High Breaking Capacity 1600A Air Circuit Breaker (ACB) - China Suppliers & Factory Solutions

Introducing the D&T CBRW3 Intelligent Air Circuit Breaker, a leading product from one of the top suppliers in China. This state-of-the-art circuit breaker is designed to operate across a wide voltage range from AC 220V to 1140V, ensuring reliable and efficient power distribution for various applications. Built with a robust insulated structure and an advanced arc-extinguishing system, it boasts high breaking capacity and stability, Our intelligent air circuit breaker features an innovative energy storage mechanism that guarantees consistent performance. The integrated intelligent controller provides precise selective protection, real-time monitoring, fault recording, and supports multiple communication protocols, Available in both fixed and withdrawable options, as well as 3- or 4-pole versions, the D&T CBRW3 ensures flexible wiring and enhanced safety interlocks, making it an ideal choice for industrial applications and new energy power systems. As a trusted factory, we are committed to delivering high-quality products that meet the needs of our clients globally

    Normal Operating and Installation Conditions

    • Ambient air temperature: The upper limit shall not exceed +55°C, and the lower limit shall not be lower than -5°C.
    • Altitude: The altitude of the installation site shall not exceed 2000m. Reference can be made to the high-altitude derating coefficient.
    • Atmospheric conditions: When the ambient air temperature is +55°C, the relative humidity of the air shall not exceed 50%. At lower temperatures, higher humidity is allowed. For example, at +20°C, it can reach 90%. Special measures shall be taken for condensation occasionally generated due to temperature changes.
    • Pollution level: Level 3.
    • Installation category: The installation category of the main circuit (including the under-voltage release coil) is Category IV; the control circuit and auxiliary circuit are Category III.
    • Installation conditions: The circuit breaker shall be installed as required by the instruction manual, and the vertical inclination of the circuit breaker shall not exceed 5°.
    • Installation protection class requirements: IP30, IP40 (installed in the cabinet compartment, with additional door frames and organic glass covers).
    • Service category: B

    Product Features

    • The contact system is installed in the insulation part compartment. Each phase contact system adopts a multi-path sheet-like structure, realizing electric force compensation and ensuring the high breaking capacity of the circuit breaker.
    • The advanced arc-extinguishing system and protective cover ensure "zero flying arc", making the product safer.
    • The circuit breaker is operated by an energy-storage mechanism for energy storage, with a fast closing speed.
    • The operating mechanism is installed in the center of the front of the circuit breaker, completely separated from the main circuit. It can make each phase have a stable and consistent final contact pressure, which plays an important role in ensuring temperature rise and breaking indicators.
    • The centered operating mechanism is convenient for symmetrical hole-opening in the center of the cabinet door of the complete set, improving the appearance quality of the complete set of cabinets.
    • It can be installed with bottom incoming lines, and has horizontal and vertical wiring methods.
    • Intelligent controller with multiple protection functions, enabling selective protection.

    Model and Description

    ATA 2000 / 2000A / 3P / Intelligent Controller Model M / Operating Voltage of the Intelligent Circuit: AC380V, AC220V, DC220V, DC110V
    1900A
    1600A
    1250A
    1000A
    800A
    Model and Description
    Breaker Model ATA2000
    Frame-rated Current Ipm (A) 2000
    Rated Operating Current In (A) 800 1000 1250 1600 1900 2000
    Rated Operating Voltage Ue (V) AC230, AC400, AC690
    Rated Frequency Hz 50/60Hz
    Rated Insulation Voltage Ui (V) 1000
    Rated Impulse Withstand Voltage Uimp (kV) 12
    Number of Poles (P) 3
    Total Breaking Time (ms) ≤30
    Closing Time (ms) ≤60
    Rated Ultimate Short-Circuit Breaking Capacity Icu (kA) (RMS) AC230V 65
    AC400V 50
    AC690V 40
    Rated Service Short-Circuit Breaking Capacity Ics (kA) (RMS) AC230V 65
    AC400V 50
    AC690V 40
    Rated Short-Time Withstand Current Icw(1s) (kA) (RMS) AC230V 65
    AC400V 50
    AC690V 40
    Operating Performance (Times) Electrical Life AC230V, AC400V 10000
    AC690V 5000
    Mechanical Life Maintenance-free 10000
    Maintenance-Required 20000
    Installation Type Fixed Type
    Main Circuit Wiring Method Fixed Type Horizontal Wiring / Vertical Wiring
    Overall Dimensions: W×H×D mm 362×402×355
    Weight (kg) 41.5 43 45

    Product Structure

    The circuit breaker has a compact structure, small volume, and features three-dimensional separation. The contact system is enclosed in an insulated base and bottom plate with a partition structure. Each phase contact is separated to form individual small chambers. The intelligent controller, operating mechanism, handle, and motor operating mechanism are arranged in sequence in front of it to form independent units.

    1. Fixed-type Circuit Breaker

    The fixed-type circuit breaker consists of the circuit breaker body and fixed installation side plates. The fixed installation side plates are used to install and fix the relative position of the circuit breaker in the switch cabinet.

    2. Structure Diagram of Fixed-type Circuit Breaker

    Product Structure Diagram

    Intelligent Controller

    Power Supply Conditions for Normal Operation of the Intelligent Controller:

    The working power of the intelligent controller is supplied by current transformers and an auxiliary power supply. To ensure reliable operation at small currents and reliable breaking in case of faults, a dual-power simultaneous supply method is adopted, as follows:

    1. Circuit Breaker CT Power Supply

    Power is supplied through the current transformer (CT) inside the circuit breaker. The normal working conditions of the controller are as follows: For the M-type controller (2000A frame circuit breaker): When the rated current In of the circuit breaker is greater than 400A, the single-phase primary current of the main circuit is not less than 0.8In, and the three-phase primary current is not less than 0.4In; when In = 400, the single-phase primary current is not less than 1.0In, and the three-phase primary current is not less than 0.6In.

    2. Auxiliary Power Supply

    Terminals 1 and 2 of the controller are for the auxiliary power supply. The normal working condition of the controller is (85% - 110%) Ue. AC or DC power supply voltages: AC230V, AC400V, DC220V, DC110V. When connecting the power supply, connect to the power supply suitable for the controller. When using functions such as ground protection, communication, thermal memory, or requiring the circuit breaker to maintain input and output signals in the open state, an auxiliary power supply must be equipped.

    3. Panel Power Supply

    For the M-type controller, power can also be connected through the DC24V power terminal on the panel. It is used when there is no power in the grid or during no-load operation, and the controller has no power supply, to check the controller (normal status, parameters, etc.). Voltage at the test port: DC24V ± 5%.

    Basic Functions

    Basic Protection Functions and Characteristics of the Intelligent Controller

    Basic Functions Diagram 1
    Basic Functions Diagram 2
    Intelligent Universal Circuit Breaker

    Overload Long-delay Protection Characteristics

    Model Setting Current Ir1 Adjustment Range Operating Time TL Accuracy ±15%
    M (0.4~1.0)In + OFF Type L (adjusted incrementally as 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1.0); Type M (adjusted incrementally at 5%) ≤1.05Ir1 >2h Not operate
    >1.3Ir1 <1h Operate
    Setting Value (tL) 15s 30s 60s 120s 240s 480s
    1.5Ir1 15s 30s 60s 120s 240s 480s
    2.0Ir1 8.4s 16.9s 33.8s 67.5s 135s 270s
    7.2Ir1 0.65s 1.3s 2.6s 5.2s 10s 21s
    Note: The operating time TL satisfies: TL=(1.5 Ir1)² tL/I²
    Thermal Memory Function (30min + OFF, can be cleared by power failure) Standard + OFF (Shut-off)

    Characteristic Curves

    • (1) Standard Inverse Time-Limit (SI)
    • (2) Very Inverse Time-Limit (VI)
    • (3) Extremely Inverse Time-Limit (Distribution Protection) (EI (G))
    • (4) Extremely Inverse Time-Limit (Motor Protection) (EI (M))
    • (5) High-Voltage Fuse Compatibility (HV)
    • (6) I²t Curve
    Characteristic Curves Diagram

    Short-circuit Short-delay Protection Characteristics

    M Intelligent Controller

    Setting Current Ir2 Adjustment Range Operating Time Ts
    1.5~10 Ir1+OFF
    Current Accuracy: ±10%
    Inverse Time-Limit Same as overload long-delay, but curve speed is 10 times faster. Accuracy: 15%
    Definite Time-Limit Setting Time ts 0.1s~0.4s
    Accuracy ±10% (Inherent 40ms)
    Thermal Memory Function (30min, can be cleared by power failure) Standard + OFF (Shut-off)

    Short-circuit Instantaneous Protection Characteristics

    Model Ir3 Accuracy
    M 2In~50kA+OFF Current Accuracy: ±15%

    Frequently Asked Questions (FAQ)

    What are the ambient operating temperature limits for the circuit breaker?

    The ambient air temperature for normal operation must have an upper limit not exceeding +55°C, and the lower limit must not be lower than -5°C.

    What is the maximum installation altitude for the ATA2000?

    The altitude of the installation site should not exceed 2000 meters. For higher altitudes, reference can be made to the high-altitude derating coefficient.

    What protection classes are required for the installation of the circuit breaker?

    The installation protection class requirements are IP30 and IP40 (when installed in the cabinet compartment, with additional door frames and organic glass covers).

    What are the wiring methods supported by the fixed-type circuit breaker?

    The fixed-type circuit breaker supports both horizontal and vertical main circuit wiring methods, and can be installed with bottom incoming lines.

    When does the intelligent controller require an auxiliary power supply?

    An auxiliary power supply must be equipped when using functions such as ground protection, communication, thermal memory, or when the circuit breaker needs to maintain input and output signals in the open state.

    What is the difference in mechanical life with and without maintenance?

    The mechanical life of the circuit breaker is 10,000 operations when maintenance-free, and up to 20,000 operations when regular required maintenance is performed.