China CBRM5 MCCB - Ultra-Compact Circuit Breaker from Reliable Suppliers and Factory, IEC 60947-2 Certified

D&T CBRM5 MCCB is designed with an ultra-compact size and exceptional breaking capacity, adhering to IEC 60947-2 standards. Manufactured in our state-of-the-art factory, it proudly holds DEKRA certification, ensuring verified safety and superior performance.

,

As one of the leading suppliers from China, we utilize an advanced production line that includes automatic screw fastening, precision laser marking, and fully automated testing systems. Each unit undergoes comprehensive automated testing, covering trip force, overtravel, contact gap, loop resistance, final contact pressure, power-frequency withstand voltage, and tripping characteristics. This rigorous process guarantees consistent and reliable operation for all our customers.

    Product Model & Description
    CBRM5-1 Product Model and Description
    Operating Environment
    Normal Operating Conditions
    • The upper limit of ambient air temperature shall not exceed +40°C, the lower limit shall not be lower than -5°C, and the average temperature within 24 hours shall not exceed +35°C. Note: When the ambient air temperature exceeds +40°C or falls below -5°C, the use of the circuit breaker should be subject to agreement with the manufacturer.
    • Installation altitude shall not exceed 2000 m.
    • The relative humidity of the atmosphere shall not exceed 50% at the maximum ambient temperature of +40°C. Higher relative humidity is allowed at lower temperatures (e.g., 90% at 20°C), with consideration given to condensation that may occur due to temperature changes on the product surface.
    Normal Installation Conditions
    • Installation category: Category Ⅲ for the main circuit, Category Ⅱ for the control and auxiliary circuits.
    • Installation orientation: Generally installed vertically (upright), but horizontal (flat-mounted) installation is also permissible.
    • Pollution degree: Degree 3.
    • External magnetic field: The external magnetic field in the installation location shall not exceed 5 times the geomagnetic field in any direction.
    Trip Unit Types & Accessory Codes
    Trip Unit Types and Accessory Codes Part 1
    Trip Unit Types and Accessory Codes Part 2
    Main Technical Parameters
    Model CBRM5Kd-125i CBRM5Kd-160 CBRM5Kd-250 CBRM5Kd-400 / CBRM5Kd-630i CBRM5Kd-800
    Frame Size Current Inm(A) 125 160 250 400, 630 800
    Rated Current In(A) 16, 20, 25, 30, 32, 40, 50, 63, 70, 75, 80, 90, 100, 125 16, 20, 25, 30, 32, 40, 50, 63, 70, 75, 80, 90, 100, 125, 140, 150, 160 100, 125, 140, 150, 160, 175, 180, 200, 225, 250 225, 250, 280, 300, 315, 350, 400, 500, 550, 630 630, 700, 800
    Number of Poles 3 4 3 4 3 4 3 4 3 4
    Rated Insulation Voltage Ui(V) 1000
    Rated Operation Voltage Ue(V) AC380, AC400, AC415 AC380, AC400, AC415, AC660, AC690
    Rated Impulse Withstand Voltage Uimp(kV) 8 12
    Arc Distance(mm) 50 100
    Breaking Capacity Level L M H L M H L M H L M H L M H
    Ultimate Short-Circuit Breaking Capacity Icu(kA) AC380V/AC400V/AC415V 10 18 25 25 36 50 36 50 70 50 70 100 50 70 100
    Service Short-Circuit Breaking Capacity Ics(kA) AC380V/AC400V/AC415V 10 18 25 25 36 50 36 50 70 50 70 100 50 70 100
    Ultimate Short-Circuit Breaking Capacity Icu(kA) AC660V/AC690V - - - 8 10 10 10 10 10 10 15 20 15 20 20
    Service Short-Circuit Breaking Capacity Ics(kA) AC660V/AC690V - - - 4 5 5 5 5 5 10 15 15 13 15 15
    Operating Performance (operations) Energized 1500 1500 1000 1000 500
    De-energized 8500 8500 7000 4000 2500
    Total 10000 10000 8000 5000 3000
    Protection Characteristics
    For Distribution Applications
    Rated Current (A) Thermal Trip Unit (Ambient Temp +40°C) Magnetic Trip Unit Operating Current (A)
    1.05ln(Cold State) Non-Tripping Time (h) 1.3In (Hot State) Tripping Time (h)
    10 ≤ In ≤ 63 No Tripping Within 1 hour ≤ 1 10In ± 20%
    160 Frame, 16-32A: 400A ± 20%
    63 < In ≤ 800 No Tripping Within 2 hours ≤ 2
    For Motor Protection
    Rated Current (A) Thermal Trip Unit (Ambient Temp +40°C) Magnetic Trip Unit Operating Current (A)
    1.0In(Cold State) Non-Tripping Time (h) 1.2ln(Hot State) Tripping Time (h) 1.5ln(Hot State) Tripping Time (h) 7.2In(Cold State) Tripping Time (h) Trip Level
    10 ≤ In ≤ 25 No Tripping Within 2 hours ≤ 2 ≤ 2min 0.5s < Tp ≤ 5s 5 12In ± 20%
    160 Frame, 16-32A: 400A ± 20%
    25 < In ≤ 250 ≤ 4min 4s < Tp ≤ 10s 10
    250 < In ≤ 800 ≤ 8min 6s < Tp ≤ 20s 20
    Circuit Breaker Classification
    • By Number of Poles: Three-Pole, Four-Pole
    • By Application: For Distribution, For Motor Protection
    • By Operating Method: Direct Handle Operation, Electric Operation (indicated by "p"), Rotary Handle Operation for Switchgear (indicated by "Z")
    Frequently Asked Questions (FAQ)
    What are the ambient operating temperature limits for the CBRM5 circuit breaker?
    The ambient air temperature must not exceed +40°C, and the lower limit must not be lower than -5°C. Additionally, the average temperature over a 24-hour period should not exceed +35°C.
    Can the CBRM5 circuit breaker be installed horizontally?
    Yes. Although it is generally designed to be installed vertically (upright), horizontal (flat-mounted) installation is also fully permissible.
    What is the maximum installation altitude for these circuit breakers?
    The normal installation altitude for the CBRM5 circuit breaker should not exceed 2000 meters.
    What do the operating method codes "p" and "Z" represent?
    The letter "p" indicates Electric Operation, while the letter "Z" indicates Rotary Handle Operation for switchgear. Standard models feature Direct Handle Operation.
    What are the available pole configurations for the CBRM5?
    The CBRM5 circuit breaker is classified by its number of poles, which includes both Three-Pole (3P) and Four-Pole (4P) configurations.