China CBRM5EN Primary-Secondary Separated MCCB Circuit Breaker - 400V, 630A, IoT Suppliers and Factory Solutions

The China-made smart IoT circuit breaker is engineered with a rated insulation voltage of 1000V, specifically tailored for three-phase four-wire power distribution systems. Operating at a frequency of 50Hz AC with a rated voltage of 400V and capable of supporting currents up to 630A, this innovative device ensures reliable indirect contact protection. It effectively prevents fire hazards caused by ground fault currents due to equipment insulation damage, thereby enhancing safety while distributing electrical energy efficiently. As a leading choice among suppliers, our factory guarantees quality and performance for all your circuit protection needs

    CBRM5E Low-voltage intelligent circuit breaker with automatic reclasing

    Product Model and Meaning

    Product model and meaning.jpg

    Scope of Application

    The smart IoT circuit breaker features a rated insulation voltage of 1000V, designed for three-phase four-wire power distribution systems; Operating at 50Hz AC with a rated voltage of 400V and rated current up to 630A. It provides indirect contact protection, prevents fire hazards caused by ground fault currents from equipment insulation damage, and distributes electrical energy while protecting circuits against overloads and short circuits. Additionally, it offers protection against line overvoltage, undervoltage, and phase loss.

    • GB/T14048.2 "Low-voltage switchgear and control equipment".
    • GB/T22710 Electronic Controller for Low Voltage Circuit Breakers.

    Main Features and Characteristics

    • It employs a high-performance 32-bit ARM microprocessor for real-time signal processing and intelligent control.
    • LCD display in Chinese/English, user-friendly interface, easy operation;
    • Features automatic reclosing; fast closing speed, with a closing time of ≤2s;
    • Three-stage protection, long delay, short delay and instantaneous, using electronic trip, independent of power supply voltage;
    • High breaking capacity to ensure the reliability of line short circuit protection;
    • Overvoltage protection, undervoltage protection, phase loss protection, zero loss protection, protection functions and parameters can be set and modified online;
    • Real-time display of three-phase power supply voltage and load current;
    • Identify and display trip types (remote lockout, overload, undervoltage, overvoltage, undervoltage, phase loss, zero-segment break, etc.), and store, query, and delete them.
    • Supports four remote functions: remote signaling, telemetry, remote control, and remote adjustment.
    • HPLC plug-and-play module with Bluetooth wireless communication for low-power operation;
    • 0.05In-1.2In measurement accuracy up to 1.0 grade;
    • The parameters such as active power, reactive power, apparent power and power factor are measured in real time, and the three-phase active power is accumulated;
    • Time control, cost control and other modes are optional, and the application is more flexible;
    • Supports DL/T645 and Modbus protocols with automatic recognition.
    • Real-time temperature monitoring of incoming line terminal strips (optional);
    • Supports online remote upgrades for easy maintenance and updates;
    • Accuracy class: Current and voltage accuracy up to 0.5s class; active and reactive power accuracy up to 1 class;
    • Supports active power demand limit, reactive power demand limit, current mutation event, current interruption, voltage harmonic content, current harmonic content, voltage waveform distortion, current waveform distortion;
    • Passive island protection (optional);
    • Terminal and contact over temperature protection (optional);
    • Power generation quality monitoring and protection (optional);
    • Three-phase unbalanced monitoring and protection of power generation current (optional).

    Service Environment

    • The installation site should be free of conductive dust, corrosive gas, flammable and explosive gas, and rain and snow invasion;
    • Altitude: not higher than 2000m;
    • Ambient temperature: -5℃~+40℃, daily average maximum temperature: ≤+35℃;
    • Relative humidity: ≤50% (at ambient temperature of +40℃);
    • The strength of the external magnetic field in any direction at the installation site is not more than 5 times that of the geomagnetic field;
    • The installation position should have good ventilation and heat dissipation;
    • When HPLC (wide band carrier) communication is required, ensure all communication devices operate under a single transformer.

    Circuit breaker classification

    Functional classification

    Conventional type

    Quantitative

    Photovoltaic

    Defencive function

    Overload protection

    Short-circuit protection

    Autoreclose circuit breaker

    Phase loss protection

    Overvoltage crowbar

    Undervoltage protection

    Zero-loss protection

    Over/under frequency protection

    Power-off protection

    Phase Sequence Protection

    Island Protection

    Over temperature Protection

    Power quality monitoring and protection

    Measurements

    Three-phase working voltage

    Three-phase working current

    Active power

    Reactive power

    Apparent output

    Voltage imbalance

    Unbalanced current

    Performance Settings

    Long delay due to overload

    Short circuit delay

    Instantaneous short circuit

    Overvoltage protection value

    Undervoltage protection value

    Time, date

    Protect investment and exit

    Phase loss protection value

    Over/under frequency protection value

    Voltage imbalance protection value

    Unbalanced current protection value

    Information Query

    Action records, fault records

    Communication

    RS-485/ Modbus

    Signal carrier

    PDA

    Topology

    ● Indicates the feature is available; △ indicates the feature is optional; ○ indicates the feature is not available.

    Key Technical Specifications

    Specifications and models

    125

    250

    400

    630

    Rated current of the shell frame class (A)

    125

    250

    400

    630

    Number of poles

    3P/4P

    Rated working voltage Ue(V)

    AC 400/50HZ

    Rated insulation voltage Ui(V)

    1000

    Rated impulse withstand voltage Uimp (V)

    8000

    Flashover distance (mm)

    ≯50

    100

    Maximum short-circuit breaking capacity(Icu,kA)

    25(S) 36(L) 50(M)

    36(S) 35(L) 50(M)35(S)

    65(L) 70(M)

    50(S) 65(L) 70(M)

    Operating short-circuit breaking capacity(Ics,kA)

    20(S) 25(L) 35(M)25(S)

    35(L)

    35(M) 35(S) 42(L)

    50(M) 50(S) 50(L) 70(M)

    Rated short-time current Icw (kA)/s

    1.5

    3

    5

    8

    Automatic closing time (S)

    ≤2s

    Operation performance (times)

    Set up an electric circuit

    1500

    1000

    1000

    1000

    No power

    8500

    7000

    4000

    4000

    Total

    10000

    8000

    5000

    5000

    Overload and short-circuit characteristics

    Three-stage protection with electronic adjustment. See "Protection Characteristics" for details.

    Overvoltage protection value (V)

    Set value (231-330)/Default value 275V

    Undervoltage protection value(V)

    Set value (88~209)/ Default value 145Y

    Phase loss protection value (V)

    Set value (10--130)/Default value 30V

    Control delay time (ms)

    ≤40ms

    Communication delay (ms)

    ≤200ms

    Measurement Accuracy Class

    accuracy

    Tolerance

    Current accuracy

    ±0.5%、±1.0%

    Voltage accuracy

    ±0.5%、±1.0%

    Active power accuracy

    ±1.0%、±1.5%、2.0%、2.5%

    Reactive power accuracy

    ±1.0%、±1.5%、2.0%、2.5%

    Protection Feature Description

    Overload and long delay protection
    The circuit breaker shall provide overload and short circuit protection, as well as photovoltaic power generation system island protection and power quality monitoring protection, and all protection functions shall support remote configuration.

    1. Long delay setting value (lr) range for over-current

    The current setting (lr) ranges from 0.4 to 1In, with OFF indicating the protection function is disabled. The time delay characteristic follows the IEC standard inverse time curve, with K factor=0.14, α factor=0.02, and L factor=0. The current I is set, while Is represents the rated current. TMS setting range: 1-10s. The long delay protection action of over-current should meet the requirements of Table 1.

    Table 1: Over-current long delay protection action table

    Short delay action current (lsd)

    Movement

    ≤lr

    Normal operation

    1lr~1.5lr

    After 10 minutes of continuous monitoring, the system will automatically report overload alarms and record data. If the current remains excessive after 10 minutes, the system will take further action.

    ≥1.5lr

    After 5 minutes of continuous monitoring, if the current remains excessive, disconnect the connection point and report the issue.

    Note: 1. The 3Ir value is conservative, with time and current parameters configured in the switch unit.

    ◆ Performance Characteristic

    1. Short delay setting value(Isd) range for over current
    Short-time operating current(Isd) range: 1.5 to 5Ir, OFF. OFF means the protection function can be disabled. The delay action is time-limited, with a set range of 1-10 seconds. The short delay protection action of overcurrent should meet the requirements of Table 2.

    Table 2: Overcurrent short delay protection action table

    Short delay action current (lsd)

    Movement

    ≤k1lr

    Normal operation

    k1lr~k2lr

    Normal operation. The system actively reports over current alarms and records data.

    ≥k2lr

    Continuously monitor the tlsd time. If the current remains excessive after the tlsd time, disconnect the connection point and report the issue.

    Note: kl and k2 are set to 1.5~5lr, with kl < k2. The time and current values are configured in the switch's main unit.

    2. Rated short-circuit current setting (li) range

    The rated instantaneous short-circuit current setting (Ii) ranges from 2 to 12Ir, with OFF indicating the protection function is disabled. The circuit breaker current protection operation shall meet the requirements of Table 3.

    Table 3: Short circuit current protection action table

    Short-circuit current

    Movement

    ≥5~8Ir

    Cut off the connection point in 0.2s and report

    3. The three-stage protection characteristic curve is shown below:

    Operation time.jpg

    ◆ Excess Voltage Protection

    The overvoltage protection voltage setting (Uov) ranges from 1.05 to 1.5 times the rated voltage (Un). The OFF setting enables the protection function to be disabled. The delay action is time-limited, with the tUov setting range being 1 to 9999 seconds. The over voltage protection operation shall meet the requirements of Table 5.

    Table 5: Overvoltage protection action table

    Maximum three-phase voltage

    Movement

    ≤234.5V

    Normal operation

    >234.5V

    Disconnect the node after 2 seconds and report

    Note: 1. OFF means you can disable this protection feature.
    2. While monitoring the voltage amplitude change, the auxiliary monitoring voltage frequency change is carried.

    ◆ Low-voltage Protection

    The molded case circuit breaker does not have this feature. The undervoltage protection voltage setting (Uuv) ranges from 0.4 to 0.9sUn. The OFF setting enables or disables this protection function. The delay action is time-limited, with tUuv adjustable from 1 to 9999 seconds. The low voltage protection action shall meet the requirements of Table 6.

    Table 6: Under voltage protection action table

    Maximum three-phase voltage

    Movement

    ≥187V

    Normal operation

    <187V

    Disconnect the node after 2 seconds and report

    Note: 1. OFF means you can disable this protection feature.
    2. While monitoring the voltage amplitude change, the auxiliary monitoring voltage frequency change is carried out. If the voltage frequency is basically unchanged, the above criteria are used for over-voltage protection.

    ◆ Terminal and Contact Over Temperature Protection

    The temperature protection setting (Tem) range for terminals and contacts is 80~160°C, with OFF indicating the protection function is disabled. The delay action is time limited, with t Tem set within the range of 1 to 9999 seconds. Terminal and contact over temperature protection action shall meet the requirements of Table 7.

    Table 7: Terminal and contact overheating protection action table

    Terminal and contact temperature

    Movement

    ≤60℃

    Normal operation

    60℃~90℃

    Operates normally, actively reports terminal and contact overheating alarms and records data

    ≥90℃

    After 60 seconds of continuous monitoring, the terminal and contact temperature remained above the limit. The connection point was disconnected and reported.

    ≥110℃

    Cut off the connection point in 0.2s and report

    Note: The temperature detection point is near the incoming and outgoing wire terminals.

    ◆ Passive Island Protection

    The passive detection method primarily identifies islanding status by monitoring the amplitude, frequency, phase, and harmonic content of the inverter's common mode voltage output. Key components include over/under-voltage protection, over/under-frequency protection, phase abrupt change detection, and harmonic detection. The set values for passive island detection criteria are: Voltage amplitude swing(dUisl): 0.1 to 0.9Un, OFF; voltage frequency swing(dFisl): 0.5 to 25Hz, OFF. Voltage phase swing(dPHisl): 1~60, OFF; Voltage waveform distortion rate swing(dUTHDisl): 0.5~30%, OFF. The delay action is time-limited, with the set time tPis adjustable within the range of 0.01 to 9.99 seconds. The passive island protection action shall meet the requirements of Table 8.

    Table 8: Passive island protection action table

    Criterion fluctuation value

    Movement

    Voltage amplitude swing or swing range

    If the voltage amplitude fluctuates beyond 20V or deviates from the [187V, 234.5V] range within 100ms, the system identifies an island.

    Voltage frequency swing or swing range

    If the voltage frequency fluctuation exceeds 0.2Hz or the fluctuation exceeds the [49.5Hz~50.2Hz] range within 100ms, the island is determined.

    Note: 1. The swing range refers to the difference between the maximum and minimum swing values within a period of time;
    2. The above criteria are primarily based on voltage-frequency oscillation, with voltage-amplitude oscillation as a secondary factor. When the voltage-frequency oscillation criterion is met, the connection point shall be disconnected within 2 seconds and reported.

    ◆ Power Generation Quality Monitoring and Protection

    The power generation harmonic monitoring and protection action shall meet the requirements of Table 9.

    Table 9: Current harmonic and protection action comparison table

    Total current distortion rate

    Movement

    ≤5%

    Normal network connection

    >5%

    After 60 seconds of continuous monitoring, if the harmonic levels remain above the limit, disconnect the connection point and report the issue.

    Note: OFF means you can disable this protection feature.

    ◆ Three-phase Power Generation Imbalance Monitoring and Protection (applicable to three-phase grid-connected access)

    The three-phase unbalanced protection of power generation current shall meet the requirements of Table 10.

    Table 10: Negative sequence three-phase current imbalance rate and protection action

    Three-phase current imbalance rate

    Movement

    ≤2%

    Normal network connection

    >2%

    After 60 seconds of continuous monitoring, if the imbalance rate remains above the threshold, disconnect the connection point and report the issue.

    Note: OFF means you can disable this protection feature.

    ◆ Undervoltage Protection

    The circuit breaker trips when the phase voltage falls below the undervoltage protection setting. Once the voltage returns to normal, the breaker automatically recloses. The undervoltage protection range is 88V to 209V, with a factory default of 187V. Users can adjust or disable the protection as needed.

    ◆ Phase Loss Protection

    When a phase is missing at the power output of the line, the circuit breaker protection trips. Once the line recovers to normal voltage, it can automatically close and resume operation. The phase loss protection setting ranges from 10V to 130V, with a factory default of 30V. Users can adjust or disable the protection as needed.

    ◆ Autoreclose Circuit Breaker

    After the line voltage exceeds the limit and trips, the line voltage will be automatically reclosed after 5s when the line voltage returns to normal, but the manual closing is not limited by time.

    ◆ External Control or Dynamic Protection Function

    External control or dynamic protection function.jpg
    Note: S1 is a passive dry node;
    When the product is in use and no external control is applied, short S1 or disable the software's external control function.

    ◆ Cost Control

    This product can be connected to a fee-controlled meter as an external circuit breaker, compatible with both pulse-type and level-type fee-controlled meters. This feature requires configuring the switch to fee-controlled mode and enabling the "Allow" option. When operating in fee-controlled mode, the automatic protection function is disabled, preventing manual or automatic closing without a fee-controlled signal. Forced closing will automatically disconnect the circuit.

    Transportation and Storage

    Transportation

    • During transportation, protect products from water, rain, snow, or corrosive liquids. Avoid mixing or contact with such substances. Prevent violent impacts or compression between items. Stack products according to packaging directions, with no more than four layers.

    Keep in Storage

    • Storage environment: ambient temperature -10°C~+45°C
    • Relative humidity: ≤90% (at ambient temperature of +20°C)
    • The storage place should be free of dust and conductive dust
    • No corrosion, flammable and explosive gas, no rain or snow invasion
    • Good drying and ventilation
    • Stack according to the packaging instructions, not more than 4 layers.

    Matters Need Attention

    • The company does not assume the "three guarantees" responsibility for non-quality problems caused by improper installation and use and for terminal burnout caused by improper wiring.
    • If you encounter any issues during product use, please contact your local distributor or our customer service center.
    • Customer service hotline: 86 0577-62793566.

    Frequently Asked Questions (FAQ)

    What is the rated insulation voltage of the CBRM5E circuit breaker?
    The CBRM5E smart IoT circuit breaker features a rated insulation voltage of 1000V, designed for three-phase four-wire power distribution systems operating at 50Hz AC with a rated voltage of 400V.
    Does the circuit breaker support automatic reclosing?
    Yes, it features automatic reclosing with a fast closing speed of ≤2s. After a line voltage trip, it will automatically reclose after 5 seconds once the line voltage returns to normal.
    What communication protocols and interfaces are supported?
    It supports DL/T645 and Modbus protocols with automatic recognition, RS-485/Modbus communication, and features an HPLC plug-and-play module with Bluetooth wireless communication.
    What are the environmental requirements for storage?
    The storage environment should have an ambient temperature of -10°C to +45°C, relative humidity ≤90% (at +20°C), be free of dust and corrosive/flammable gases, and stacked no more than 4 layers high.
    What protection features are included for terminals and contacts?
    It offers optional terminal and contact over-temperature protection with a setting range of 80°C to 160°C. If temperatures reach ≥110°C, the connection point is cut off in 0.2 seconds to prevent damage.