High Breaking Capacity 2500A Air Circuit Breaker (ACB) from China Suppliers and Factory - CBRW3 Series
Normal Operating and Installation Conditions
Temperature & Altitude
Ambient air temperature: Upper limit shall not exceed +55°C, lower limit not less than -5°C. Altitude of the installation site shall not exceed 2000m (high-altitude derating coefficient can be referred to).
Atmospheric Conditions
At +55°C, relative humidity shall not exceed 50%. Higher humidity is allowed at lower temperatures (e.g., 90% at +20°C). Special measures shall be taken for occasional condensation.
Pollution & Category
Pollution degree: Level 3. Installation category: Category Ⅳ for main circuit (including under-voltage release coil); Category Ⅲ for control and auxiliary circuits.
Installation & Protection
Vertical inclination shall not exceed 5°. Protection class: IP30, IP40 (installed in cabinet compartment with door frames and organic glass covers). Service category: B.
Product Features
- The contact system is installed in the small chamber of the insulating part. The contact system of each phase adopts a multi-path sheet-like structure, realizes electric force compensation and ensures the high breaking capacity of the circuit breaker.
- The advanced arc-extinguishing system and protective cover ensure “zero flying arc”, making the product more secure.
- The circuit breaker is operated for energy storage by the energy-storage mechanism, with a fast closing speed.
- The operating mechanism is installed at the center of the front of the circuit breaker and is completely separated from the main circuit. It can make each phase have a stable and consistent final contact pressure, which plays an important role in ensuring the temperature rise and breaking indicators.
- The centered operating mechanism facilitates symmetric hole-opening in the middle of the complete set of cabinet doors, improving the appearance quality of the complete set of cabinets.
- It can be installed with bottom incoming lines and has horizontal and vertical wiring methods.
- Intelligent controller, with multiple protection functions, can realize selective protection.
Model and Description
| ATA | 3200 | / | 3200A | / | 3P | / | Intelligent Controller Model(M) | / | Operating Voltage of the Intelligent Circuit AC380V/ AC220V /DC220V/ DC110 |
| 3150A | |||||||||
| 2900A | |||||||||
| 2500A | |||||||||
| 2000A |
Product Features
| Breaker Model | ATA3200 | |||
| Frame - rated Current lrm(A) | 3200 | |||
| Rated Operating Current In (A) | 2000□2500 | 2900、3150、3200 | ||
| Rated Operating Voltage Ue (v) | AC230、AC400、AC690 | |||
| Rated Frequency Hz | 50/60Hz | |||
| Rated insulation Voltage Ui(V) | 1000 | |||
| Rated impulse Withstand Voltage Uimp (kV) | 12 | |||
| Number of Poles (P) | 3 | |||
| Total Breaking Time (ms) | ≤30 | |||
| Closing Time (ms) | ≤60 | |||
| Rated Ultimate Short .Circuit Breaking Capacity Icu(kA)(RMS) | AC230V | 65 | ||
| AC400V | 65 | |||
| AC690V | 50 | |||
| Rated Service Short .Circuit Breaking Capacity Ics (kA)(RMS) | AC400V | 65 | ||
| AC690V | 65 | |||
| AC230V | 50 | |||
| Rated Short . Time Withstand Current Icw(1S)(KA)(RMS) | AC230V | 65 | ||
| AC400V | 65 | |||
| AC690V | 50 | |||
| Operating Performance(Times) | Electrical Life | AC230V AC400V | 10000 | 8000 |
| AC690V | 5000 | 5000 | ||
| Mechanical Life | Maintenance-free | 10000 | 8000 | |
| Maintenance Required | 20000 | 15000 | ||
| Installation Type | Fixed Type | |||
| Main Circuit wiring Method | Fixed Type | Horizontal Wiring, Vertical wiring | ||
| Overall Dimensions:WxHxD mm | 422X402X368 | |||
| Weight (kg) | 55 | 66 | ||
Frequently Asked Questions
Q: What is the operating temperature range for the ATA3200 circuit breaker?
The ambient air temperature for normal operation must be between a lower limit of -5°C and an upper limit of +55°C.
Q: What is the maximum installation altitude without derating?
The standard installation altitude should not exceed 2000 meters. For higher altitudes, a high-altitude derating coefficient must be applied.
Q: What protection classes are available for installation?
The device meets IP30 and IP40 protection requirements when installed in the cabinet compartment with door frames and organic glass covers added.
Q: Does the ATA3200 support vertical wiring?
Yes, the circuit breaker supports both horizontal and vertical wiring methods, and can be installed with bottom incoming lines.
Q: What is the mechanical life expectancy of this circuit breaker?
The mechanical life is 10,000 operations under maintenance-free conditions, and can reach up to 20,000 operations when required maintenance is performed.
Q: What safety benefits does the arc-extinguishing system offer?
The advanced arc-extinguishing system and protective cover ensure "zero flying arc", which makes the product and the operating environment significantly more secure.

CBRM5EL Automatic Reclosing MCCB
CBRM3EL Remote Reclosing MCCB
CBRM5E Intelligent MCCB
CBRM5EKd Electronic MCCB
CBRM5Kd Compact MCCB
CBRM5K Lockable MCCB
CBRM5EN Primary-secondary Separated MCCB
CBRECB Meter Remote Control MCCB
CBRB7BL Type B Smart RCBO
CBRB7 Compact MCB
CBRB7-AP PV Grid-connected MCB
CBRW3 4000A ACB
CBRW3 2500A ACB
CBRW3 1600A ACB