China Suppliers Factory CBRM5EKd Electronic Adjustable Circuit Breaker MCCB with LCD Display - High Breaking Capacity
Product Model & Description
- Type A: The N pole is not equipped with an overcurrent release and remains permanently connected; it does not open or close together with the other three poles.
- Type B: The N pole is not equipped with an overcurrent release but opens and closes together with the other three poles (N pole closes first and opens last).
Operating Environment
◆ The upper limit of ambient air temperature shall not exceed +40°C, the lower limit shall not be lower than -5°C, and the average temperature within 24 hours shall not exceed +35°C. Note: When the ambient air temperature exceeds +40°C or falls below -5°C, the use of the circuit breaker should be subject to agreement with the manufacturer.
◆ Installation altitude shall not exceed 2000 m.
◆ The relative humidity of the atmosphere shall not exceed 50% at the maximum ambient temperature of +40°C. Higher relative humidity is allowed at lower temperatures (e.g., 90% at 20°C), with consideration given to condensation that may occur due to temperature changes on the product surface.
◆ Installation category: Category Ⅲ for the main circuit, Category Ⅱ for the control and auxiliary circuits.
◆ Installation orientation: Generally installed vertically (upright), but horizontal (flat-mounted) installation is also permissible.
◆ Pollution degree: Degree 3.
◆ External magnetic field: The external magnetic field in the installation location shall not exceed 5 times the geomagnetic field in any direction.
Trip Unit Types & Accessory Codes
Main Technical Parameters
Model |
CBRM5Kd-125i |
CBRM5Kd-160 |
CBRM5Kd-250 |
CBRM5Kd-400 |
CBRM5Kd-800 |
||||||||||||||||
Frame Size Current Inm(A) |
125 |
160 |
250 |
400、630 |
800 |
||||||||||||||||
Rated Current In(A) |
16、20、25、30、32、40、50、63、70、75、80、90、100、125 |
16、20、25、30、32、40、50、63、70、75、80、90、100、125、140、150、160 |
100、125、140、150、160、175、180、200、225、250 |
225、250、280、300、315、350、400、500、550、630 |
630、700、800 |
||||||||||||||||
Number of Poles |
3 |
4 |
3 |
4 |
3 |
4 |
3 |
4 |
3 |
4 |
|||||||||||
Rated Insulation Voltage Ui(V) |
1000 |
||||||||||||||||||||
Rated Operation Voltage Ue(V) |
AC380、AC400、AC415 |
AC380、AC400、AC415、AC660、AC690 |
|||||||||||||||||||
Rated Impulse Withstand Voltage Uimp(kV) |
8 |
12 |
|||||||||||||||||||
Arc Distance(mm) |
50 |
100 |
|||||||||||||||||||
Breaking Capacity Level |
L |
M |
H |
L |
M |
H |
L |
M |
H |
L |
M |
H |
L |
M |
H |
||||||
Ultimate Short-Circuit Breaking Capacity Icu(kA) AC380V/AC400V/AC415V |
10 |
18 |
25 |
25 |
36 |
50 |
36 |
50 |
70 |
50 |
70 |
100 |
50 |
70 |
100 |
||||||
Service Short-Circuit Breaking Capacity Ics(kA) AC380V/AC400V/AC415V |
10 |
18 |
25 |
25 |
36 |
50 |
36 |
50 |
70 |
50 |
70 |
100 |
50 |
70 |
100 |
||||||
Ultimate Short-Circuit Breaking Capacity Icu(kA) AC660V/AC690V |
- |
- |
- |
8 |
10 |
10 |
10 |
10 |
10 |
10 |
15 |
20 |
15 |
20 |
20 |
||||||
Service Short-Circuit Breaking Capacity Ics(kA) AC660V/AC690V |
- |
- |
- |
4 |
5 |
5 |
5 |
5 |
5 |
10 |
15 |
15 |
13 |
15 |
15 |
||||||
Operating Performance (operations) |
Energized |
1500 |
1500 |
1000 |
1000 |
500 |
|||||||||||||||
De-energized |
8500 |
8500 |
7000 |
4000 |
2500 |
||||||||||||||||
Total |
10000 |
10000 |
8000 |
5000 |
3000 |
||||||||||||||||
Protection Characteristics
Rated Current (A) |
Thermal Trip Unit (Ambient Temp +40) |
Magnetic Trip Unit Operating Current (A) |
|
1.05In(Cold State) Non-Tripping Time (h) |
1.3In (Hot State) Tripping Time (h) |
||
10≤In≤63 |
No Tripping Within 1 hour |
≤1 |
10In±20% |
63<In≤800 |
No Tripping Within 2 hours |
≤2 |
|
Rated Current (A) |
Thermal Trip Unit (Ambient Temp +40) |
Magnetic Trip Unit Operating Current (A) |
||||
1.0In(Cold State)Non-Tripping Time (h) |
1.2In(Hot State) Tripping Time (h) |
1.5In(Hot State) Tripping Time (h) |
7.2In(Cold State)Tripping Time (h) |
Trip Level |
||
10≤In≤25 |
No Tripping Within 2 hours |
≤2 |
≤2min |
0.5s<Tp≤5s |
5 |
12In±20% |
25<In≤250 |
≤4min |
4s<Tp≤10s |
10 |
|||
250<In≤800 |
≤8min |
6s<Tp≤20s |
20 |
|||
Circuit Breaker Classification
- By Number of Poles: Three-Pole, Four-Pole
- By Application: For Distribution, For Motor Protection
- By Operating Method: Direct Handle Operation, Electric Operation (indicated by "p"), Rotary Handle Operation for Switchgear (indicated by "Z")
Frequently Asked Questions (FAQ)
A1: For Type A, the N pole is not equipped with an overcurrent release, remains permanently connected, and does not open or close together with the other three poles. For Type B, the N pole is also not equipped with an overcurrent release, but it opens and closes together with the other three poles (closing first and opening last).
A2: The installation altitude for these circuit breakers must not exceed 2000 meters.
A3: The normal ambient air temperature should be within the range of -5°C to +40°C, and the average temperature over a 24-hour period must not exceed +35°C. For temperatures outside this range, usage must be agreed upon with the manufacturer.
A4: Yes. Although the circuit breaker is generally designed to be installed vertically (upright), horizontal (flat-mounted) installation is also permissible.
A5: The letter "p" indicates Electric Operation, and the letter "Z" indicates Rotary Handle Operation for switchgear.
A6: The rated insulation voltage (Ui) for these circuit breaker models is 1000V.

CBRM5EL Automatic Reclosing MCCB
CBRM3EL Remote Reclosing MCCB
CBRM5E Intelligent MCCB
CBRM5EKd Electronic MCCB
CBRM5Kd Compact MCCB
CBRM5K Lockable MCCB
CBRM5EN Primary-secondary Separated MCCB
CBRECB Meter Remote Control MCCB
CBRB7BL Type B Smart RCBO
CBRB7 Compact MCB
CBRB7-AP PV Grid-connected MCB
CBRW3 4000A ACB
CBRW3 2500A ACB
CBRW3 1600A ACB