CBRM5EKd Electronic Adjustable Circuit Breaker With LCD Display (MCCB)
Product Model&Description

Four-Pole Product Codes
Type A: N pole without overcurrent release element, and the N pole remains closed at all times and does not open or close with the other three poles.
Type B: N pole without overcurrent release element, and the N pole opens and closes with the other three poles (the N pole closes first and opens later).
Operating Environment
Normal Operating Conditions
◆The upper limit of ambient air temperature shall not exceed +40'C, the lower limit shall not be lower than -5'C, and the average temperature within 24 hours shall not exceed +35°C.Note: When the ambient air temperature exceeds +40'C or falls below -5°C, the use of the circuit breaker should be subject to agreement with the manufacturer.
◆Installation altitude shall not exceed 2000 m.
◆The relative humidity of the atmosphere shall not exceed 50% at the maximum ambient temperature of +40°C Higher relative humidity is allowed at lower temperatures (e.g., 90% at 20°C), with consideration given to condensation that may occur due to temperature changes on the product surface.
Normal Installation Conditions
◆Installation category: Category Ⅲ for the main circuit, Category Ⅱ for the control and auxiliary circuits.
◆Installation orientation: Generally installed vertically (upright), but horizontal (flat-mounted) installation is also permissible.
◆Pollution degree:Degree 3.
◆External magnetic field: The external magnetic field in the installation location shall not exceed 5 times the geomagnetic field in any direction.
Trip Unit Types &Accessory Codes


Main Technical Parameters
|
Model |
CBRM5Kd-125i |
CBRM5Kd-160 |
CBRM5Kd-250 |
CBRM5Kd-400 CBRM5Kd-630i |
CBRM5Kd-800 |
||||||||||||||||
|
Frame Size Current Inm(A) |
125 |
160 |
250 |
400、630 |
800 |
||||||||||||||||
|
Rated Current In(A) |
10、16、20、25、30、32、40、50、63、70、75、80、90、100、125 |
16、20、25、30、32、40、50、63、70、75、80、90、100、125、140、150、160 |
100、125、140、150、160、175、180、200、225、250 |
225、250、280、300、315、350、400、500、550、630 |
630、700、800 |
||||||||||||||||
|
Number of Poles |
3 |
4 |
3 |
4 |
3 |
4 |
3 |
4 |
3 |
4 |
|||||||||||
|
Rated Insulation Voltage Ui(V) |
1000 |
||||||||||||||||||||
|
Rated Operation Voltage Ue(V) |
AC380、AC400、AC415 |
AC380、AC400、AC415、AC660、AC690 |
|||||||||||||||||||
|
Rated Impulse Withstand Voltage Uimp(kV) |
8 |
12 |
|||||||||||||||||||
|
Arc Distance(mm) |
50 |
100 |
|||||||||||||||||||
|
Breaking Capacity Level |
L |
M |
H |
L |
M |
H |
L |
M |
H |
L |
M |
H |
L |
M |
H |
||||||
|
Ultimate Short-Circuit Breaking Capacity Icu(kA)AC380V/AC400V/AC415V |
10 |
18 |
36 |
25 |
36 |
50 |
36 |
50 |
70 |
50 |
70 |
100 |
50 |
70 |
100 |
||||||
|
Service Short-Circuit Breaking Capacity Ics(kA)AC380VAC400V/AC415V |
10 |
18 |
36 |
25 |
36 |
50 |
36 |
50 |
70 |
50 |
70 |
100 |
50 |
70 |
100 |
||||||
|
Ultimate Short-Circuit Breaking Capacity Icu(kA)AC660W/AC690V |
- |
- |
- |
8 |
10 |
10 |
10 |
10 |
10 |
10 |
15 |
20 |
15 |
20 |
25 |
||||||
|
Service Short-Circuit Breaking Capacity Ics(kA)AC660V/AC690V |
- |
- |
- |
8 |
10 |
10 |
10 |
10 |
10 |
10 |
15 |
20 |
13 |
15 |
20 |
||||||
|
Number of operating cycles |
With current |
4000 |
4000 |
4000 |
1000 |
500 |
|||||||||||||||
|
Without current |
10000 |
10000 |
10000 |
4000 |
2500 |
||||||||||||||||
|
Total |
14000 |
14000 |
14000 |
5000 |
3000 |
||||||||||||||||
Protection Characteristics
For Distribution Applications
|
Rated Current (A) |
Thermal Trip Unit (Ambient Temp +40) |
Magnetic Trip Unit Operating Current (A) |
|
|
1.05ln(Cold State) Non-Tripping Time (h) |
1.3In (Hot State) Tripping Time (h) |
||
|
10≤In≤63 |
No Tripping Within 1 hour |
≤1 |
10In±20% |
|
63<In≤800 |
No Tripping Within 2 hours |
≤2 |
|
For Motor Protection
|
Rated Current (A) |
Thermal Trip Unit (Ambient Temp +40) |
Magnetic Trip Unit Operating Current (A) |
||||
|
1.0In(Cold State)Non-Tripping Time (h) |
1.2ln(Hot State) Tripping Time (h) |
1.5ln(Hot State) Tripping Time (h) |
7.2In(Cold State)Tripping Time (h) |
Trip Level |
||
|
10≤In≤25 |
No Tripping Within 2 hours |
≤2 |
≤2min |
0.5s<Tp≤5s |
5 |
12In±20% 160 Frame,16-32A:400A ±20% |
|
25<In≤250 |
≤4min |
4s<Tp≤10s |
10 |
|||
|
250<In≤800 |
≤8min |
6s<Tp≤20s |
20 |
|||
Circuit Breaker Classification
By Number of Poles: Three-Pole, Four-Pole
By Application: For Distribution, For Motor Protection
By Operating Method: Direct Handle Operation, Electric Operation (indicated by "p" ), Rotary Handle Operation for Switchgear (indicated by "Z" )
Circuit Breaker Accessories(Dual-Cover Type)
|
Rated Control Power Supply Voltage Us (V) |
AC230V、AC400V;DC24V |
|
|
Rated Operating Voltage (V) |
(0.7-1.1)Us |
|
|
Shunt Release |
|
Note: K The micros witch inside the shunt release,connected in series with the coil, is normally closed After the breaker trips,the contact opens automatically;it closes when the breaker is switched on, The dashed box indicates the internal accessory wiring diagram of the circuit breaker. |
|
|
||
|
Rated Control Power Supply Voltage Us (V) |
AC230V、AC400V |
|
|
Operating Voltage (V) |
The circuit breaker reliably trips when the voltage is 35%-70% of the rated operational voltage.The breaker closes reliably when the voltage is 85%- 110% of the rated operational voltage. |
|
|
Under voltage Release |
|
Note: P1, P2, UC2, and UC1 are terminal designations. |
|
|
||
|
Conventional Thermal Current Ith(A) |
3A |
|
|
Rated Operating Current Ie(A) |
0.26A when In≤250A; 0.3A when In≥400A |
|
|
Auxiliary Contact |
|
|
|
|
||
|
Conventional Thermal Current Ith(A) |
3A |
|
|
Rated Operating Current Ie(A) |
0.26A when In≤250A;0.3A when In ≥ 400A |
|
|
Alarm Contact |
|
|
|
|
||
|
Conventional Thermal Current Ith(A) |
3A |
|
|
Rated Operating Current Ie(A) |
0.26A when In≤250A;0.3A when In ≥ 400A |
|
|
Auxiliary Contact, Alarm Contact |
|
|
|
|
||
|
Wiring Diagram |
||
|
Input Voltage (V) |
AC230V、AC400V;DC110V、DC230V、DC24V |
|
|
Motor Operator Mechanism |
|
Description: P1-P2: External power supply inputSB1,SB2: Operating buttons (provided by the user)Note: The dashed box indicates the internal wiring diagram of the circuit breaker accessories. |
|
|
||
Overall Dimensions and Mounting Dimensions of the Motor Operator Mechanism

|
Model |
Overall Dimensions(mm) |
Mounting Dimensions (mm) |
||||
|
L1 |
B |
H |
H1 |
a |
b |
|
|
125i |
102 |
73 |
92 |
14 |
25 |
117 |
|
160 |
116 |
90 |
97 |
16 |
30 |
129 |
|
250 |
116 |
90 |
95 |
16 |
35 |
126 |
|
400、630i |
176 |
130 |
151 |
34.5 |
44 |
194 |
|
800 |
176 |
130 |
146 |
31 |
70 |
243 |
Overall Dimensions and Mounting Dimensions of Rear-Connected Circuit Breaker (125i)

Overall Dimensions and Mounting Dimensions of Rear-Connected Circuit Breaker ( 160-800 )

|
Model |
Overall Dimensions(mm) |
Mounting Dimensions (mm) |
||||||
|
L2 |
H1 |
H2 |
A1 |
A2 |
b2 |
D |
d |
|
|
160 |
132 |
42 |
75 |
60 |
90 |
132 |
Φ24 |
Φ8.5 |
|
250 |
144 |
39 |
73 |
70 |
105 |
144 |
Φ24 |
Φ8.5 |
|
400、630i |
226 |
34 |
69 |
87 |
130.5 |
226 |
Φ32 |
Φ12.5 |
|
800 |
243 |
62 |
84 |
140 |
210 |
234 |
Φ48 |
Φ14 |
Overall Dimensions and Mounting Dimensions of Plug-in Rear-Connected Circuit Breaker

|
Model |
A |
B1 |
B2 |
C1 |
C2 |
E |
F |
G |
K |
H |
H1 |
H2 |
N |
S |
Q |
B3 |
B4 |
AM |
BM |
4-d |
|
125i |
145 |
75 |
100 |
50 |
75 |
60 |
121 |
92 |
27 |
27 |
16 |
15 |
142 |
87 |
26 |
80 |
110 |
M5 |
M5 |
Φ6.5 |
|
160 |
169 |
91 |
125 |
60 |
90 |
56 |
132 |
92 |
38 |
50 |
33 |
28 |
179 |
83 |
48 |
101 |
135 |
M6 |
M8 |
Φ6.5 |
|
250 |
186 |
107 |
145 |
70 |
105 |
54 |
145 |
94 |
46 |
50 |
33 |
37 |
196 |
84 |
56 |
117 |
155 |
M6 |
M8 |
Φ6.5 |
|
400、630i |
280 |
144 |
188 |
88 |
132 |
145 |
224 |
180 |
50 |
60 |
38 |
46 |
290 |
170 |
60 |
154 |
198 |
M8 |
M12 |
Φ8.5 |
|
800 |
300 |
210 |
280 |
90 |
160 |
142 |
243 |
174 |
63 |
87 |
61 |
21 |
315 |
170 |
73 |
220 |
290 |
M10 |
M14 |
Φ10 |
Overall Dimensions and Mounting Dimensions of Plug-in Front-Connected Circuit Breaker

|
Model |
Overall Dimensions(mm) |
|||||||||||||||
|
A |
B |
E |
F |
G(3P) |
H |
L(3P) |
L1 |
L2 |
M |
N |
K |
d |
A1(3P) |
B1 |
D |
|
|
125i |
91 |
48 |
121 |
55 |
50 |
150 |
78 |
25 |
25 |
193 |
176 |
23 |
Φ6 |
25 |
112 |
Φ3.5 |

|
Model |
Overall Dimensions(mm) |
||||||||||||||||||
|
A |
B |
C |
D |
E |
F |
H |
H1 |
K1 |
K2 |
d1 |
d2 |
A1 |
A2 |
A3 |
A4 |
A5 |
A6 |
A7 |
|
|
160 |
172 |
96 |
216 |
50 |
61 |
66 |
15 |
35 |
38 |
38 |
Φ6.5 |
M8 |
18 |
3 |
19 |
10.5 |
30 |
10.5 |
196 |
|
250 |
183 |
110 |
261 |
51.5 |
64 |
70 |
42.5 |
35 |
44 |
44 |
Φ6.5 |
M8 |
49 |
3 |
22 |
13.5 |
35 |
22 |
227 |
|
400、630i |
282 |
144 |
362 |
362 |
146 |
88 |
20 |
59 |
50 |
50 |
Φ8.5 |
Φ11 |
26 |
6 |
30 |
14.5 |
44 |
25 |
331 |
|
800 |
305 |
210 |
409 |
409 |
144 |
90 |
16 |
61 |
62 |
62 |
Φ11 |
Φ13 |
24 |
8 |
35 |
35 |
70 |
36 |
377 |
Overall Dimensions and Mounting Dimensions of Rotary Handle Operating Mechanism

|
Model |
125i |
160 |
250 |
400、630i |
800 |
|
Mounting Dimensions H(mm) |
54 |
60 |
60 |
97 |
90 |
|
A |
25 |
30 |
35 |
44 |
70 |
|
B |
95 |
120 |
142 |
195 |
243 |
Note: The standard rod length provided at delivery is 150mm.
Dimensions of the Circuit Breaker with Protective Cover

|
Model |
125i |
160 |
250L、M |
250H |
400 |
630i |
800 |
|
Number of Poles |
3P |
3P |
3P |
3P |
3P |
3P |
3P |
|
L4 |
170 |
195 |
208 |
208 |
292 |
505 |
436 |
|
W3 |
78 |
92.5 |
107 |
107 |
140 |
186.5 |
234 |
|
H5 |
67.5 |
67.5 |
74 |
100 |
101.5 |
101.5 |
111 |
Overall Dimensions &Mounting Dimensions(Dual-Cover Type)

|
Model |
Overall Dimensions(mm) |
Mounting Dimensions (mm) |
|||||||||||||
|
L |
L1 |
L2 |
L3 |
W1 |
W2 |
H |
H1 |
H2 |
H3 |
H4 |
W |
B |
d |
A |
|
|
CBRM5Kd-125iL、M、H |
135 |
86 |
49 |
24.5 |
78 |
103 |
63.5 |
21 |
69.5 |
95 |
21 |
25 |
117 |
Φ4.2 |
25 |
|
CBRM5Kd-160L、M、H |
150 |
95 |
51 |
29 |
92.5 |
122.5 |
65.5 |
25.5 |
75 |
100 |
23 |
30 |
130 |
Φ4.5 |
30 |
|
CBRM5Kd-250L、M |
165 |
102 |
56.5 |
31 |
107 |
142 |
72 |
21.5 |
79 |
105 |
21.5 |
35 |
126 |
Φ5 |
35 |
|
CBRM5Kd-250H |
165 |
102 |
56.5 |
31 |
107 |
142 |
97 |
21.5 |
105 |
132 |
21.5 |
35 |
126 |
Φ5 |
35 |
|
CBRM5Kd-400L、M、H |
257 |
150 |
87.5 |
58 |
140 |
184 |
99 |
35 |
108 |
163 |
37 |
44 |
194 |
Φ7 |
44 |
|
CBRM5Kd-630iL、M、H |
257 |
150 |
87.5 |
58 |
140 |
184 |
99 |
36.5 |
108 |
163 |
38.5 |
44 |
194 |
Φ7 |
44 |
|
CBRM5Kd-800L、M、H |
280 |
180 |
86.9 |
64 |
210 |
280 |
109 |
38 |
117 |
170 |
41.5 |
70 |
243 |
Φ7.5 |
70 |
Operation &Maintenance
◆Before installation, carefully review the relevant dimensional drawings and mounting instructions, and verify that the nameplate technical specifications meet the requirements.
◆For circuit breakers with a motor operator mechanism, do not remove the motor operator during installation, as it may affect tripping characteristics, After tripping, the motor operator automatically resets the breaker. Closing requires a closing command from the upper- level controller, tripping similarly requires a tripping command. For manual closing opening, set the motor operator switch to "Manual" . If the breaker is in the free trip position, it must be manually reset before performing closing or opening operations.
◆Internal and external accessories of the circuit breaker are preset at the factory. Users should not attempt to adjust or disassemble them.Installation can be done directly.
◆The phase line must be properly connected. Otherwise, internal electronic circuits may not function properly.affecting the protection capability.
◆For breakers equipped with an under voltage release, the release must be supplied with its rated operating voltage before closing is possible.
Transportation& Storage
Transportation
Protect against harmful liquids (such as water, rain, snow, chemical solvents, corrosive liquids, etc.) and avoid mixing with incompatible items; prevent strong impact and compression. Stack according to the packaging orientation instructions; the number of layers must comply with the label on the outer carton.
Storage
◆Ambient Temperature:-10℃to +45℃.
◆Relative Humidity: 90% (at +20℃ambient temperature).
◆The storage location shall be free of dust and conductive particles.
◆No corrosive, flammable, or explosive gases; protected from rain and snow.
◆It shall be dry and well ventilated.
◆Stack according to packaging orientation; the number of layers must not exceed the limit indicated on the outer carton.
Precautions
◆The company is not responsible for warranty claims if terminal damage is caused by improper installation, improper use(non-quality issues),or incorrect wiring.
◆If any issues arise during product use, please contact your local distributor or the company's customer service center.

CBRM5EL Automatic Reclosing MCCB
CBRM3EL Remote Reclosing MCCB
CBRM5E Intelligent MCCB
CBRM5EKd Electronic MCCB
CBRM5Kd Compact MCCB
CBRM5K Lockable MCCB
CBRM5EN Primary-secondary Separated MCCB
CBRECB Meter Remote Control MCCB
CBRB7BL Type B Smart RCBO
CBRB7 Compact MCB
CBRB7-AP PV Grid-connected MCB
CBRW3 4000A ACB
CBRW3 2500A ACB
CBRW3 1600A ACB