Inquiry Now
Leave Your Message
Products Categories
Featured Products

CBRM5K Compact Lockable Molded Case Circuit Breaker (MCCB) - China Factory Suppliers for Enhanced Safety

,

Enhanced Safety with Built-in Key Lock

,

The D&T CBRM5K molded case circuit breaker (MCCB) is engineered with a built-in key lock mechanism that ensures the switch remains securely in the OFF position. This design prevents unauthorized operation, accidental power-on, and tampering, making it an ideal choice for safeguarding electrical systems. As a reliable product from trusted China suppliers, this MCCB ensures safe electrical isolation during maintenance or idle periods, making it an essential component for safety-conscious factories.

,

    Model and Meaning

    Model and Meaning

    Meets Standards

    The products conform to the following standards:
    GB/T14048.1-2012 Low-voltage switchgear and controlgear - Part 1: General;
    GB/T14048.2-2008 Low-voltage switchgear and controlgear - Part 2: Circuit breakers;
    GB/T17701-2008 Circuit breakers for equipment.

    Main Functions and Features

    • It adopts a high-performance 32-bit ARM microprocessor for real-time signal processing and intelligent control;
    • The LCD Chinese display provides a user-friendly interface and simple operation;
    • It features residual current (leakage current) protection with online adjustment of the residual current level and reclosing function;
    • It monitors and tracks the residual current of the line in real time and automatically adjusts the level to ensure the product's operational rate and reliability;
    • It offers three-stage protection: long-delay, short-delay, and instantaneous, using electronic tripping that is independent of power supply voltage;
    • It has high breaking capacity to ensure the reliability of line short-circuit protection;
    • Over-voltage protection, under-voltage protection, phase loss protection;
    • Real-time display of line residual current, three-phase power supply voltage, and load current;
    • Protection functions and parameters can be set and modified online;
    • The tripping type (residual current, lockout, overload, undervoltage, overvoltage, phase loss) can be identified, displayed, stored, queried, and deleted;
    • Network-type models have communication capabilities, enabling remote signaling, telemetry, remote control, and remote adjustment;
    • Pluggable surge protection modules (optional);
    • Feature infrared communication (optional).

    Main Technical Parameters

    Specifications and Models CBRM3EL-125CY
    CBRM3EL-125CS
    CBRM3EL-250CY
    CBRM3EL-250CS
    CBRM3EL-400CY
    CBRM3EL-400CS
    CBRM3EL-630CY
    CBRM3EL-630CS
    CBRM3EL-800CY
    CBRM3EL-800CS
    Frame rating rated current (A) 125 250 400 630 800
    Extreme number 3P+N 3P+N, 2P 3P+N 3P+N 3P+N
    Rated operating voltage Ue (V) AC 400/50HZ
    Rated insulation voltage Ui (V) 1000
    Rated impulse withstand voltage Uimp (V) 8000
    Flight arc distance (mm) ≤50 ≤100
    Ultimate short-circuit breaking capacity Icu(kA) 50 (H type 70) 65 (H type 85) 65
    Operating short-circuit breaking capacity Ics(kA) 35 (H type 50) 42 (H type 65) 42
    Rated residual short circuit connection (disconnection) Ability IΔm(kA) 12.5 (H type 17.5) 16.25 (H type 21.5) 16.25
    Rated short-time withstand current Icw (kA)/s 1.5 3 5 8 10
    Residual current operating characteristics AC type
    Rated residual operating current IΔN(mA) 50/100/200/300/400/500/600/800
    MCU Automatic tracking or manual setting
    100/200/300/400/500/600/800/1000
    MCU Automatic tracking or manual setting
    Remaining motion time characteristics Delayed/Non-delayed
    Delay-type limit of non-drive time (s) 0.06/0.1/0.2 optional: 2IAn
    Break time (s) IΔn≤0.5; 2IΔn≤0.2; 5IΔn≤0.15
    Automatic reclosing time (s) 20-60
    Operational performance (times) power ups 1500 1000 1000 500
    No power 8500 7000 4000 2500
    Total number of times 10000 8000 5000 3000
    Overload and short-circuit characteristics Three-stage protection, electronically adjustable; see "Protection Feature Description" for details.
    Overvoltage protection value (V) Set value (250~300) ± 5%
    Undervoltage protection value (V) Set value (145~200) ± 5%
    Joint control delay time (ms) ≤40ms
    Communication delay time (ms) ≤200ms

    Protection Features Description

    Overload long delay protection

    Action value setting range
    Table 1: Overload Long Delay Parameter Settings

    Parameter Frame current Setting value Factory setting value
    Action setting value Ir1 125 50A, 63A, 80A, 100A, 125A 125A
    250 100A, 125A, 140A, 160A, 180A, 200A, 225A, 250A 250A
    400 160A, 180A, 200A, 225A, 250A, 315A, 350A, 400A 400A
    630 250A, 315A, 350A, 400A, 500A, 630A 630A
    800 315A, 350A, 400A, 500A, 630A, 700A, 800A 800A
    Delay time setting value tL 3s, 4s, 6s, 8s, 10s, 12s, 16s, 18s, OFF 12s
    Action characteristics

    Table 2: Protective Action Characteristics

    Ambient temperature Current Name Setting current multiple Agreed Time
    +40℃ Non-tripping current agreed upon 1.05lr1 ≥2h
    Conventional tripping current 1.3lr1 <2h
    Delay characteristics

    Overload protection operates based on inverse time characteristics:
    T=(6Ir1/I)2tL Delay accuracy: ±10%
    Where T is the action time value, lr1 is the long delay protection setting value, I is the fault current, and TL is the long delay time setting value.

    Short circuit short delay protection

    Short-circuit short-delay protection prevents impedance short circuits in power distribution systems, and the tripping delay is for selective protection. Short-circuit short-delay protection parameter settings.
    Table 3: Short-circuit short-delay parameter settings

    Parameter settings Setting value Factory setting value
    Short-delay operating current setting value Ir2 2lr1, 2.5lr1, 3lr1, 4lr1, 5lr1, 6lr1, 7lr1, 8lr1, 10lr1, 12lr1 6lr1
    Short delay time setting value ts 0.1s, 0.2s, 0.3s, 0.4s, 0.6s, 0.8s, 1.0s, OFF 0.4s

    Short-circuit short-delay protection operation characteristics
    Table 4: Short-circuit short-delay action characteristics

    Characteristic Fault current multiple Tripping characteristics Delay error
    Non-action characteristics ≤0.85 lr2 No action /
    Action characteristics >1.15 lr2 Delayed action ±40ms
    Instantaneous protection Short-circuit instantaneous protection related parameter settings

    Table 5: Instantaneous Parameter Settings

    Parameter settings Setting value Factory setting value
    Instantaneous operating current setting value Ir3 4 lr1, 6 lr1, 7 lr1, 8 lr1, 10 lr1, 11 lr1, 12 lr1, 13 lr1, 14 lr1, OFF 10 lr1

    Short circuit instantaneous protection operation characteristics
    Table 6: Instantaneous motion characteristics

    Characteristic Current multiple (I/Ir3) Tripping characteristics Tripping time
    Non-action characteristics ≤0.85 No action ≥200ms
    Action characteristics >1.15 Instantaneous action <200ms
    Residual current protection characteristics

    Gear setting range

    Parameter Setting values (125, 250, 400) Setting values (630, 800) Factory setting value
    Residual operating current IΔn 50, 100, 200, 300, 400, 500, 600, 800 (Auto) 100, 200, 300, 400, 500, 600, 800, 1000 Automatic 500

    External Shape and Installation Dimensions

    External shape and installation dimensions 1

    Note: The auxiliary contact is on the left and the surge protection module is on the right in the diagram; the dimensions of the accessories are the same for all models.

    External shape and installation dimensions 2
    External shape and installation dimensions 3External shape and installation dimensions 4External shape and installation dimensions 5

    Characteristic Curves

    Characteristic curves

    Frequently Asked Questions (FAQ)

    What standards do these circuit breakers conform to?
    The products conform to standard specifications GB/T14048.1-2012 (Low-voltage switchgear and controlgear - Part 1: General), GB/T14048.2-2008 (Part 2: Circuit breakers), and GB/T17701-2008 (Circuit breakers for equipment).
    What microprocessor technology is used in the device?
    It adopts a high-performance 32-bit ARM microprocessor to perform real-time signal processing and intelligent control.
    Does the circuit breaker support remote monitoring and communication?
    Yes, network-type models have communication capabilities that enable remote signaling, telemetry, remote control, and remote adjustment. Optional infrared communication is also available.
    How does the residual current protection feature operate?
    It monitors and tracks the residual current (leakage current) of the line in real time, allowing online adjustment of the residual current level and features an automatic tracking or manual setting via MCU.
    What kinds of protections are offered in the three-stage protection system?
    It includes overload long-delay protection, short-circuit short-delay protection, and short-circuit instantaneous protection, using electronic tripping that operates independently of the power supply voltage.
    What auxiliary modules can be optionally integrated?
    The unit supports optional pluggable surge protection modules and infrared communication modules depending on installation requirements.