China CBRM5KdE Electronic Adjustable MCCB Suppliers - Ultra-Compact Circuit Breaker Factory with High Breaking Capacity
Product Model & Description
Four-Pole Product Codes
Type A: The N pole is not equipped with an overcurrent release and remains permanently connected; it does not open or close together with the other three poles.
Type B: The N pole is not equipped with an overcurrent release but opens and closes together with the other three poles (N pole closes first and opens last).
Operating Environment
Normal Operating Conditions
- The upper limit of ambient air temperature shall not exceed +40°C, the lower limit shall not be lower than -5°C, and the average temperature within 24 hours shall not exceed +35°C. (Note: Special agreements with the manufacturer are required if temperatures exceed these limits).
- Installation altitude shall not exceed 2000 m.
- The relative humidity of the atmosphere shall not exceed 50% at the maximum ambient temperature of +40°C. Higher relative humidity is allowed at lower temperatures (e.g., 90% at 20°C), considering condensation due to temperature changes.
Normal Installation Conditions
- Installation category: Category Ⅲ for the main circuit, Category Ⅱ for the control and auxiliary circuits.
- Installation orientation: Generally installed vertically (upright), but horizontal (flat-mounted) installation is also permissible.
- Pollution degree: Degree 3.
- External magnetic field: Shall not exceed 5 times the geomagnetic field in any direction at the installation location.
Trip Unit Types & Accessory Codes
Main Technical Parameters
| Model | CBRM5Kd-125i | CBRM5Kd-160 | CBRM5Kd-250 | CBRM5Kd-400 / CBRM5Kd-630i | CBRM5Kd-800 | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Frame Size Current Inm(A) | 125 | 160 | 250 | 400, 630 | 800 | ||||||||||||||||
| Rated Current In(A) | 16, 20, 25, 30, 32, 40, 50, 63, 70, 75, 80, 90, 100, 125 | 16, 20, 25, 30, 32, 40, 50, 63, 70, 75, 80, 90, 100, 125, 140, 150, 160 | 100, 125, 140, 150, 160, 175, 180, 200, 225, 250 | 225, 250, 280, 300, 315, 350, 400, 500, 550, 630 | 630, 700, 800 | ||||||||||||||||
| Number of Poles | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | |||||||||||
| Rated Insulation Voltage Ui(V) | 1000 | ||||||||||||||||||||
| Rated Operation Voltage Ue(V) | AC380, AC400, AC415 | AC380, AC400, AC415, AC660, AC690 | |||||||||||||||||||
| Rated Impulse Withstand Voltage Uimp (kV) | 8 | 12 | |||||||||||||||||||
| Arc Distance(mm) | 50 | 100 | |||||||||||||||||||
| Breaking Capacity Level | L | M | H | L | M | H | L | M | H | L | M | H | L | M | H | ||||||
| Ultimate Short-Circuit Breaking Capacity Icu(kA) AC380V/AC400V/AC415V |
10 | 18 | 25 | 25 | 36 | 50 | 36 | 50 | 70 | 50 | 70 | 100 | 50 | 70 | 100 | ||||||
| Service Short-Circuit Breaking Capacity Ics(kA) AC380V/AC400V/AC415V |
10 | 18 | 25 | 25 | 36 | 50 | 36 | 50 | 70 | 50 | 70 | 100 | 50 | 70 | 100 | ||||||
| Ultimate Short-Circuit Breaking Capacity Icu(kA) AC660V/AC690V |
- | - | - | 8 | 10 | 10 | 10 | 10 | 10 | 10 | 15 | 20 | 15 | 20 | 20 | ||||||
| Service Short-Circuit Breaking Capacity Ics(kA) AC660V/AC690V |
- | - | - | 4 | 5 | 5 | 5 | 5 | 5 | 10 | 15 | 15 | 13 | 15 | 15 | ||||||
| Operating Performance (operations) | Energized | 1500 | 1500 | 1000 | 1000 | 500 | |||||||||||||||
| De-energized | 8500 | 8500 | 7000 | 4000 | 2500 | ||||||||||||||||
| Total | 10000 | 10000 | 8000 | 5000 | 3000 | ||||||||||||||||
Protection Characteristics
For Distribution Applications
| Rated Current (A) | Thermal Trip Unit (Ambient Temp +40°C) | Magnetic Trip Unit Operating Current (A) | |
|---|---|---|---|
| 1.05In (Cold State) Non-Tripping Time (h) | 1.3In (Hot State) Tripping Time (h) | ||
| 10 ≤ In ≤ 63 | No Tripping Within 1 hour | ≤ 1 | 10In ± 20% 160 Frame, 16-32A: 400A ± 20% |
| 63 < In ≤ 800 | No Tripping Within 2 hours | ≤ 2 | |
For Motor Protection
| Rated Current (A) | Thermal Trip Unit (Ambient Temp +40°C) | Magnetic Trip Unit Operating Current (A) | ||||
|---|---|---|---|---|---|---|
| 1.0In (Cold State) Non-Tripping Time (h) | 1.2In (Hot State) Tripping Time (h) | 1.5In (Hot State) Tripping Time (h) | 7.2In (Cold State) Tripping Time (h) | Trip Level | ||
| 10 ≤ In ≤ 25 | No Tripping Within 2 hours | ≤ 2 | ≤ 2 min | 0.5s < Tp ≤ 5s | 5 | 12In ± 20% 160 Frame, 16-32A: 400A ± 20% |
| 25 < In ≤ 250 | ≤ 4 min | 4s < Tp ≤ 10s | 10 | |||
| 250 < In ≤ 800 | ≤ 8 min | 6s < Tp ≤ 20s | 20 | |||
Circuit Breaker Classification
By Number of Poles
- Three-Pole
- Four-Pole
By Application
- For Distribution
- For Motor Protection
By Operating Method
- Direct Handle Operation
- Electric Operation (indicated by "p")
- Rotary Handle Operation for Switchgear (indicated by "Z")
Frequently Asked Questions (FAQ)
Q1: What is the normal operating temperature range for the circuit breaker?
The ambient air temperature should be between -5°C and +40°C, with a 24-hour average not exceeding +35°C. If your application requirements fall outside this range, please consult the manufacturer.
Q2: Can the CBRM5Kd circuit breaker be installed at high altitudes?
Yes, the device is rated for installation at altitudes up to 2000 meters under normal operating conditions.
Q3: What is the difference between Type A and Type B four-pole configurations?
In Type A, the N pole is permanently connected and does not open or close with the other three poles. In Type B, the N pole does not have an overcurrent release but is designed to open and close together with the other three poles (closing first and opening last).
Q4: Are horizontal installations allowed for this circuit breaker series?
Yes. While the standard installation orientation is vertical (upright), horizontal (flat-mounted) installation is also permissible.
Q5: What are the available operating methods?
The circuit breakers can be operated via three methods: Direct Handle Operation, Electric Operation (coded as "p"), or Rotary Handle Operation for Switchgear (coded as "Z").
Q6: What is the relative humidity limit for safe operation?
The relative humidity should not exceed 50% at the maximum temperature of +40°C. Higher humidity (such as 90% at 20°C) is acceptable at lower temperatures, provided condensation on the product surface is managed.

CBRM5EL Automatic Reclosing MCCB
CBRM3EL Remote Reclosing MCCB
CBRM5E Intelligent MCCB
CBRM5EKd Electronic MCCB
CBRM5Kd Compact MCCB
CBRM5K Lockable MCCB
CBRM5EN Primary-secondary Separated MCCB
CBRECB Meter Remote Control MCCB
CBRB7BL Type B Smart RCBO
CBRB7 Compact MCB
CBRB7-AP PV Grid-connected MCB
CBRW3 4000A ACB
CBRW3 2500A ACB
CBRW3 1600A ACB