High Breaking Capacity 1600A Air Circuit Breaker (ACB) - China Suppliers & Factory Solutions
Normal Operating and Installation Conditions
- Ambient air temperature: The upper limit shall not exceed +55°C, and the lower limit shall not be lower than -5°C.
- Altitude: The altitude of the installation site shall not exceed 2000m. Reference can be made to the high-altitude derating coefficient.
- Atmospheric conditions: When the ambient air temperature is +55°C, the relative humidity of the air shall not exceed 50%. At lower temperatures, higher humidity is allowed. For example, at +20°C, it can reach 90%. Special measures shall be taken for condensation occasionally generated due to temperature changes.
- Pollution level: Level 3.
- Installation category: The installation category of the main circuit (including the under-voltage release coil) is Category IV; the control circuit and auxiliary circuit are Category III.
- Installation conditions: The circuit breaker shall be installed as required by the instruction manual, and the vertical inclination of the circuit breaker shall not exceed 5°.
- Installation protection class requirements: IP30, IP40 (installed in the cabinet compartment, with additional door frames and organic glass covers).
- Service category: B
Product Features
- The contact system is installed in the insulation part compartment. Each phase contact system adopts a multi-path sheet-like structure, realizing electric force compensation and ensuring the high breaking capacity of the circuit breaker.
- The advanced arc-extinguishing system and protective cover ensure "zero flying arc", making the product safer.
- The circuit breaker is operated by an energy-storage mechanism for energy storage, with a fast closing speed.
- The operating mechanism is installed in the center of the front of the circuit breaker, completely separated from the main circuit. It can make each phase have a stable and consistent final contact pressure, which plays an important role in ensuring temperature rise and breaking indicators.
- The centered operating mechanism is convenient for symmetrical hole-opening in the center of the cabinet door of the complete set, improving the appearance quality of the complete set of cabinets.
- It can be installed with bottom incoming lines, and has horizontal and vertical wiring methods.
- Intelligent controller with multiple protection functions, enabling selective protection.
Model and Description
| ATA | 2000 | / | 2000A | / | 3P | / | Intelligent Controller Model M | / | Operating Voltage of the Intelligent Circuit: AC380V, AC220V, DC220V, DC110V |
| 1900A | |||||||||
| 1600A | |||||||||
| 1250A | |||||||||
| 1000A | |||||||||
| 800A |
| Breaker Model | ATA2000 | ||||
| Frame-rated Current Ipm (A) | 2000 | ||||
| Rated Operating Current In (A) | 800 | 1000 1250 1600 | 1900 2000 | ||
| Rated Operating Voltage Ue (V) | AC230, AC400, AC690 | ||||
| Rated Frequency Hz | 50/60Hz | ||||
| Rated Insulation Voltage Ui (V) | 1000 | ||||
| Rated Impulse Withstand Voltage Uimp (kV) | 12 | ||||
| Number of Poles (P) | 3 | ||||
| Total Breaking Time (ms) | ≤30 | ||||
| Closing Time (ms) | ≤60 | ||||
| Rated Ultimate Short-Circuit Breaking Capacity Icu (kA) (RMS) | AC230V | 65 | |||
| AC400V | 50 | ||||
| AC690V | 40 | ||||
| Rated Service Short-Circuit Breaking Capacity Ics (kA) (RMS) | AC230V | 65 | |||
| AC400V | 50 | ||||
| AC690V | 40 | ||||
| Rated Short-Time Withstand Current Icw(1s) (kA) (RMS) | AC230V | 65 | |||
| AC400V | 50 | ||||
| AC690V | 40 | ||||
| Operating Performance (Times) | Electrical Life | AC230V, AC400V | 10000 | ||
| AC690V | 5000 | ||||
| Mechanical Life | Maintenance-free | 10000 | |||
| Maintenance-Required | 20000 | ||||
| Installation Type | Fixed Type | ||||
| Main Circuit Wiring Method | Fixed Type | Horizontal Wiring / Vertical Wiring | |||
| Overall Dimensions: W×H×D mm | 362×402×355 | ||||
| Weight (kg) | 41.5 | 43 | 45 | ||
Product Structure
The circuit breaker has a compact structure, small volume, and features three-dimensional separation. The contact system is enclosed in an insulated base and bottom plate with a partition structure. Each phase contact is separated to form individual small chambers. The intelligent controller, operating mechanism, handle, and motor operating mechanism are arranged in sequence in front of it to form independent units.
1. Fixed-type Circuit Breaker
The fixed-type circuit breaker consists of the circuit breaker body and fixed installation side plates. The fixed installation side plates are used to install and fix the relative position of the circuit breaker in the switch cabinet.
2. Structure Diagram of Fixed-type Circuit Breaker
Intelligent Controller
Power Supply Conditions for Normal Operation of the Intelligent Controller:
The working power of the intelligent controller is supplied by current transformers and an auxiliary power supply. To ensure reliable operation at small currents and reliable breaking in case of faults, a dual-power simultaneous supply method is adopted, as follows:
1. Circuit Breaker CT Power Supply
Power is supplied through the current transformer (CT) inside the circuit breaker. The normal working conditions of the controller are as follows: For the M-type controller (2000A frame circuit breaker): When the rated current In of the circuit breaker is greater than 400A, the single-phase primary current of the main circuit is not less than 0.8In, and the three-phase primary current is not less than 0.4In; when In = 400, the single-phase primary current is not less than 1.0In, and the three-phase primary current is not less than 0.6In.
2. Auxiliary Power Supply
Terminals 1 and 2 of the controller are for the auxiliary power supply. The normal working condition of the controller is (85% - 110%) Ue. AC or DC power supply voltages: AC230V, AC400V, DC220V, DC110V. When connecting the power supply, connect to the power supply suitable for the controller. When using functions such as ground protection, communication, thermal memory, or requiring the circuit breaker to maintain input and output signals in the open state, an auxiliary power supply must be equipped.
3. Panel Power Supply
For the M-type controller, power can also be connected through the DC24V power terminal on the panel. It is used when there is no power in the grid or during no-load operation, and the controller has no power supply, to check the controller (normal status, parameters, etc.). Voltage at the test port: DC24V ± 5%.
Basic Functions
Basic Protection Functions and Characteristics of the Intelligent Controller
Overload Long-delay Protection Characteristics
| Model | Setting Current Ir1 Adjustment Range | Operating Time TL Accuracy ±15% | ||||||
|---|---|---|---|---|---|---|---|---|
| M | (0.4~1.0)In + OFF Type L (adjusted incrementally as 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1.0); Type M (adjusted incrementally at 5%) | ≤1.05Ir1 | >2h Not operate | |||||
| >1.3Ir1 | <1h Operate | |||||||
| Setting Value (tL) | 15s | 30s | 60s | 120s | 240s | 480s | ||
| 1.5Ir1 | 15s | 30s | 60s | 120s | 240s | 480s | ||
| 2.0Ir1 | 8.4s | 16.9s | 33.8s | 67.5s | 135s | 270s | ||
| 7.2Ir1 | 0.65s | 1.3s | 2.6s | 5.2s | 10s | 21s | ||
| Note: The operating time TL satisfies: TL=(1.5 Ir1)² tL/I² | ||||||||
| Thermal Memory Function (30min + OFF, can be cleared by power failure) | Standard + OFF (Shut-off) | |||||||
Characteristic Curves
- (1) Standard Inverse Time-Limit (SI)
- (2) Very Inverse Time-Limit (VI)
- (3) Extremely Inverse Time-Limit (Distribution Protection) (EI (G))
- (4) Extremely Inverse Time-Limit (Motor Protection) (EI (M))
- (5) High-Voltage Fuse Compatibility (HV)
- (6) I²t Curve
Short-circuit Short-delay Protection Characteristics
M Intelligent Controller
| Setting Current Ir2 Adjustment Range | Operating Time Ts | ||
|---|---|---|---|
| 1.5~10 Ir1+OFF Current Accuracy: ±10% |
Inverse Time-Limit | Same as overload long-delay, but curve speed is 10 times faster. Accuracy: 15% | |
| Definite Time-Limit | Setting Time ts | 0.1s~0.4s | |
| Accuracy | ±10% (Inherent 40ms) | ||
| Thermal Memory Function (30min, can be cleared by power failure) | Standard + OFF (Shut-off) | ||
Short-circuit Instantaneous Protection Characteristics
| Model | Ir3 | Accuracy |
|---|---|---|
| M | 2In~50kA+OFF | Current Accuracy: ±15% |

CBRM5EL Automatic Reclosing MCCB
CBRM3EL Remote Reclosing MCCB
CBRM5E Intelligent MCCB
CBRM5EKd Electronic MCCB
CBRM5Kd Compact MCCB
CBRM5K Lockable MCCB
CBRM5EN Primary-secondary Separated MCCB
CBRECB Meter Remote Control MCCB
CBRB7BL Type B Smart RCBO
CBRB7 Compact MCB
CBRB7-AP PV Grid-connected MCB
CBRW3 4000A ACB
CBRW3 2500A ACB
CBRW3 1600A ACB