China CBRM5KdE Electronic Adjustable MCCB - High Breaking Capacity Circuit Breaker from Quality Suppliers & Factory

,

D&T CBRM5KD MCCB is a compact circuit breaker designed to deliver high breaking capacity, conforming to IEC 60947-2 standards and certified by DEKRA for safety and performance. Manufactured in China, our factory utilizes advanced technology to ensure superior quality and reliability.

,

The dual-cover design of the CBRM5KD MCCB promotes safe isolation of live parts, making the installation of accessories straightforward and secure. As one of the leading suppliers in the industry, we prioritize safety and user experience.

,

Equipped with an automated production line featuring automatic screw fastening, precision laser marking, and comprehensive automated testing systems, every unit is rigorously tested. We ensure that each MCCB undergoes 100% automated testing for trip force, overtravel, contact gap, loop resistance, final contact pressure, power-frequency withstand voltage, and tripping characteristics, guaranteeing consistent and dependable performance.

,

    Product Model & Description

    Product Model & Description

    Four-Pole Product Codes:

    Type A

    The N pole is not equipped with an overcurrent release and remains permanently connected; it does not open or close together with the other three poles.

    Type B

    The N pole is not equipped with an overcurrent release but opens and closes together with the other three poles (N pole closes first and opens last).

    Operating Environment

    Normal Operating Conditions

    • The upper limit of ambient air temperature shall not exceed +40°C, the lower limit shall not be lower than -5°C, and the average temperature within 24 hours shall not exceed +35°C. (Note: When the ambient air temperature exceeds +40°C or falls below -5°C, the use of the circuit breaker should be subject to agreement with the manufacturer).
    • Installation altitude shall not exceed 2000 m.
    • The relative humidity of the atmosphere shall not exceed 50% at the maximum ambient temperature of +40°C. Higher relative humidity is allowed at lower temperatures (e.g., 90% at 20°C), with consideration given to condensation that may occur due to temperature changes on the product surface.

    Normal Installation Conditions

    • Installation category: Category Ⅲ for the main circuit, Category Ⅱ for the control and auxiliary circuits.
    • Installation orientation: Generally installed vertically (upright), but horizontal (flat-mounted) installation is also permissible.
    • Pollution degree: Degree 3.
    • External magnetic field: The external magnetic field in the installation location shall not exceed 5 times the geomagnetic field in any direction.

    Trip Unit Types & Accessory Codes

    Trip Unit Types & Accessory Codes
    Trip Unit Types & Accessory Codes Details

    Main Technical Parameters

    Model CBRM5Kd-125i CBRM5Kd-160 CBRM5Kd-250 CBRM5Kd-400
    CBRM5Kd-630i
    CBRM5Kd-800
    Frame Size Current Inm(A) 125 160 250 400, 630 800
    Rated Current In(A) 16, 20, 25, 30, 32, 40, 50, 63, 70, 75, 80, 90, 100, 125 16, 20, 25, 30, 32, 40, 50, 63, 70, 75, 80, 90, 100, 125, 140, 150, 160 100, 125, 140, 150, 160, 175, 180, 200, 225, 250 225, 250, 280, 300, 315, 350, 400, 500, 550, 630 630, 700, 800
    Number of Poles 3 4 3 4 3 4 3 4 3 4
    Rated Insulation Voltage Ui(V) 1000
    Rated Operation Voltage Ue(V) AC380, AC400, AC415 AC380, AC400, AC415, AC660, AC690
    Rated Impulse Withstand Voltage Uimp (kV) 8 12
    Arc Distance(mm) 50 100
    Breaking Capacity Level L M H L M H L M H L M H L M H
    Ultimate Short-Circuit Breaking Capacity Icu(kA) AC380V/AC400V/AC415V 10 18 25 25 36 50 36 50 70 50 70 100 50 70 100
    Service Short-Circuit Breaking Capacity Ics(kA) AC380V/AC400V/AC415V 10 18 25 25 36 50 36 50 70 50 70 100 50 70 100
    Ultimate Short-Circuit Breaking Capacity Icu(kA) AC660V/AC690V - - - 8 10 10 10 10 10 10 15 20 15 20 20
    Service Short-Circuit Breaking Capacity Ics(kA) AC660V/AC690V - - - 4 5 5 5 5 5 10 15 15 13 15 15
    Operating Performance (operations) Energized 1500 1500 1000 1000 500
    De-energized 8500 8500 7000 4000 2500
    Total 10000 10000 8000 5000 3000

    Protection Characteristics

    For Distribution Applications

    Rated Current (A) Thermal Trip Unit (Ambient Temp +40°C) Magnetic Trip Unit Operating Current (A)
    1.05In (Cold State) Non-Tripping Time (h) 1.3In (Hot State) Tripping Time (h)
    10 ≤ In ≤ 63 No Tripping Within 1 hour ≤ 1 10In ± 20%
    160 Frame, 16-32A: 400A ± 20%
    63 < In ≤ 800 No Tripping Within 2 hours ≤ 2

    For Motor Protection

    Rated Current (A) Thermal Trip Unit (Ambient Temp +40°C) Magnetic Trip Unit Operating Current (A)
    1.0In (Cold State) Non-Tripping Time (h) 1.2In (Hot State) Tripping Time (h) 1.5In (Hot State) Tripping Time (h) 7.2In (Cold State) Tripping Time (h) Trip Level
    10 ≤ In ≤ 25 No Tripping Within 2 hours ≤ 2 ≤ 2 min 0.5s < Tp ≤ 5s 5 12In ± 20%
    160 Frame, 16-32A: 400A ± 20%
    25 < In ≤ 250 ≤ 4 min 4s < Tp ≤ 10s 10
    250 < In ≤ 800 ≤ 8 min 6s < Tp ≤ 20s 20

    Circuit Breaker Classification

    • By Number of Poles: Three-Pole, Four-Pole
    • By Application: For Distribution, For Motor Protection
    • By Operating Method: Direct Handle Operation, Electric Operation (indicated by "p" ), Rotary Handle Operation for Switchgear (indicated by "Z" )

    Frequently Asked Questions

    What is the difference between Type A and Type B four-pole circuit breakers?
    Type A has an N pole without an overcurrent release that is permanently connected and does not open or close with the other three poles. Type B also has no overcurrent release on the N pole, but it opens and closes together with the other three poles, closing first and opening last.
    What are the altitude and temperature requirements for normal operation?
    The installation altitude must not exceed 2000 meters. The normal operating ambient temperature range is -5°C to +40°C, with a 24-hour average not exceeding +35°C. For operations outside these limits, contact the manufacturer.
    What is the rated insulation voltage (Ui) of the CBRM5Kd series?
    The rated insulation voltage (Ui) for the CBRM5Kd series circuit breakers is 1000V.
    How are these circuit breakers classified by operating methods?
    They can be operated in three ways: Direct Handle Operation, Electric Operation (marked with "p"), or Rotary Handle Operation for Switchgear (marked with "Z").
    What installation conditions must be met regarding magnetic fields and pollution?
    The installation site must have a pollution degree of 3. Additionally, the external magnetic field in any direction at the installation location must not exceed 5 times the geomagnetic field.