China CBRM5 MCCB: Ultra-Compact Circuit Breaker with High Breaking Capacity | Trusted Suppliers & Factory

,

D&T CBRM5 MCCB is an ultra-compact circuit breaker that combines high breaking capacity with compliance to IEC 60947-2 standards. This product has been rigorously tested and holds a DEKRA certification, ensuring its safety and performance, making it a top choice among China suppliers.

,

At our factory, we leverage advanced technology including automatic screw fastening, precision laser marking, and fully automated testing systems. Each unit of our MCCB undergoes 100% automated testing for critical parameters such as trip force, overtravel, contact gap, loop resistance, final contact pressure, power-frequency withstand voltage, and tripping characteristics. This meticulous testing process guarantees consistent and reliable operation, confirming our status as leading suppliers in the industry.

,

    Product Model & Description

    CBRM5 Product Model and Description Diagram

    Operating Environment

    Normal Operating Conditions

    • Ambient Temperature: The upper limit of ambient air temperature shall not exceed +40°C, the lower limit shall not be lower than -5°C, and the average temperature within 24 hours shall not exceed +35°C. (Note: When the ambient air temperature exceeds +40°C or falls below -5°C, the use of the circuit breaker should be subject to agreement with the manufacturer.)
    • Installation Altitude: Shall not exceed 2000 m.
    • Atmospheric Humidity: The relative humidity of the atmosphere shall not exceed 50% at the maximum ambient temperature of +40°C. Higher relative humidity is allowed at lower temperatures (e.g., 90% at 20°C), with consideration given to condensation that may occur due to temperature changes on the product surface.

    Normal Installation Conditions

    • Installation Category: Category Ⅲ for the main circuit, Category Ⅱ for the control and auxiliary circuits.
    • Installation Orientation: Generally installed vertically (upright), but horizontal (flat-mounted) installation is also permissible.
    • Pollution Degree: Degree 3.
    • External Magnetic Field: The external magnetic field in the installation location shall not exceed 5 times the geomagnetic field in any direction.

    Trip Unit Types & Accessory Codes

    Trip Unit Types and Accessory Codes Part 1
    Trip Unit Types and Accessory Codes Part 2

    Main Technical Parameters

    Model CBRM5Kd-125i CBRM5Kd-160 CBRM5Kd-250 CBRM5Kd-400 / CBRM5Kd-630i CBRM5Kd-800
    Frame Size Current Inm(A) 125 160 250 400, 630 800
    Rated Current In(A) 16, 20, 25, 30, 32, 40, 50, 63, 70, 75, 80, 90, 100, 125 16, 20, 25, 30, 32, 40, 50, 63, 70, 75, 80, 90, 100, 125, 140, 150, 160 100, 125, 140, 150, 160, 175, 180, 200, 225, 250 225, 250, 280, 300, 315, 350, 400, 500, 550, 630 630, 700, 800
    Number of Poles 3 4 3 4 3 4 3 4 3 4
    Rated Insulation Voltage Ui(V) 1000
    Rated Operation Voltage Ue(V) AC380, AC400, AC415 AC380, AC400, AC415, AC660, AC690
    Rated Impulse Withstand Voltage Uimp(kV) 8 12
    Arc Distance(mm) 50 100
    Breaking Capacity Level L M H L M H L M H L M H L M H
    Ultimate Short-Circuit Breaking Capacity Icu(kA) AC380V/AC400V/AC415V 10 18 25 25 36 50 36 50 70 50 70 100 50 70 100
    Service Short-Circuit Breaking Capacity Ics(kA) AC380V/AC400V/AC415V 10 18 25 25 36 50 36 50 70 50 70 100 50 70 100
    Ultimate Short-Circuit Breaking Capacity Icu(kA) AC660V/AC690V - - - 8 10 10 10 10 10 10 15 20 15 20 20
    Service Short-Circuit Breaking Capacity Ics(kA) AC660V/AC690V - - - 4 5 5 5 5 5 10 15 15 13 15 15
    Operating Performance (operations) Energized 1500 1500 1000 1000 500
    De-energized 8500 8500 7000 4000 2500
    Total 10000 10000 8000 5000 3000

    Protection Characteristics

    For Distribution Applications

    Rated Current (A) Thermal Trip Unit (Ambient Temp +40°C) Magnetic Trip Unit Operating Current (A)
    1.05In (Cold State) Non-Tripping Time (h) 1.3In (Hot State) Tripping Time (h)
    10 ≤ In ≤ 63 No Tripping Within 1 hour ≤ 1 10In ± 20%
    160 Frame, 16-32A: 400A ± 20%
    63 < In ≤ 800 No Tripping Within 2 hours ≤ 2

    For Motor Protection

    Rated Current (A) Thermal Trip Unit (Ambient Temp +40°C) Magnetic Trip Unit Operating Current (A)
    1.0In (Cold State) Non-Tripping Time (h) 1.2In (Hot State) Tripping Time (h) 1.5In (Hot State) Tripping Time (h) 7.2In (Cold State) Tripping Time (h) Trip Level
    10 ≤ In ≤ 25 No Tripping Within 2 hours ≤ 2 ≤ 2min 0.5s < Tp ≤ 5s 5 12In ± 20%
    160 Frame, 16-32A: 400A ± 20%
    25 < In ≤ 250 ≤ 4min 4s < Tp ≤ 10s 10
    250 < In ≤ 800 ≤ 8min 6s < Tp ≤ 20s 20

    Circuit Breaker Classification

    • By Number of Poles: Three-Pole, Four-Pole
    • By Application: For Distribution, For Motor Protection
    • By Operating Method: Direct Handle Operation, Electric Operation (indicated by "p"), Rotary Handle Operation for Switchgear (indicated by "Z")

    Frequently Asked Questions (FAQ)

    Q1: What are the normal operating temperature limits for the CBRM5 circuit breaker?
    The ambient air temperature should be between -5°C and +40°C, with a 24-hour average temperature not exceeding +35°C. For conditions outside this range, please consult the manufacturer.
    Q2: Can the CBRM5 circuit breaker be installed horizontally?
    Yes. While vertical (upright) installation is standard, horizontal (flat-mounted) installation is also fully permissible.
    Q3: What is the maximum installation altitude for this circuit breaker?
    The installation altitude for normal operating conditions must not exceed 2000 meters.
    Q4: What pole options are available for the CBRM5 series?
    The CBRM5 series circuit breakers are classified and available in both Three-Pole and Four-Pole configurations.
    Q5: What are the different operating methods supported by the CBRM5 series?
    The circuit breakers can be operated via a Direct Handle, Electric Operation (denoted by "p"), or Rotary Handle Operation for Switchgear (denoted by "Z").
    Q6: How do the trip characteristics differ between distribution and motor protection models?
    Distribution models feature a magnetic trip unit operating current of 10In ±20% (with specific frame exceptions), whereas motor protection models are designed with a magnetic trip unit operating current of 12In ±20% to accommodate startup currents.