CBRM5EL Compact Automatic Reclosing Circuit Breaker with Residual Current Protection - China Suppliers Factory

Introducing our advanced residual current circuit breaker, designed specifically for three-phase AC systems operating at 50Hz frequency. With a rated insulation voltage of 1000V and capable of handling rated voltages up to 400V and currents up to 630A, this product is perfect for distribution networks. As a leading manufacturer in China, our factory ensures top-notch quality, providing essential indirect contact protection. This circuit breaker is engineered to prevent fire hazards caused by ground fault currents that may result from equipment insulation damage. It effectively distributes electrical energy, safeguarding lines and power equipment against overloads, undervoltage, short circuits, and single-phase grounding faults. Trust our factory for reliable and efficient solutions in electrical safety as a reputable supplier in the industry

    Residual Current Protection (RCD) Circuit Breaker (Smart Reclosing)

    Product Model and Meaning

    Product Model and Meaning

    Meets standards

    The product meets the following standards:

    • GB/T14048.1-2012 Low voltage switchgear and control equipment Part 1: General principles
    • GB/T14048.2-2008 Low-voltage switchgear and control equipment Part 2: Circuit breakers
    • GB/T1770 1-2008 <Equipment circuit breakers>

    Main functions and features

    • Adopt high-performance 32-bit ARM microprocessor, real-time signal processing and intelligent control; LCD Chinese display, user-friendly interface, easy operation.
    • The residual current (leakage current) protection can be adjusted online, and has the function of reclosing.
    • Real-time monitoring and tracking of the residual current of the line, automatic adjustment of the range, to ensure the operation rate and reliability of the product.
    • Three-stage protection, long delay, short delay and instantaneous, using electronic trip, independent of power supply voltage.
    • It has high breaking capacity and ensures the reliability of line short circuit protection. Overvoltage protection, undervoltage protection, phase loss protection.
    • The residual current of the line, the three-phase power supply voltage and the load current are displayed in real time.
    • Protective functions and parameters can be set and modified online.
    • Trip types (residual current, lockout, overload, undervoltage, overvoltage, phase loss) are identified, displayed, and can be stored, queried, and deleted.
    • The network has communication function, which can realize remote signal, remote measurement, remote control and remote adjustment.
    • Plug-and-play lightning protection module (optional).
    • Supports infrared communication (optional).

    Key technical specifications

    Specifications and models CERM5EL-125CY
    CBRM5EL-125CS
    CERM5EL-250CY
    CRRM5EL-250CS
    CBRM5EL-400CY
    CBRM5EL-400CS
    CBRM5EL-630CY
    CRRM5EL-630CS
    Rated current of the shell frame class (A) 125 250 400 630
    Number of poles 3P+N 3P+N 3P+N 3P+N
    Rated working voltage Ue (V) AC 400/50HZ
    Rated insulation voltage Ui(V) 800 1000
    Rated impulse withstand voltage Uimp(V) 8000
    Flashover distance(mm) ≠50 ≠100
    Maximum short-circuit breaking capacity (lcu, kA) 50 65 85
    Operating short-circuit breaking capacity (les, kA) 35 42 65
    Rated residual short-circuit breaking capacity IΔm (kA) 12.5 16.25 21.25
    Rated short-time withstand current (LCW) in kA/s 1.5 3 5 8
    RCD trip characteristics AC mould
    Rated residual operating current IΔn (mA) 50/100/200/300/400/500/600/800
    MCU automatically tracks or manually sets any value
    100/200/300/400/500/600/800/1000 MCU
    automatic tracking or manual setting
    Remaining motion time characteristics Delayed/non-delayed
    Delay-type limit non-drive time (s) 0.06:2IΔn
    Break-time(s) IΔn≤0.5; 2IΔn≤0.2; 5IΔn≤0.15
    Automatic reclosing time (s) 20-60
    Operation performance (times) Set up an electric circuit 1500 1000 1000
    No power 8500 7000 1000
    Total 10000 8000 5000
    Overload and short-circuit characteristics Three stage protection with electronic adjustment, See "Protection Characteristics" for details.
    Over-voltage protection value (V) Set value (250~300)±5%
    Under-voltage protection value (V) Set value (145-200)±5%
    Control delay time (ms) ≤40ms
    Communication delay (ms) ≤200ms

    Protection feature description

    ◆ Overload and long delay protection
    Action value range (Table 1: Overload Long Delay Parameter Settings)

    Parameter Shroud current Set value Factory set value
    Action set-point Ir1 125 50A, 63A, 80A, 100A, 125A 125A
    250 100A, 125A, 140A, 160A, 180A, 200A, 225A, 250A 250A
    400 160A, 180A, 200A, 225A, 250A, 315A, 350A, 400A 400A
    630 250A, 315A, 350A, 400A, 500A, 630A 630A
    Delay time setting value tL 3s, 4s, 6s, 8s, 10s, 12s, 16s, 18s, OFF 12s

    ◆ Performance characteristic
    Table 2: Protection Action Characteristics

    Ambient temperature Current name Set current multiplier Appointed time
    +40℃ Conventional non tripping current 1.05Ir1 ≥2h
    Conventional tripping current 1.3Ir1 <2h

    ◆ Time-delay characteristics
    The overload protection is based on the inverse time characteristic.
    The delay time is calculated as T=(6Ir1/I) x L, with a tolerance of +10%. Here, T represents the action time, Ir1 is the long delay protection setting, I denotes the fault current, and L stands for the long delay time setting.

    ◆ Short circuit short delay protection
    Short delay protection prevents impedance short circuit in the power distribution system, and the trip delay is to achieve selective protection. Short-circuit short delay protection parameter settings (Table 3: Short-Circuit Delay Parameter Setting)

    Parameter setting Set value Factory set value
    Short delay action current setting Ir2 2Ir1, 2.5Ir1, 3Ir1, 4Ir1, 5Ir1, 6Ir1, 7Ir1, 8Ir1, 10Ir1, 12Ir1 6Ir1
    Short delay time setting value ts 0.1s, 0.2s, 0.3s, 0.4s, 0.6s, 0.8s, 1.0s, OFF 0.4s

    Short-circuit short delay protection action characteristics (Table 4: Short Delay Action Characteristics of Short Circuit)

    Characteristic Fault current multiple Trip characteristics Delay error
    No action feature ≤0.85 Ir2 Failure to actuate /
    Performance characteristic >1.15 Ir2 Deferred action ±40ms

    ◆ Instant Protection
    Set parameters for instantaneous short-circuit protection (Table 5: Instantaneous parameter setting)

    Parameter setting Set value Factory set value
    Instantaneous action current setting Ir3 4 Ir1, 6 Ir1, 7 Ir1, 8 Ir1, 9 Ir1, 10 Ir1, 11 Ir1, 12 Ir1, 13 Ir1, 14 Ir1, OFF 10 Ir1

    Instantaneous short-circuit protection characteristics (Table 6: Instantaneous Motion Characteristics)

    Characteristic Current multiplier (I/Ir3) Trip characteristics Trip time
    No action feature ≤0.85 Failure to actuate ≥200ms
    Performance characteristic >1.15 Movement <200ms

    ◆ Setting range for residual current protection characteristics (Table 7)

    Parameter Set value (125, 250, 400) Set value (630) Factory set value
    Remaining motion current IΔn 50, 100, 200, 300, 400, 500, 600, 800, automatic 100, 200, 300, 400, 500, 600, 800, 1000, automatic 500

    ◆ Performance characteristic (Table 8: Protection Action Characteristics)

    Parameter Characteristic
    Rated no-load current 0.5IΔn
    Rated operating current ≥0.75IΔn
    Time-delay characteristics 2IΔn Limit Time (Δt) Break-time
    IΔn 2IΔn 5IΔn
    Non-delay ≤0.3s ≤0.15s ≤0.04s
    0.06 ≥0.06s ≤0.5s ≤0.2s ≤0.15s

    ◆ Auto mode
    In automatic gear mode, the gear values and floating values are:

    Gauge reading (mA) Floating value (mA)
    50 25
    100 50
    200 100
    300 150
    400 200
    500 250
    600 300
    800 400
    1000 -

    When the residual current exceeds the floating threshold of a setting without reaching its activation level and remains stable for 60 seconds, the setting is raised by one level. This process continues until reaching the maximum setting. Conversely, when the residual current falls below the floating threshold of the next lower setting and remains stable for 120 seconds, the setting is lowered by one level. This sequence repeats until the minimum setting is reached. Taking the 'Auto 2' setting with an initial residual current of 100mA as an example: When the circuit breaker is energized, the setting automatically resets to 300mA. If the residual current increases above 150mA and remains stable for 60 seconds, the setting changes to 500mA. When the residual current decreases below 150mA and stays stable for 120 seconds, the setting adjusts to 200mA.

    ◆ Autoreclose circuit breaker
    When the residual current exceeds the set trip current threshold, the circuit breaker will trip. After 20-60 seconds, it can automatically reclose, though manual reclosing is unrestricted. If the fault current disappears within 5 seconds after reclosing, the operation is successful and the breaker resumes normal operation. If the fault persists, the breaker will trip again and remain locked, preventing automatic reclosing. In such cases, manual reclosing must be performed.

    ◆ Over-voltage protection
    When the line phase voltage exceeds the overvoltage protection setting, the circuit breaker trips. Once the voltage returns to normal, the circuit breaker automatically recloses and resumes operation. The overvoltage protection setting ranges from 250V to 300V, with a factory default of 275V. Users can adjust or disable the protection as needed.

    ◆ Undervoltage protection
    When the phase voltage falls below the undervoltage protection setting, the circuit breaker trips. Once the voltage returns to normal, the breaker automatically recloses. The undervoltage protection range is 145V to 200V, with a factory default of 145V. Users can adjust or disable the protection as needed.

    ◆ Phase loss protection function
    When a phase is missing at the power supply end of the line, the circuit breaker protection trips. When the line is restored to normal voltage, the circuit breaker can be automatically closed and put into operation.

    Outline Overall and Installing Dimensions

    Outline Overall and Installing Dimensions 1Outline Overall and Installing Dimensions 2Outline Overall and Installing Dimensions 3Outline Overall and Installing Dimensions 4

    Characteristic curve

    ◆ Linked protection function
    The Linkage Interface Can Be Used to Coordinate With Other Fire Fighting Equipment for Protection as Follows.

    IN input settings Function declaration Priority Delay time
    Input control IN1 is short-circuited to DCOM Circuit breaker closed Low ≤40ms
    IN3 is short-circuited to DCOM Trip the circuit breaker Gao ≤40ms

    Note: Prolonged short-circuiting will keep the circuit breaker in the open state.

    Operating Time

    Frequently Asked Questions (FAQ)

    What standards does the Residual Current Protection (RCD) Circuit Breaker meet?
    The product complies with the standards GB/T14048.1-2012 (Low voltage switchgear and control equipment - General principles), GB/T14048.2-2008 (Low-voltage switchgear and control equipment - Circuit breakers), and GB/T1770 1-2008 (Equipment circuit breakers).
    How does the automatic reclosing function work?
    When the residual current exceeds the set threshold, the breaker trips. It will automatically attempt to reclose after 20-60 seconds. If the fault disappears within 5 seconds after reclosing, normal operation is restored. If the fault persists, it trips again and locks, requiring manual reclosing.
    What are the over-voltage and under-voltage protection thresholds?
    The over-voltage protection range is adjustable between 250V and 300V (factory default is 275V). The under-voltage protection range is adjustable between 145V and 200V (factory default is 145V). Users can modify or disable these protections as required.
    What is the difference between manual and automatic residual current setting mode?
    In manual mode, users set a specific value for the rated residual operating current. In automatic mode, the MCU automatically tracks the line leakage and adjusts the threshold settings dynamically based on stable readings over 60 or 120 seconds.
    Does this circuit breaker support remote communication and control?
    Yes, the device features network communication capabilities that enable remote signaling, remote measurement, remote control, and remote adjustment. It also supports optional infrared communication.
    What happens in the event of a phase loss?
    When a phase is missing at the power supply end of the line, the phase loss protection is triggered and the circuit breaker trips. Once the line voltage is restored to normal, the circuit breaker can automatically close and resume operations.