents the action time, lrl is the long delay protection setting, i denotes the fault current, and L stands for the long delay time setting.

    ◆Short circuit short delay protection
    Short delay protection prevents impedance short circuit in the power distribution sytem. and the trip delay is to achieve selective protection.Short-circuit short delay protection parameter settings.
    Table 3: Short-Circuit Delay Parameter Setting

    Parameter setting

    Set value

    Factory set value

    Short delay action current setting Ir2

    2Irl,2.5lrl,3Irl,4lrl,5Ir1,6lIrl,7Irl,8lrl,10Irl,12lr

    6lr1

    Short delay time setting value ts

    10.1s,0.2s,0.3s,0.4s,0.6s,0.8s,1.0s,OFF

    0.4s

    Short-circuit short delay protection action characteristics
    Table 4:Short Delay Action Characteristics of Short Circuit

    Characteristic

    Fault current multiple

    Trip characteristics

    Delay error

    No action feature

    ≤0.85 Ir2

    Failure to actuate

    /

    Performance characteristic

    >1.15 Ir2

    Deferred action

    ±40ms

    ◆Instant Protection
    Set parameters for instantaneous short-circuit protection
    Table 5:Instantaneous parameter setting

    Parameter setting

    Set value

    Factory set value

    Instantaneous action current setting Ir3

    4 Irl,6 Irl,7 Irl,8 Irl,9 Irl,10 Irl,11 Irl,12 Irl,13 Irl,14 Irl,OFF

    10 Ir1

    Instantaneous short-circuit protection characteristics
    Table 6:Instantaneous Motion Characteristics

    Characteristic

    Current multiplier (1/r3)

    Trip characteristics

    Trip time

    No action feature

    ≤0.85

    Failure to actuate

    ≥200ms

    Performance characteristic

    >1. 15

    Movement

    <200ms

    ◆Setting range for residual current protection characteristics
    Table 7

    Parameter

    Set value (125.250,400)

    Set value (630)

    Factory set value

    Remaining motion current I△n

    50,100,200,300,400500,600,800.automatic

    100,200,300,400,500,600,800.1000automatic

    500

    ◆Performance characteristic
    Table 8: Protection Action Characteristics

    Parameter

    Characteristic

    Rated no-load current

    0.5I△n

    Rated operating current

    ≥0.751△n

    Time-delay characteristics

    2I△n Limit Time (△t)

    Break-time

    I△n

    2I△n

    5I△n

    Non-delay

     

    ≤0.3s

    ≤0.15s

    ≤0.04s

    0.06

    ≥0.06s

    ≤0.5s

    ≤0.2s

    ≤0.15s

    ◆Auto mode
    In automatic gear mode, the gear values and floating values are:

    Gauge reading (mA)

    Floating value (mA)

    50

    25

    100

    50

    200

    100

    300

    150

    400

    200

    500

    250

    600

    300

    800

    400

    1000

    -

    When the residual current exceeds the floating threshold of a setting without reaching its activation level and remains stable for 60 seconds, the setting is raised by one level. This process continues until reaching the maximum setting. Conversely, when the residual current falls below the floating threshold of the next lower setting and remains stable for 120 seconds, the setting is lowered by one level. This sequence repeats until the minimum setting is reached. Taking the 'Auto 2' setting with an initial residual current of 100mA as an example: When the circuit breaker is energized, the setting automatically resets to 300mA. If the residual current increases above 150mA and remains stable for 60 seconds, the setting changes to 500mA. When the residual current decreases below 150mA and stays stable for 120 seconds, the setting adjusts to 200mA.

    ◆Autoreclose circuit breaker
    When the residual current exceeds the set trip current threshold, the circuit breaker will trip. After 20-60 seconds, it can automatically reclose, though manual reclosing is unrestricted. If the fault current disappears within 5 seconds after reclosing, the operation is successful and the breaker resumes normal operation. If the fault persists, the breaker will trip again and remain locked, preventing automatic reclosing. In such cases, manual reclosing must be performed.

    ◆Over-voltage protection
    When the line phase voltage exceeds the overvoltage protection setting, the circuit breaker trips. Once the voltage returns to normal, the circuit breaker automatically recloses and resumes operation. The overvoltage protection setting ranges from 250V to 300V, with a factory default of 275V. Users can adjust or disable the protection as needed.

    ◆Undervoltage protection
    When the phase voltage falls below the undervoltage protection setting, the circuit breaker trips. Once the voltage returns to normal, the breaker automatically recloses. The undervoltage protection range is 145V to 200V, with a factory default of 145V. Users can adjust or disable the protection as needed.

    ◆Phase loss protection function
    When a phase is missing at the power supply end of the line, the circuit breaker protection trips. When the line is restored to normal voltage, the circuit breaker can be automatically closed and put into operation.

    Outline Overall and Installing Dimensions

    Outline Overall and Installing Dimensions.1.jpg

    Outline Overall and Installing Dimensions.2.jpg

    Outline Overall and Installing Dimensions.3.jpg

    Outline Overall and Installing Dimensions.4.jpg

    characteristic curve

    ◆Linked protection function
    The Linkage lnterface Can Be Used to Coordinate With Other Fire Fighting Equipment for Protection as Follows.

    IN input settings

    Function declaration

    Priority

    Delay time

    Input control

    IN1 is short-circuited to DCOM

    Circuit breaker closed

    Low

    ≤40ms

    IN3 is short-circuited to DCOM

    Trip the circuit breaker

    Gao

    ≤40ms

    Note: Prolonged short-circuiting will keep the circuit breaker in the open state.

    operating time.jpg

    • CBRM5EL-125CY

      CBRM5EL-125CY

    • CBRM5EL-160CY、250CY

      CBRM5EL-160CY、250CY

    • CBRM5EL-400CY

      CBRM5EL-400CY

    • CBRM5EL-630CY

      CBRM5EL-630CY