China CBRM3EL Automatic Reclosing Circuit Breaker Supplier - MCCB with Residual Current Protection from Factory

The residual current circuit breaker, with a rated insulation voltage of 1000V, is designed specifically for three-phase AC systems operating at a nominal voltage of 400V and capable of handling rated currents up to 80A. This unit features a four-wire neutral point directly grounded (T) in the distribution network, ensuring indirect contact protection. It effectively mitigates fire risks associated with ground fault currents due to equipment insulation failure. As a key component in the distribution of electrical energy, it safeguards lines and power equipment against hazards like overload, under-voltage, short circuits, and single-phase grounding faults. Trusted by many in China, this product is a reliable choice among leading suppliers and factories in the industry

    CBRM3EL Leakage Circuit Breaker

    Meets Standards

    The product meets the following standards:

    • GB/T14048.1-2012 Low voltage switchgear and control equipment Part 1: General principles;
    • GB/T14048.2-2008 Low-voltage switchgear and control equipment Part 2: Circuit breakers;
    • GB/T17701-2008 <Equipment circuit breakers>.

    Main Functions and Features

    • Adopt high-performance 32-bit ARM microprocessor, real-time signal processing and intelligent control;
    • LCD Chinese display, user-friendly interface, easy operation;
    • The residual current (leakage current) protection can be adjusted online, and has the function of reclosing;
    • Real-time monitoring and tracking of the residual current of the line, automatic adjustment of the range, to ensure the operation rate and reliability of the product;
    • Three-stage protection, long delay, short delay and instantaneous, using electronic trip, independent of power supply voltage;
    • High breaking capacity to ensure the reliability of line short circuit protection;
    • Over-voltage protection, under-voltage protection, phase loss protection;
    • The residual current of the line, the three-phase power supply voltage and the load current are displayed in real time;
    • Protective functions and parameters can be set and modified online.
    • Trip types (residual current, lockout, overload, under-voltage, over-voltage, phase loss) are identified and displayed, and can be stored, queried, and deleted.
    • The network type has communication functions, which can realize remote signaling, remote measurement, remote control and remote adjustment.
    • Plug-and-play lightning protection module (optional)
    • Supports infrared communication (optional)

    Key Technical Specifications

    Specifications and models CBRV3F-125CY
    CRRV3EL-125CS
    CBRM3FI.-250CY
    CBRM3EL-250CS
    CBRM3EI.-400CY
    CBRM3EL-400CS
    CBRV3EL-630CY
    CBRM3EL 630CS
    CBRM3EL 800CY
    CBRM3EL-800CS
    Rated current of the shell frame class (A) 125 250 400 630 800
    Number of poles 3P+N 3P+N,2P 3P+N 3P+N 3P+N
    Rated working voltage Ue (V) AC 400/50HZ
    Rated insulation voltage Ui (V) 1000
    Rated impulse withstand voltage Uimp (V) 8000
    Flash-over distance(mm) ≠50 ≠100
    Maximum short-circuit breaking capacity (lcu, kA) 50 (H-type 70) 65 (H-type 85) 65
    Operating short-circuit breaking capacity (lcs, kA) 35 (H-type 50) 42 (H-type 65) 42
    Rated residual short-circuit breaking capacity I△m (kA) 12.5 (H-type 17.5) 16.25 (H-type 21.5) 16.25
    Rated short-time current Icw (kA)is 1.5 3 5 8 10
    RCD trip characteristics AC mould
    Rated residual operating current I△n (mA) 50/100/200/300/400/500/600/800MCU
    automatic tracking or manual setting
    100/200/300/400/500/600/800/1000
    MCU automatic tracking or manual
    Remaining motion time characteristics Delayed/non-delayed
    Delay-type limit non-drive time (s) 0.06/0.1/0.2 Optional:21△n
    Break-time (s) I△≤0.5;2I△n≤0.2;51△n≤0.15
    Automatic reclosing time (s) 20-60
    Operation performance (times) Set up an electric circuit 1500 1000 1000 500
    No power 8500 7000 4000 2500
    Total 10000 8000 5000 3000
    Overload and short-circuit characteristics Three-stage protection with electronic adjustment. See "Protection Characteristics" for details.
    Over-voltage protection value (V) Set value(250~300)±5%
    Under-voltage protection value (V) Set value (14S--200)±5%
    Control delay time (ms) ≤40ms
    Communication delay (ms) ≤200ms

    Protection Feature Description

    ◆ Overload and long delay protection

    Action value range
    Table 1: Overload Long Delay Parameter Settings

    Parameter Shroud current Set value Factory set value
    Action set-point Irl 125 50A、63A、80A、100A、125A 125A
    250 100A、125A、140A、160A、180A、200A、225A、250A 250A
    400 160A、180A、200A、225A、250A、315A、350A、400A 400A
    630 250A、315A、350A、400A、500A、630A 630A
    800 315A、350A、400A、500A、630A、700A、800A 800A
    Delay time setting value tL 3s,4s,6s,8s,10s,12s,16s,18s,OFF 12s

    ◆ Performance characteristic
    Table 2: Protection Action Characteristics

    Ambient temperature Current name Set current multiplier Appointed time
    +40℃ Conventional non tripping current 1.05Ir1 ≥2h
    Conventional tripping current 1. 3Ir1 <2h

    ◆ Time-delay characteristics
    The overload protection is based on the inverse time characteristic.
    The delay time T is calculated as (6rll, with a tolerance oft10%.Here,T represents the action time Irl is he long delay protection setting,I denotes the fault current. And tL is the long delay time setting.

    ◆ Short circuit short delay protection
    Short delay protection prevents impedance short circuit in the distribution system, and the trip delay is to achieve selective protection.
    Short-circuit short delay protection parameter settings
    Table 3: Short-circuit delay parameter setting

    Parameter setting Set value Factory set value
    Short delay action current setting lr2 2Ir1,2.5lr1,3lr1,4lr1,5lr1,6lr1,7lrl,8lrl,10lr1,121r1 6lr1
    Short delay time setting value ts 0.1s,0.2s,0.3s,0.4s,0.6s,0.8s,1.0s,OFF 0.4s

    Short-circuit short delay protection action characteristics
    Table 4: Short Delay Action Characteristics of Short Circuit

    Characteristic Fault current multiple Trip characteristics Delay error
    No action feature ≤0.85 Ir2 Failure to actuate /
    Performance characteristic >1.15Ir2 Deferred action ±40ms

    ◆ Instant Protection
    Set parameters for instantaneous short-circuit protection
    Table 5: Instantaneous parameter setting

    Parameter setting Set value Factory set value
    Instantaneous action current setting lr3 4 Irl,6 Irl,7 Irl,8 Irl, 10 Irl,11 Ir1,12 Irl,13 rl,14 rl,0FF 10 Ir1

    Short-circuit instantaneous protection action characteristics
    Table 6: Instantaneous motion characteristics

    Characteristic Current ratio (I/r3) Trip characteristics Trip time
    No action feature ≤0.85 Failure to actuate ≥200ms
    Performance characteristic >1.15 Instantaneous operation <200ms

    Setting range for residual current protection characteristics

    Parameter Set value (125,250,400) Set value (630,800) Factory set value
    Remaining motion current I△n 50,100,200,300,400,500,600,800automatic 100,200,300,400,500,600,800,1000automatic 500

    Outline Overall and Installing Dimensions

    Outline Overall and Installing Dimensions

    Note: The left side of the attachment in the diagram is the auxiliary contact, and the right side is the lightning protection module. All models have the same attachment dimensions.

    Outline Overall and Installing Dimensions 2Outline Overall and Installing Dimensions 3Outline Overall and Installing Dimensions 4Outline Overall and Installing Dimensions 5

    Characteristic Curve

    Characteristic Curve

    Frequently Asked Questions (FAQ)

    What industry standards does the CBRM3EL Leakage Circuit Breaker comply with?
    The CBRM3EL circuit breaker meets GB/T14048.1-2012 (Low voltage switchgear and control equipment - General principles), GB/T14048.2-2008 (Low-voltage switchgear and control equipment - Circuit breakers), and GB/T17701-2008 (Equipment circuit breakers) standards.
    What are the main features of the microprocessor used in this circuit breaker?
    It adopts a high-performance 32-bit ARM microprocessor that enables real-time signal processing and intelligent control. It also features a user-friendly LCD Chinese display for easy monitoring and operation.
    How does the residual current protection system work?
    The residual current (leakage current) protection can be adjusted online. It features real-time monitoring and tracking of the line's residual current with automatic range adjustment to ensure high reliability and operation rates. It also supports auto-reclosing.
    What protection functions does the CBRM3EL provide?
    It provides three-stage protection (long delay, short delay, and instantaneous) using electronic trip independent of the power supply voltage. Additionally, it offers over-voltage, under-voltage, and phase loss protection.
    Does this circuit breaker support remote communication?
    Yes, the network-type model supports communication functions that enable remote signaling, remote measurement, remote control, and remote adjustment. It also has optional support for plug-and-play lightning protection and infrared communication.
    What is the automatic reclosing time range of the device?
    The automatic reclosing time for the CBRM3EL Leakage Circuit Breaker is set between 20 to 60 seconds.