CBRW3 2500A Intelligent Air Circuit Breaker - High Breaking Capacity from China Suppliers & Factory
Normal Operating and Installation Conditions
The upper limit shall not exceed +55°C, and the lower limit shall not be less than -5°C.
The altitude of the installation site shall not exceed 2000m. The high-altitude derating coefficient can be referred to.
At +55°C, relative humidity shall not exceed 50%. Higher humidity is allowed at lower temperatures (e.g., 90% at +20°C). Condensation measures should be taken.
Pollution degree: Level 3. Installation Category: Main circuit Category Ⅳ; control/auxiliary circuits Category Ⅲ.
Vertical inclination shall not exceed 5°. Protection class requirements: IP30, IP40 (with compartment door frames and organic glass covers).
Service category: B
Product Features
-
1
The contact system is installed in the small chamber of the insulating part. The contact system of each phase adopts a multi-path sheet-like structure, realizes electric force compensation and ensures the high breaking capacity of the circuit breaker.
-
2
The advanced arc-extinguishing system and protective cover ensure "zero flying arc", making the product more secure.
-
3
The circuit breaker is operated for energy storage by the energy-storage mechanism, with a fast closing speed.
-
4
The operating mechanism is installed at the center of the front of the circuit breaker and is completely separated from the main circuit. It can make each phase have a stable and consistent final contact pressure, which plays an important role in ensuring the temperature rise and breaking indicators.
-
5
The centered operating mechanism facilitates symmetric hole-opening in the middle of the complete set of cabinet doors, improving the appearance quality of the complete set of cabinets.
-
6
It can be installed with bottom incoming lines and has horizontal and vertical wiring methods.
-
7
Intelligent controller, with multiple protection functions, can realize selective protection.
Model and Description
| ATA | 3200 | / | 3200A | / | 3P | / | Intelligent Controller Model(M) | / | Operating Voltage of the Intelligent Circuit AC380V/ AC220V /DC220V/ DC110 |
| 3150A | |||||||||
| 2900A | |||||||||
| 2500A | |||||||||
| 2000A |
Product Features
| Breaker Model | ATA3200 | |||
| Frame - rated Current lrm(A) | 3200 | |||
| Rated Operating Current In (A) | 2000, 2500 | 2900, 3150, 3200 | ||
| Rated Operating Voltage Ue (v) | AC230, AC400, AC690 | |||
| Rated Frequency Hz | 50/60Hz | |||
| Rated insulation Voltage Ui(V) | 1000 | |||
| Rated impulse Withstand Voltage Uimp (kV) | 12 | |||
| Number of Poles (P) | 3 | |||
| Total Breaking Time (ms) | ≤30 | |||
| Closing Time (ms) | ≤60 | |||
| Rated Ultimate Short .Circuit Breaking Capacity Icu(kA)(RMS) | AC230V | 65 | ||
| AC400V | 65 | |||
| AC690V | 50 | |||
| Rated Service Short .Circuit Breaking Capacity Ics (kA)(RMS) | AC400V | 65 | ||
| AC690V | 65 | |||
| AC230V | 50 | |||
| Rated Short . Time Withstand Current Icw(1S)(KA)(RMS) | AC230V | 65 | ||
| AC400V | 65 | |||
| AC690V | 50 | |||
| Operating Performance(Times) | Electrical Life | AC230V AC400V | 10000 | 8000 |
| AC690V | 5000 | 5000 | ||
| Mechanical Life | Maintenance-free | 10000 | 8000 | |
| Maintenance Required | 20000 | 15000 | ||
| Installation Type | Fixed Type | |||
| Main Circuit wiring Method | Fixed Type | Horizontal Wiring, Vertical wiring | ||
| Overall Dimensions:WxHxD mm | 422X402X368 | |||
| Weight (kg) | 55 | 66 | ||

CBRM5EL Automatic Reclosing MCCB
CBRM3EL Remote Reclosing MCCB
CBRM5E Intelligent MCCB
CBRM5EKd Electronic MCCB
CBRM5Kd Compact MCCB
CBRM5K Lockable MCCB
CBRM5EN Primary-secondary Separated MCCB
CBRECB Meter Remote Control MCCB
CBRB7BL Type B Smart RCBO
CBRB7 Compact MCB
CBRB7-AP PV Grid-connected MCB
CBRW3 4000A ACB
CBRW3 2500A ACB
CBRW3 1600A ACB