High Breaking Capacity Air Circuit Breaker 2500A from China Suppliers & Factory - CBRW3 Intelligent ACB
Normal Operating and Installation Conditions
Ambient Air Temperature
The upper limit shall not exceed +55°C, and the lower limit shall not be less than -5°C.
Altitude
The altitude of the installation site shall not exceed 2000m. The high-altitude derating coefficient can be referred to.
Atmospheric Conditions
At +55°C, relative humidity shall not exceed 50%. Higher humidity is allowed at lower temperatures (e.g., 90% at +20°C). Special measures shall be taken for occasional condensation.
Pollution Degree
Level 3.
Installation Category
Main circuit (including under-voltage release coil) is Category Ⅳ; control and auxiliary circuits are Category Ⅲ.
Installation Conditions
Installed as required in the instruction manual. The vertical inclination shall not exceed 5°.
Protection Class
IP30, IP40 (installed in the cabinet compartment, with door frames and organic glass covers added).
Service Category
Category B
Product Features
-
1
The contact system is installed in the small chamber of the insulating part. The contact system of each phase adopts a multi-path sheet-like structure, realizes electric force compensation and ensures the high breaking capacity of the circuit breaker.
-
2
The advanced arc-extinguishing system and protective cover ensure "zero flying arc", making the product more secure.
-
3
The circuit breaker is operated for energy storage by the energy-storage mechanism, with a fast closing speed.
-
4
The operating mechanism is installed at the center of the front of the circuit breaker and is completely separated from the main circuit. It can make each phase have a stable and consistent final contact pressure, which plays an important role in ensuring the temperature rise and breaking indicators.
-
5
The centered operating mechanism facilitates symmetric hole-opening in the middle of the complete set of cabinet doors, improving the appearance quality of the complete set of cabinets.
-
6
It can be installed with bottom incoming lines and has horizontal and vertical wiring methods.
-
7
Intelligent controller, with multiple protection functions, can realize selective protection.
Model and Description
| ATA | 3200 | / | 3200A | / | 3P | / | Intelligent Controller Model(M) | / | Operating Voltage of the Intelligent Circuit AC380V/ AC220V /DC220V/ DC110 |
| 3150A | |||||||||
| 2900A | |||||||||
| 2500A | |||||||||
| 2000A |
Product Specifications
| Breaker Model | ATA3200 | |||
| Frame-rated Current lrm(A) | 3200 | |||
| Rated Operating Current In (A) | 2000□2500 | 2900、3150、3200 | ||
| Rated Operating Voltage Ue (v) | AC230、AC400、AC690 | |||
| Rated Frequency Hz | 50/60Hz | |||
| Rated insulation Voltage Ui(V) | 1000 | |||
| Rated impulse Withstand Voltage Uimp (kV) | 12 | |||
| Number of Poles (P) | 3 | |||
| Total Breaking Time (ms) | ≤30 | |||
| Closing Time (ms) | ≤60 | |||
| Rated Ultimate Short-Circuit Breaking Capacity Icu(kA)(RMS) | AC230V | 65 | ||
| AC400V | 65 | |||
| AC690V | 50 | |||
| Rated Service Short-Circuit Breaking Capacity Ics (kA)(RMS) | AC400V | 65 | ||
| AC690V | 65 | |||
| AC230V | 50 | |||
| Rated Short-Time Withstand Current Icw(1S)(KA)(RMS) | AC230V | 65 | ||
| AC400V | 65 | |||
| AC690V | 50 | |||
| Operating Performance (Times) | Electrical Life | AC230V AC400V | 10000 | 8000 |
| AC690V | 5000 | 5000 | ||
| Mechanical Life | Maintenance-free | 10000 | 8000 | |
| Maintenance Required | 20000 | 15000 | ||
| Installation Type | Fixed Type | |||
| Main Circuit wiring Method | Fixed Type | Horizontal Wiring, Vertical wiring | ||
| Overall Dimensions: WxHxD mm | 422X402X368 | |||
| Weight (kg) | 55 | 66 | ||
Frequently Asked Questions (FAQ)
What is the operating temperature range for the ATA3200 circuit breaker?
The ambient air temperature for normal operation should have an upper limit not exceeding +55°C, and the lower limit must not be less than -5°C.
Does the ATA3200 support selective circuit protection?
Yes, the circuit breaker features an intelligent controller with multiple protection functions that can realize selective protection.
What are the installation protection class requirements for this model?
The requirements are IP30 and IP40 when installed in the cabinet compartment, with door frames and organic glass covers added.
What is the mechanical and electrical life of the ATA3200?
The mechanical life is up to 20,000 cycles with maintenance (10,000 cycles maintenance-free). The electrical life ranges up to 10,000 cycles at AC230V/AC400V, and up to 5,000 cycles at AC690V.
What wiring options are available for the main circuit?
The fixed installation type supports both horizontal and vertical wiring methods, and it can also be installed with bottom incoming lines.

CBRM5EL Automatic Reclosing MCCB
CBRM3EL Remote Reclosing MCCB
CBRM5E Intelligent MCCB
CBRM5EKd Electronic MCCB
CBRM5Kd Compact MCCB
CBRM5K Lockable MCCB
CBRM5EN Primary-secondary Separated MCCB
CBRECB Meter Remote Control MCCB
CBRB7BL Type B Smart RCBO
CBRB7 Compact MCB
CBRB7-AP PV Grid-connected MCB
CBRW3 4000A ACB
CBRW3 2500A ACB
CBRW3 1600A ACB