China Suppliers Factory CBRM5EL Compact Automatic Reclosing Circuit Breaker with Residual Current Protection (MCCB)

The residual current circuit breaker series is designed for high-performance applications, featuring a rated insulation voltage of 1000V. Ideal for three-phase AC systems operating at a frequency of 50Hz and rated for 400V, these circuit breakers can handle rated currents of up to 630A. When integrated into distribution networks, the four-wire neutral point is effectively grounded, offering indirect contact protection. This essential safety device mitigates fire risks associated with ground fault currents caused by insulation failures. It ensures the reliable distribution of electrical energy, safeguarding lines and power equipment against hazards such as overload, undervoltage, short circuits, and single-phase grounding faults. As a leading supplier and factory in China, we are committed to delivering high-quality solutions that enhance safety and efficiency in your electrical systems

    Residual Current Protection (RCD) Circuit Breaker (Smart Reclosing)

    Product Model and Meaning

    Product Model and Meaning

    Meets standards

    The product meets the following standards.
    GB/T14048.1-2012 Low voltage switchgear and control equipment Part 1: General principles;
    GB/T14048.2-2008 Low-voltage switchgear and control equipment Part 2: Circuit breakers;
    GB/T1770 1-2008 <Equipment circuit breakers>.

    Main functions and features

    • Adopt high-performance 32-bit ARM microprocessor, real-time signal processing and intelligent control; LCD Chinese display, user-friendly interface, easy operation;
    • The residual current (leakage current) protection can be adjusted online, and has the function of reclosing;
    • Real-time monitoring and tracking of the residual current of the line, automatic adjustment of the range, to ensure the operation rate and reliability of the product;
    • Three-stage protection, long delay, short delay and instantaneous, using electronic trip, independent of power supply voltage;
    • It has high breaking capacity and ensures the reliability of line short circuit protection. Overvoltage protection, undervoltage protection, phase loss protection;
    • The residual current of the line, the three-phase power supply voltage and the load current are displayed in real time;
    • Protective functions and parameters can be set and modified online.
    • Trip types (residual current, lockout, overload, undervoltage, overvoltage, phase loss) are identified, displayed, and can be stored, queried, and deleted;
    • The network has communication function, which can realize remote signal, remote measurement, remote control and remote adjustment.
    • Plug-and-play lightning protection module (optional).
    • Supports infrared communication (optional).

    Key technical specifications

    Specifications and models CERM5EL-125CY
    CBRM5EL-125CS
    CERM5EL-250CY
    CRRM5EL-250CS
    CBRM5EL-400CY
    CBRM5EL-400CS
    CBRM5EL-630CY
    CRRM5EL-630CS
    Rated current of the shell frame class (A) 125 250 400 630
    Number of poles 3P+N 3P+N 3P+N 3P+N
    Rated working voltage Ue (V) AC 400/50HZ
    Rated insulation voltage Ui(V) 800 1000
    Rated impulse withstand voltage Uimp(V) 8000
    Flashover distance(mm) ≠50 ≠100
    Maximum short-circuit breaking capacity (lcu, kA) 50 65 85
    Operating short-circuit breaking capacity (les, kA) 35 42 65
    Rated residual short-circuit breaking capacity I△m (kA) 12.5 16.25 21.25
    Rated short-time withstand current (LCW) in kA/s 1.5 3 5 8
    RCD trip characteristics AC mould
    Rated residual operating current I△n (mA) 50/100/200/300/400/500/600/800
    MCU automatically tacks or manually sets any value
    100/200/300/400/500
    600/800/1000 MCU
    automatic trucking or
    manual setting
    Remaining motion time characteristics Delayed/non-delayed
    Delay-type limit non-drive time (s) 0.06:21△n
    Break-time(s) I△n≤≤0.5;21△n≤0.2:51△n≤0.15
    Automatic reclosing time (s) 20-60
    Operation performance (times) Set up an electric circuit 1500 1000 1000
    No power 8500 7000 1000
    Total 10000 8000 5000
    Overload and short-circuit characteristics Three stage protection with electronic adjustment, See "Protection Characteristics" for details.
    Over-voltage protection value (V) Set value (250~300)±5%
    Under-voltage protection value (V) Set value (145-200)±5%
    Control delay time (ms) ≤40ms
    Communication delay (ms) ≤200ms

    Protection feature description

    ◆Overload and long delay protection

    Action value range
    Table 1:Overload Long Delay Parameter Settings

    Parameter Shroud current Set value Factory set value
    Action set-point Irl 125 50A、63A、80A、100A、125A 125A
    250 100A、125A、140A、160A、180A、200A、225A、250A 250A
    400 160A、180A、200A、225A、250A、315A、350A、400A 400A
    630 250A、315A、350A、400A、500A、630A 630A
    Delay time setting value tL 3s,4s,6s,8s, 10s,12s,16s, 18s, OFF 12s

    ◆Performance characteristic
    Table 2: Protection Action Characteristics

    Ambient temperature Current name Set current multiplier Appointed time
    +40℃ Conventional non tripping current 1.051r1 ≥2h
    Conventional tripping current 1.3Ir1 <2h

    ◆Time-delay characteristics
    The overload protection is based on the inverse time characteristic.
    The delay time is calculated as T=(6lrl/l) x L, with a tolerance of+10%.Here,T represents the action time, lrl is the long delay protection setting, i denotes the fault current, and L stands for the long delay time setting.

    ◆Short circuit short delay protection

    Short delay protection prevents impedance short circuit in the power distribution sytem. and the trip delay is to achieve selective protection.Short-circuit short delay protection parameter settings.
    Table 3: Short-Circuit Delay Parameter Setting

    Parameter setting Set value Factory set value
    Short delay action current setting Ir2 2Irl,2.5lrl,3Irl,4lrl,5Ir1,6lIrl,7Irl,8lrl,10Irl,12lr 6lr1
    Short delay time setting value ts 10.1s,0.2s,0.3s,0.4s,0.6s,0.8s,1.0s,OFF 0.4s

    Short-circuit short delay protection action characteristics
    Table 4:Short Delay Action Characteristics of Short Circuit

    Characteristic Fault current multiple Trip characteristics Delay error
    No action feature ≤0.85 Ir2 Failure to actuate /
    Performance characteristic >1.15 Ir2 Deferred action ±40ms

    ◆Instant Protection

    Set parameters for instantaneous short-circuit protection
    Table 5:Instantaneous parameter setting

    Parameter setting Set value Factory set value
    Instantaneous action current setting Ir3 4 Irl,6 Irl,7 Irl,8 Irl,9 Irl,10 Irl,11 Irl,12 Irl,13 Irl,14 Irl,OFF 10 Ir1

    Instantaneous short-circuit protection characteristics
    Table 6:Instantaneous Motion Characteristics

    Characteristic Current multiplier (1/r3) Trip characteristics Trip time
    No action feature ≤0.85 Failure to actuate ≥200ms
    Performance characteristic >1. 15 Movement <200ms

    ◆Setting range for residual current protection characteristics

    Table 7

    Parameter Set value (125.250,400) Set value (630) Factory set value
    Remaining motion current IΔn 50,100,200,300,400500,600,800.automatic 100,200,300,400,500,600,800.1000automatic 500

    ◆Performance characteristic
    Table 8: Protection Action Characteristics

    Parameter Characteristic
    Rated no-load current 0.5IΔn
    Rated operating current ≥0.751Δn
    Time-delay characteristics 2IΔn Limit Time (Δt) Break-time
    IΔn 2IΔn 5IΔn
    Non-delay ≤0.3s ≤0.15s ≤0.04s
    0.06 ≥0.06s ≤0.5s ≤0.2s ≤0.15s

    ◆Auto mode
    In automatic gear mode, the gear values and floating values are:

    Gauge reading (mA) Floating value (mA)
    50 25
    100 50
    200 100
    300 150
    400 200
    500 250
    600 300
    800 400
    1000 -

    When the residual current exceeds the floating threshold of a setting without reaching its activation level and remains stable for 60 seconds, the setting is raised by one level. This process continues until reaching the maximum setting. Conversely, when the residual current falls below the floating threshold of the next lower setting and remains stable for 120 seconds, the setting is lowered by one level. This sequence repeats until the minimum setting is reached. Taking the 'Auto 2' setting with an initial residual current of 100mA as an example: When the circuit breaker is energized, the setting automatically resets to 300mA. If the residual current increases above 150mA and remains stable for 60 seconds, the setting changes to 500mA. When the residual current decreases below 150mA and stays stable for 120 seconds, the setting adjusts to 200mA.

    ◆Autoreclose circuit breaker
    When the residual current exceeds the set trip current threshold, the circuit breaker will trip. After 20-60 seconds, it can automatically reclose, though manual reclosing is unrestricted. If the fault current disappears within 5 seconds after reclosing, the operation is successful and the breaker resumes normal operation. If the fault persists, the breaker will trip again and remain locked, preventing automatic reclosing. In such cases, manual reclosing must be performed.

    ◆Over-voltage protection
    When the line phase voltage exceeds the overvoltage protection setting, the circuit breaker trips. Once the voltage returns to normal, the circuit breaker automatically recloses and resumes operation. The overvoltage protection setting ranges from 250V to 300V, with a factory default of 275V. Users can adjust or disable the protection as needed.

    ◆Undervoltage protection
    When the phase voltage falls below the undervoltage protection setting, the circuit breaker trips. Once the voltage returns to normal, the breaker automatically recloses. The undervoltage protection range is 145V to 200V, with a factory default of 145V. Users can adjust or disable the protection as needed.

    ◆Phase loss protection function
    When a phase is missing at the power supply end of the line, the circuit breaker protection trips. When the line is restored to normal voltage, the circuit breaker can be automatically closed and put into operation.

    Outline Overall and Installing Dimensions

    Outline Overall and Installing Dimensions 1
    Outline Overall and Installing Dimensions 2
    Outline Overall and Installing Dimensions 3
    Outline Overall and Installing Dimensions 4

    characteristic curve

    ◆Linked protection function
    The Linkage lnterface Can Be Used to Coordinate With Other Fire Fighting Equipment for Protection as Follows.

    IN input settings Function declaration Priority Delay time
    Input control IN1 is short-circuited to DCOM Circuit breaker closed Low ≤40ms
    IN3 is short-circuited to DCOM Trip the circuit breaker Gao ≤40ms

    Note: Prolonged short-circuiting will keep the circuit breaker in the open state.

    operating time

    Frequently Asked Questions (FAQ)

    What is the primary function of the Smart Reclosing RCD Circuit Breaker?
    It provides comprehensive electrical protection, including residual current (leakage) protection, overload, short-circuit, overvoltage, undervoltage, and phase loss protection. It features automatic reclosing to restore power automatically after transient faults.
    How does the automatic reclosing function handle persistent line faults?
    If a fault persists after the circuit breaker automatically recloses (within 20-60 seconds), the breaker will trip again and remain locked in the open position. Automatic reclosing is then disabled, and manual intervention is required to reset and close the breaker.
    Can the protection parameters and settings be adjusted online?
    Yes, the protective parameters—including residual current limits, overload thresholds, overvoltage/undervoltage limits, and delay times—can be configured, modified, and monitored online via the user-friendly LCD screen or communication interfaces.
    What standards does this circuit breaker comply with?
    The circuit breaker is designed and manufactured in compliance with GB/T14048.1-2012 (General principles for low-voltage switchgear), GB/T14048.2-2008 (Low-voltage circuit breakers), and GB/T17701-2008 (Equipment circuit breakers).
    Does this device support remote control and smart grid integration?
    Yes, the breaker features advanced network communication capabilities that support remote signaling, remote measurement, remote control, and remote parameter adjustment. Optional infrared communication is also supported.