Inquiry Now
Leave Your Message
Products Categories
Featured Products

China CBRM3EL Automatic Reclosing Circuit Breaker Suppliers with Residual Current Protection - Factory Direct Sales

The residual current circuit breaker, designed with a rated insulation voltage of 1000V, is ideal for three-phase AC systems. It features a rated voltage of 400V and supports rated currents of up to 80A. This advanced protection device is perfect for distribution networks where the neutral point is directly grounded (T). It provides essential indirect contact protection, significantly reducing fire risks associated with ground fault currents due to insulation failure. Additionally, it effectively distributes electrical energy while safeguarding lines and power equipment from potential threats such as overloads, under-voltage conditions, short circuits, and single-phase grounding faults. As a leading manufacturer and supplier from China, our factory ensures high-quality residual current circuit breakers that meet international standards, perfect for various industrial applications

    CBRM3EL Leakage Circuit Breaker

    Meets Standards

    The product meets the following standards:
    GB/T14048.1-2012 Low voltage switchgear and control equipment Part 1: General principles;
    GB/T14048.2-2008 Low-voltage switchgear and control equipment Part 2: Circuit breakers;
    GB/T17701-2008 <Equipment circuit breakers>.

    Main Functions and Features

    • Adopt high-performance 32-bit ARM microprocessor, real-time signal processing and intelligent control;
    • LCD Chinese display, user-friendly interface, easy operation;
    • The residual current (leakage current) protection can be adjusted online, and has the function of reclosing;
    • Real-time monitoring and tracking of the residual current of the line, automatic adjustment of the range, to ensure the operation rate and reliability of the product;
    • Three-stage protection, long delay, short delay and instantaneous, using electronic trip, independent of power supply voltage;
    • High breaking capacity to ensure the reliability of line short circuit protection;
    • Over-voltage protection, under-voltage protection, phase loss protection;
    • The residual current of the line, the three-phase power supply voltage and the load current are displayed in real time;
    • Protective functions and parameters can be set and modified online.
    • Trip types (residual current, lockout, overload, under-voltage, over-voltage, phase loss) are identified and displayed, and can be stored, queried, and deleted.
    • The network type has communication functions, which can realize remote signaling, remote measurement, remote control and remote adjustment.
    • Plug-and-play lightning protection module (optional)
    • Supports infrared communication (optional)

    Key Technical Specifications

    Specifications and models

    CBRV3F-125CY
    CRRV3EL-125CS

    CBRM3FI.-250CY
    CBRM3EL-250CS

    CBRM3EI.-400CY
    CBRM3EL-400CS

    CBRV3EL-630CY
    CBRM3EL 630CS

    CBRM3EL 800CY
    CBRM3EL-800CS

    Rated current of the shell frame class (A)

    125

    250

    400

    630

    800

    Number of poles

    3P+N

    3P+N,2P

    3P+N

    3P+N

    3P+N

    Rated working voltage Ue (V)

    AC 400/50HZ

    Rated insulation voltage Ui (V)

    1000

    Rated impulse withstand voltage Uimp (V)

    8000

    Flash-over distance(mm)

    ≠50

    ≠100

    Maximum short-circuit breaking capacity (lcu, kA)

    50 (H-type 70)

    65 (H-type 85)

    65

    Operating short-circuit breaking capacity (lcs, kA)

    35 (H-type 50)

    42 (H-type 65)

    42

    Rated residual short-circuit breaking capacity I△m (kA)

    12.5 (H-type 17.5)

    16.25 (H-type 21.5)

    16.25

    Rated short-time current Icw (kA)is

    1.5

    3

    5

    8

    10

    RCD trip characteristics

    AC mould

    Rated residual operating current I△n (mA)

    50/100/200/300/400/500/600/800MCU
    automatic tracking or manual setting

    100/200/300/400/500/600/800/1000
    MCU automatic tracking or manual

    Remaining motion time characteristics

    Delayed/non-delayed

    Delay-type limit non-drive time (s)

    0.06/0.1/0.2 Optional:21△n

    Break-time (s)

    I△≤0.5;2I△n≤0.2;51△n≤0.15

    Automatic reclosing time (s)

    20-60

    Operation performance (times)

    Set up an electric circuit

    1500

    1000

    1000

    500

    No power

    8500

    7000

    4000

    2500

    Total

    10000

    8000

    5000

    3000

    Overload and short-circuit characteristics

    Three-stage protection with electronic adjustment. See "Protection Characteristics" for details.

    Over-voltage protection value (V)

    Set value(250~300)±5%

    Under-voltage protection value (V)

    Set value (14S--200)±5%

    Control delay time (ms)

    ≤40ms

    Communication delay (ms)

    ≤200ms

    Protection Feature Description

    ◆Overload and long delay protection

    Action value range
    Table 1: Overload Long Delay Parameter Settings

    Parameter

    Shroud current

    Set value

    Factory set value

    Action set-point Irl

    125

    50A、63A、80A、100A、125A

    125A

    250

    100A、125A、140A、160A、180A、200A、225A、250A

    250A

    400

    160A、180A、200A、225A、250A、315A、350A、400A

    400A

    630

    250A、315A、350A、400A、500A、630A

    630A

    800

    315A、350A、400A、500A、630A、700A、800A

    800A

    Delay time setting value tL

    3s,4s,6s,8s,10s,12s,16s,18s,OFF

    12s

    ◆performance characteristic

    Table 2: Protection Action Characteristics

    Ambient temperature

    Current name

    Set current multiplier

    Appointed time

    +40℃

    Conventional non tripping current

    1.05Ir1

    ≥2h

    Conventional tripping current

    1.3Ir1

    <2h

    ◆time-delay characteristics

    The overload protection is based on the inverse time characteristic.
    The delay time T is calculated as (6rll, with a tolerance oft10%. Here, T represents the action time, Irl is the long delay protection setting, I denotes the fault current, and tL is the long delay time setting.

    ◆Short circuit short delay protection

    Short delay protection prevents impedance short circuit in the distribution system, and the trip delay is to achieve selective protection.
    Short-circuit short delay protection parameter settings
    Table 3: Short-circuit delay parameter setting

    Parameter setting

    Set value

    Factory set value

    Short delay action current setting lr2

    2Ir1,2.5lr1,3lr1,4lr1,5lr1,6lr1,7lrl,8lrl,10lr1,121r1

    6lr1

    Short delay time setting value ts

    0.1s,0.2s,0.3s,0.4s,0.6s,0.8s,1.0s,OFF

    0.4s

    Short-circuit short delay protection action characteristics
    Table 4: Short Delay Action Characteristics of Short Circuit

    Characteristic

    Fault current multiple

    Trip characteristics

    Delay error

    No action feature

    ≤0.85 Ir2

    Failure to actuate

    /

    Performance characteristic

    >1.15Ir2

    Deferred action

    ±40ms

    ◆Instant Protection

    Set parameters for instantaneous short-circuit protection
    Table 5: Instantaneous parameter setting

    Parameter setting

    Set value

    Factory set value

    Instantaneous action current setting lr3

    4 Irl,6 Irl,7 Irl,8 Irl, 10 Irl,11 Ir1,12 Irl,13 rl,14 rl,0FF

    10 Ir1

    Short-circuit instantaneous protection action characteristics
    Table 6: Instantaneous motion characteristics

    Characteristic

    Current ratio (I/r3)

    Trip characteristics

    Trip time

    No action feature

    ≤0.85

    Failure to actuate

    ≥200ms

    Performance characteristic

    >1.15

    Instantaneous operation

    <200ms

    Setting range for residual current protection characteristics

    Parameter

    Set value (125,250,400)

    Set value (630,800)

    Factory set value

    Remaining motion current I△n

    50,100,200,300,400,500,600,800automatic

    100,200,300,400,500,600,800,1000automatic

    500

    Outline Overall and Installing Dimensions

    Outline Overall and Installing Dimensions 1

    Note: The left side of the attachment in the diagram is the auxiliary contact, and the right side is the lightning protection module. All models have the same attachment dimensions.

    Outline Overall and Installing Dimensions 2Outline Overall and Installing Dimensions 3Outline Overall and Installing Dimensions 4Outline Overall and Installing Dimensions 5

    Characteristic Curve

    Characteristic Curve

    Frequently Asked Questions (FAQ)

    What standards does the CBRM3EL Leakage Circuit Breaker meet?
    The product meets GB/T14048.1-2012 (Low voltage switchgear and control equipment - General principles), GB/T14048.2-2008 (Circuit breakers), and GB/T17701-2008 (Equipment circuit breakers) standards.
    What microprocessor is used in this circuit breaker?
    It adopts a high-performance 32-bit ARM microprocessor for real-time signal processing and intelligent control.
    Can the residual current parameters be adjusted online?
    Yes, the residual current (leakage current) protection can be adjusted online. Additionally, it has a reclosing function and supports real-time monitoring and tracking of the line's residual current.
    What types of protection functions does the CBRM3EL support?
    It provides three-stage protection (long delay, short delay, and instantaneous) using electronic trip independent of power supply voltage. It also supports over-voltage, under-voltage, and phase loss protection.
    Does this circuit breaker support remote communication?
    Yes, the network type has communication functions that realize remote signaling, remote measurement, remote control, and remote adjustment. It also supports optional infrared communication.
    Are there optional modules for lightning protection?
    Yes, the device supports an optional plug-and-play lightning protection module.

    Leave Your Message