China CBRM5EKd Adjustable Circuit Breaker with LCD Display - Reliable MCCB from Top Suppliers and Factory
Product Model & Description
Four-Pole Product Codes
- Type A: The N pole is not equipped with an overcurrent release and remains permanently connected; it does not open or close together with the other three poles.
- Type B: The N pole is not equipped with an overcurrent release but opens and closes together with the other three poles (N pole closes first and opens last).
Operating Environment
Normal Operating Conditions
- The upper limit of ambient air temperature shall not exceed +40°C, the lower limit shall not be lower than -5°C, and the average temperature within 24 hours shall not exceed +35°C. (Note: When the ambient air temperature exceeds +40°C or falls below -5°C, the use of the circuit breaker should be subject to agreement with the manufacturer).
- Installation altitude shall not exceed 2000 m.
- The relative humidity of the atmosphere shall not exceed 50% at the maximum ambient temperature of +40°C. Higher relative humidity is allowed at lower temperatures (e.g., 90% at 20°C), with consideration given to condensation that may occur due to temperature changes on the product surface.
Normal Installation Conditions
- Installation category: Category Ⅲ for the main circuit, Category Ⅱ for the control and auxiliary circuits.
- Installation orientation: Generally installed vertically (upright), but horizontal (flat-mounted) installation is also permissible.
- Pollution degree: Degree 3.
- External magnetic field: The external magnetic field in the installation location shall not exceed 5 times the geomagnetic field in any direction.
Trip Unit Types & Accessory Codes
Main Technical Parameters
| Model | CBRM5Kd-125i | CBRM5Kd-160 | CBRM5Kd-250 | CBRM5Kd-400 / CBRM5Kd-630i | CBRM5Kd-800 | ||||||||||||||||
| Frame Size Current Inm(A) | 125 | 160 | 250 | 400, 630 | 800 | ||||||||||||||||
| Rated Current In(A) | 16, 20, 25, 30, 32, 40, 50, 63, 70, 75, 80, 90, 100, 125 | 16, 20, 25, 30, 32, 40, 50, 63, 70, 75, 80, 90, 100, 125, 140, 150, 160 | 100, 125, 140, 150, 160, 175, 180, 200, 225, 250 | 225, 250, 280, 300, 315, 350, 400, 500, 550, 630 | 630, 700, 800 | ||||||||||||||||
| Number of Poles | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | |||||||||||
| Rated Insulation Voltage Ui(V) | 1000 | ||||||||||||||||||||
| Rated Operation Voltage Ue(V) | AC380, AC400, AC415 | AC380, AC400, AC415, AC660, AC690 | |||||||||||||||||||
| Rated Impulse Withstand Voltage Uimp(kV) | 8 | 12 | |||||||||||||||||||
| Arc Distance(mm) | 50 | 100 | |||||||||||||||||||
| Breaking Capacity Level | L | M | H | L | M | H | L | M | H | L | M | H | L | M | H | ||||||
| Ultimate Short-Circuit Breaking Capacity Icu(kA) AC380V/AC400V/AC415V | 10 | 18 | 25 | 25 | 36 | 50 | 36 | 50 | 70 | 50 | 70 | 100 | 50 | 70 | 100 | ||||||
| Service Short-Circuit Breaking Capacity Ics(kA) AC380V/AC400V/AC415V | 10 | 18 | 25 | 25 | 36 | 50 | 36 | 50 | 70 | 50 | 70 | 100 | 50 | 70 | 100 | ||||||
| Ultimate Short-Circuit Breaking Capacity Icu(kA) AC660V/AC690V | - | - | - | 8 | 10 | 10 | 10 | 10 | 10 | 10 | 15 | 20 | 15 | 20 | 20 | ||||||
| Service Short-Circuit Breaking Capacity Ics(kA) AC660V/AC690V | - | - | - | 4 | 5 | 5 | 5 | 5 | 5 | 10 | 15 | 15 | 13 | 15 | 15 | ||||||
| Operating Performance (operations) | Energized | 1500 | 1500 | 1000 | 1000 | 500 | |||||||||||||||
| De-energized | 8500 | 8500 | 7000 | 4000 | 2500 | ||||||||||||||||
| Total | 10000 | 10000 | 8000 | 5000 | 3000 | ||||||||||||||||
Protection Characteristics
For Distribution Applications
| Rated Current (A) | Thermal Trip Unit (Ambient Temp +40°C) | Magnetic Trip Unit Operating Current (A) | |
|---|---|---|---|
| 1.05In (Cold State) Non-Tripping Time (h) | 1.3In (Hot State) Tripping Time (h) | ||
| 10 ≤ In ≤ 63 | No Tripping Within 1 hour | ≤ 1 | 10In ± 20% 160 Frame, 16-32A: 400A ± 20% |
| 63 | No Tripping Within 2 hours | ≤ 2 | |
For Motor Protection
| Rated Current (A) | Thermal Trip Unit (Ambient Temp +40°C) | Magnetic Trip Unit Operating Current (A) | ||||
|---|---|---|---|---|---|---|
| 1.0In (Cold State) Non-Tripping Time (h) | 1.2In (Hot State) Tripping Time (h) | 1.5In (Hot State) Tripping Time (h) | 7.2In (Cold State) Tripping Time (h) | Trip Level | ||
| 10 ≤ In ≤ 25 | No Tripping Within 2 hours | ≤ 2 | ≤ 2 min | 0.5s | 5 | 12In ± 20% 160 Frame, 16-32A: 400A ± 20% |
| 25 | ≤ 4 min | 4s | 10 | |||
| 250 | ≤ 8 min | 6s | 20 | |||
Circuit Breaker Classification
- By Number of Poles: Three-Pole, Four-Pole.
- By Application: For Distribution, For Motor Protection.
- By Operating Method: Direct Handle Operation, Electric Operation (indicated by "p"), Rotary Handle Operation for Switchgear (indicated by "Z").
Frequently Asked Questions
What is the difference between Type A and Type B Four-Pole circuit breakers?
Type A has an N pole that is not equipped with an overcurrent release, remains permanently connected, and does not open or close together with the other three poles. Type B also lacks an overcurrent release on the N pole but opens and closes together with the other three poles (closing first and opening last).
What are the ambient temperature limits for normal operation?
The ambient air temperature must not exceed +40°C, and the lower limit must not be lower than -5°C. Additionally, the average temperature over a 24-hour period should not exceed +35°C. For operation outside these limits, user agreement with the manufacturer is required.
What is the maximum installation altitude for these circuit breakers?
The standard installation altitude for the circuit breakers should not exceed 2000 meters.
What are the relative humidity requirements for installation?
At the maximum temperature of +40°C, the relative humidity must not exceed 50%. Higher humidity levels are permitted at lower temperatures (e.g., 90% at 20°C), provided consideration is given to condensation on the product surface caused by temperature shifts.
What options are available for operating the circuit breakers?
They can be operated using a Direct Handle, via Electric Operation (indicated by "p"), or using a Rotary Handle Operation designed for switchgear (indicated by "Z").
What is the rated insulation voltage (Ui) of the CBRM5Kd series?
The rated insulation voltage (Ui) for the CBRM5Kd series circuit breakers is 1000V.

CBRM5EL Automatic Reclosing MCCB
CBRM3EL Remote Reclosing MCCB
CBRM5E Intelligent MCCB
CBRM5EKd Electronic MCCB
CBRM5Kd Compact MCCB
CBRM5K Lockable MCCB
CBRM5EN Primary-secondary Separated MCCB
CBRECB Meter Remote Control MCCB
CBRB7BL Type B Smart RCBO
CBRB7 Compact MCB
CBRB7-AP PV Grid-connected MCB
CBRW3 4000A ACB
CBRW3 2500A ACB
CBRW3 1600A ACB