High Breaking Capacity 4000A Air Circuit Breaker (ACB) - China Suppliers & Factory Standard
Maximum: +55°C; Minimum: -5°C
The installation site should not exceed 2000 meters above sea level. Derating factors for high altitude should be taken into consideration.
When the ambient air temperature is +55°C, the relative humidity of the air should not exceed 50%. Higher humidity is permissible at lower temperatures, e.g., up to 90% at +20°C. Special measures should be taken to prevent condensation caused by occasional temperature variations.
Pollution Degree: Degree 3
Installation Category: Main circuit undervoltage trip coil: Category Ⅳ; Control and auxiliary circuits: Category Ⅲ
Installation Requirements: The circuit breaker must be installed according to the instructions. The vertical inclination of the circuit breaker should not exceed 5°.
Protection Degree Requirements for Installation: IP30 or IP40 (when installed in a cabinet compartment, with an additional door frame and transparent cover made of organic glass).
Utilization Category: Category B
-
1. The contact system is installed in individual insulated compartments, and each phase adopts a multi-laminated contact structure. This design achieves electrodynamic compensation, ensuring high breaking capacity of the circuit breaker.
-
2. An advanced arc-extinguishing system and protective cover ensure “zero arc flash”, enhancing operational safety.
-
3. The circuit breaker operates via a stored-energy mechanism, allowing for rapid closing action.
-
4. The operating mechanism is centrally mounted on the front of the circuit breaker, completely isolated from the main circuit. This ensures stable and consistent contact pressure across all poles, playing a critical role in meeting temperature rise and breaking performance requirements.
-
5. The centrally located operating mechanism facilitates symmetrical cut-outs on the switchgear cabinet door, improving the aesthetic quality of the complete unit.
-
6. Bottom entry installation is supported, with both horizontal and vertical wiring configurations available.
-
7. The intelligent controller offers multiple protection functions, enabling selective protection.
| ATA | 4000 | / | 4000A | / | 3P | / | Operating Voltage of Control Circuit (V) | / | Model of Intelligent Controller AC380V/AC220V/DC220V/DC110 |
| 3600A | |||||||||
| 3200A | |||||||||
| 3150A | |||||||||
| 2900A | |||||||||
| 2500A | |||||||||
| 2000A |
| Circuit Breaker Model | ATA4000 | ||
| Rated Current of Frame Level Inm (A) | 4000 | ||
| Rated Working Current In (A) | 2000、2500、2900、3150、3200、3600、4000 | ||
| Rated Working Voltage Ie (V) | AC230、AC400、AC690 | ||
| Rated Frequency Hz | 50/60Hz | ||
| Rated Insulation Voltage Ui (V) | 1000 | ||
| Rated Impulse Withstand Voltage Uimp (kV) | 12 | ||
| Number of Poles (P) | 3 | ||
| Total Breaking Time (ms) | 30 | ||
| Closing Time (ms) | 60 | ||
| Rated Limited Short - circuit Breaking Capacity Icu (kA) (RMS Value) | AC230V | 65 | |
| AC400V | 65 | ||
| AC690V | 50 | ||
| Rated Running Short - circuit Breaking Capacity Ics (kA) (RMS Value) | AC230V | 65 | |
| AC400V | 65 | ||
| AC690V | 50 | ||
| Rated Short - time Withstand Current Icw (1s)(kA)(RMS Value) | AC230V | 65 | |
| AC400V | 65 | ||
| AC690V | 50 | ||
| Operating Performance (Times) | Electrical Life | AC230V AC400V | 6000 |
| AC690V | 3000 | ||
| Mechanical Life | Maintenance - free | 10000 | |
| With Maintenance | 15000 | ||
| Installation Type | Fixed Type | ||
| Main Circuit Wiring Method | Horizontal Wiring, Vertical Wiring | ||
| Overall Dimensions: W×H×D mm | 537X406X406 | ||
| Weight (kg) | 77.5 | ||
The circuit breaker has a compact structure, small volume, and the feature of three-dimensional separation. The contact system is sealed in the insulating base and bottom plate with a separating structure. Each phase contact is separated to form individual small chambers. The intelligent controller, operating mechanism, handle, and motor operating mechanism are arranged in sequence in front of it to form their respective independent units.
The fixed-type circuit breaker consists of the circuit breaker body and the fixed installation side plate. The fixed installation side plate is used for installing and fixing the relative position of the circuit breaker in the switch cabinet.
The structural design allows for systematic installation, ensuring high stability and convenient integration into industrial switchgear systems.
A1: The circuit breaker is designed to operate within an ambient air temperature range of a maximum of +55°C to a minimum of -5°C.
A2: Yes, it can be installed at altitudes up to 2000 meters above sea level. For installations exceeding this altitude, appropriate derating factors must be applied.
A3: The ATA4000 features an advanced arc-extinguishing system and protective cover that completely contains the arc during breaking, ensuring "zero arc flash" and enhancing operator safety.
A4: The circuit breaker supports bottom entry installation and is compatible with both horizontal and vertical wiring configurations to fit different switchgear designs.
A5: The ATA4000 has an electrical life of up to 6000 cycles (at AC230V/AC400V) and a mechanical life of 10,000 cycles maintenance-free, which can be extended to 15,000 cycles with regular maintenance.
A6: The fixed-type configuration consists of the circuit breaker body and a fixed installation side plate, which securely positions and locks the circuit breaker within the switch cabinet.

CBRM5EL Automatic Reclosing MCCB
CBRM3EL Remote Reclosing MCCB
CBRM5E Intelligent MCCB
CBRM5EKd Electronic MCCB
CBRM5Kd Compact MCCB
CBRM5K Lockable MCCB
CBRM5EN Primary-secondary Separated MCCB
CBRECB Meter Remote Control MCCB
CBRB7BL Type B Smart RCBO
CBRB7 Compact MCB
CBRB7-AP PV Grid-connected MCB
CBRW3 4000A ACB
CBRW3 2500A ACB
CBRW3 1600A ACB