CBRM5E Ultra Compact Intelligent MCCB from China Suppliers - Fast Auto-Reclosing & Smart Grid Solutions Factory

,

The D&T CBRM5E ultra-compact smart MCCB, produced by leading China suppliers, offers rapid auto-reclosing within just 2 seconds, ensuring efficient power management.

,

This advanced circuit breaker provides extensive protection functions, fault recording, real-time temperature detection, and precise metering capabilities, with a rated current of up to 630A.

,

Supported by multiple communication protocols and remote control features, it is perfectly suited for modern power distribution and smart grid initiatives, making it a preferred choice for factories looking to enhance efficiency.

,

Additionally, it functions as an externally controlled breaker for smart meters, incorporating islanding safeguards and power generation monitoring, enabling secure photovoltaic grid connections.

,

With our in-house SMT production capabilities, we guarantee rigorous quality control and outstanding product stability, positioning us as a reliable choice among manufacturers and suppliers in China.

,

    Main functions and features Product model and meaning

    Product model and meaning

    Main functions and features

    • Adopt high-performance 32-bit ARM microprocessor for real-time signal processing and intelligent control;
    • LCD display in Chinese/English, user-friendly interface, easy to operate;
    • Have automatic reclosing function; high closing speed, closing time ≤ 2s;
    • Long delay, short delay, and instantaneous three-section protection, adopting electronic tripping, independent of power supply voltage;
    • Have high breaking capacity, ensuring reliability of short circuit protection;
    • Overvoltage protection, undervoltage protection, open phase protection, and null line loss protection; the protection functions and parameters can be set and modified online;
    • Real-time display of three-phase power supply voltage and load current;
    • Identification, display, storage, query, and deletion of tripping types (remote blocking, overload, undervoltage, overvoltage, voltage loss, open phase, disconnection of null lines, etc.);
    • Support the functions of remote signaling, telemetering, remote control, and remote adjustment;
    • HPLC pluggable module and micro-power Bluetooth wireless communication;
    • 0.05In-1.2In measurement can reach Grade 1.0;
    • Real-time measurement of active power, reactive power, apparent power, power factor and other parameters, and accumulation of three-phase active electrical energy;
    • Time control, cost control and other modes are optional, making the application more flexible;
    • Support DL/T645 protocol and Modbus protocol, and automatically identify them;
    • Real-time monitoring of the temperature of the incoming terminal block (optional);
    • Support online remote upgrade for easy maintenance and upgrade;
    • Accuracy class: The current and voltage accuracy can reach up to Class 0.5s; the accuracy of active and reactive power can reach up to Class 1;
    • Support active power demand exceeding the limit, reactive power demand exceeding the limit, current abrupt change event, current interruption, voltage harmonic content, current harmonic content, voltage waveform distortion, and current waveform distortion;
    • Have passive islanding protection (optional);
    • Have terminal and contact overtemperature protection (optional);
    • Have power generation quality monitoring and protection (optional);
    • Have three-phase unbalanced monitoring and protection for power generation current (optional).

    Operating environment

    • The installation site should be free of conductive dust, corrosive gases, flammable and explosive gases, and invasion of rain or snow;
    • Altitude: Not exceeding 2,000m;
    • Ambient temperature: -5℃~+40℃, mean daily maximum temperature: ≤ +35℃;
    • Relative humidity: ≤ 50% (when the ambient temperature is +40℃);
    • The magnetic field strength of the external magnetic field of the installation site should not exceed 5 times the strength of the geomagnetic field in any direction;
    • The installation location should have good ventilation and heat dissipation conditions;
    • When HPLC (broadband carrier) communication is required, make sure that all communication devices work under one transformer.

    Classification and functions of circuit breakers

    Functional classification Conventional type Metering type Photovoltaic type
    Protection function Overload protection
    Short circuit protection
    Automatic reclosing
    Open phase protection
    Overvoltage protection
    Undervoltage protection
    Null line loss protection
    Over/Under-frequency protection
    Power outage protection
    Phase sequence protection
    Islanding protection
    Overtemperature protection
    Power quality monitoring and protection
    Measurement display Three-phase operating voltage
    Three-phase operating current
    Active power
    Reactive power
    Apparent power
    Voltage imbalance
    Current imbalance
    Performance setting Long delay of overload
    Short delay of short circuit
    Instantaneous short circuit
    Overvoltage protection value
    Undervoltage protection value
    Time and date
    Protecting enabling and disabling
    Open phase protection value
    Over/Under-frequency protection value
    Voltage imbalance protection value
    Current imbalance protection value
    Information query and display Action records and fault records
    Communication function RS-485/ Modbus
    Carrier
    Bluetooth
    Topology

    ● means this function is available; △ means this function is optional; ○ means this function is not available;

    Main technical parameters

    Specification and model 125 250 400 630
    Rated current of frame size (A) 125 250 400 630
    Number of poles 3P/4P
    Rated operating voltage Ue (V) AC 400/50HZ
    Rated insulation voltage Ui (V) 1000
    Rated impulse withstand voltage Uimp (V) 8000
    Flashover distance (mm) ≥50 ≥100
    Limit short-circuit breaking capacity lcu(kA) 25(S) 36(L) 50(M) 36(S) 35(L) 50(M) 35(S) 65(L) 70(M) 50(S) 65(L) 70(M)
    Operating short-circuit breaking capacity lcs(kA) 20(S) 25(L) 35(M) 25(S) 35(L) 35(M) 35(S) 42(L) 50(M) 50(S) 50(L) 70(M)
    Rated short-time withstand current Icw (kA)/s 1.5 3 5 8
    Automatic closing time (s) ≤2s
    Operating performance (times) Power on 1500 1000 1000 1000
    No power supply 8500 7000 4000 4000
    Total number of times 10000 8000 5000 5000
    Overload and short circuit characteristics Three-section protection, electronically adjustable; for details, please refer to "Protection characteristics description"
    Overvoltage protection value (V) Set value (231~330) / Default value 275V
    Undervoltage protection value (V) Set value (88~209) / Default value 145V
    Open phase protection value (V) Set value (10~130) / Default value 30V
    Control delay time (ms) ≤40ms
    Communication delay time (ms) ≤200ms

    Measurement accuracy class

    Accuracy Allowable error
    Current accuracy ±0.5%、 ±1.0%
    Voltage accuracy ±0.5%、 ±1.0%
    Active power accuracy ±1.0%、 ±1.5%、 2.0%、 2.5%
    Reactive power accuracy ±1.0%、 ±1.5%、 2.0%、 2.5%

    Note: The temperature detection point is located near the incoming and outgoing wiring terminals.

    ◆Passive islanding protection
    ◆The passive inspection method mainly detects whether the system is in an islanding state by detecting the amplitude, frequency, phase position, and harmonic content of the common point voltage at the output terminal of the inverter, mainly including overvoltage/undervoltage protection, overfrequency/underfrequency protection, phase change detection, harmonic detection, etc. The setting values of passive islanding detection criteria;
    ◆Voltage amplitude swing (dUisI): 0.1~0.9Un, OFF; voltage frequency swing (dFisI): 0.5~25Hz, OFF;
    Voltage phase swing (dPHisl): 1~60°, OFF; voltage waveform distortion swing (dUTHDisI): 0.5~30%, OFF;
    The delay action characteristic is a fixed time limit, and tPis setting range is 0.01-9.99s;
    The passive islanding protection action should meet the requirements in Table 8.

    Protection characteristics description

    ◆Overload long delay protection
    The circuit breaker should provide overload and short-circuit protection, photovoltaic power generation system islanding protection and power quality monitoring protection. The setting values of all protection functions should support remote configuration.
    1. Range of overcurrent long delay setting value (Ir)
    Range of current setting value (Ir): 0.4~1In, OFF. OFF means it can be turned off, that is, turning off the protection function. The delay action characteristic is the IEC standard inverse time limit curve, Kfactor=0.14, αfactor=0.02, Lfactor=0, I=set current, Is=rated current:

    Protection characteristics description

    Tms setting range: 1-10s.

    The overcurrent long delay protection action should meet the requirements in Table 1.

    Comparison Table of Overcurrent Long Delay Protection Actions.

    Long delay action current (lr1) Action
    ≤Ir Normal operation
    1Ir~1.5Ir Continuously observe for 10 minutes, actively report overload alarm and record the data; after 10 minutes, the current still exceeds the standard limit
    ≥1.5Ir Observe continuously for 5 minutes. If the current still exceeds the standard limit after 5 minutes, cut off the grid connection point and report it

    Note: 1.3lr is a conservative value, and the time and current values are set in the switch body.

    ◆Action characteristics
    1. Range of overcurrent short delay setting value (Isd)
    Range of short-time action current (Isd): 1.5~5lr, OFF. OFF means it can be turned off, that is, turning off the protection function. The delay action characteristic is a fixed time limit, and the setting range of tlsd is 1-10s. The overcurrent short delay protection action should meet the requirements in Table 2.

    Comparison Table of Overcurrent Short Delay Protection Action.

    Table 2
    Short delay action current (lsd) Action
    ≤k1Ir Normal operation
    k1Ir~k2Ir Normal operation; actively report overcurrent alarms and record the data
    ≥k2Ir Continuously observe for tlsd time, and if the current still exceeds the standard limit after tlsd time, cut off the grid connection point and report it

    Note: k1, k2=1.5~5lr, k1<k2; the time and current values are set in the switch body.

    2. Range of rated short-time breaking current setting value (Ii).
    Range of rated instantaneous short-circuit current setting value (I): 2~12lr, OFF. OFF means it can be turned off, that is, turning off the protection function.
    The breaking current protection action should meet the requirements in Table 3.

    Comparison Table of Short-circuit Current Protection Action

    Table 3
    Short-circuit current Action
    ≥ 5~8lr Cut off the grid connection point in 0.2 seconds and report it

    3. The protection characteristic curve of three-section protection is shown in the following figure:

    action time

    ◆Overvoltage protection Range of overvoltage protection voltage setting value (Uov) is 1.05~1.5Un. OFF means it can be turned off, that is, turning off the protection function.
    The delay action characteristic is a fixed time limit, and the setting range of tUov is 1-9999s.
    The overvoltage protection action should meet the requirements in Table 5.

    Comparison Table of Overvoltage Protection Action

    Table 5
    Maximum value of three-phase voltage Action
    ≤ 234.5V Normal operation
    > 234.5V Cut off the grid connection point after 2s and report it
    Note:
    1.OFF means it can be turned off, that is, turning off the protection function.
    2.While monitoring the changes in voltage amplitude, also monitor the changes in voltage frequency. If the voltage frequency remains basically unchanged, use the above criteria for overvoltage protection.

    Note: OFF means it can be turned off, that is, turning off the protection function.

    ◆Undervoltage protection
    The molded case circuit breakers do not have such function.
    Range of undervoltage protection voltage setting value (Uuv) is 0.4~0.95Un. OFF means it can be turned off, that is, turning off the protection function.
    The delay action characteristic is a fixed time limit, and the setting range of tUuv is 1-9,999s.
    The undervoltage protection action should meet the requirements in Table 6.

    Comparison Table of Undervoltage Protection Action

    Table 6
    Minimum value of three-phase voltage Action
    ≥ 187V Normal operation
    < 187V Cut off the grid connection point after 2s and report it
    Note:
    1.OFF means it can be turned off, that is, turning off the protection function.
    2. While monitoring the changes in voltage amplitude, also monitor the changes in voltage frequency. If the voltage frequency remains basically unchanged, use the above criteria for overvoltage protection.

    ◆Terminal and contact overtemperature protection
    Range of terminal and contact overtemperature protection setting value (Tem): 80~160℃, OFF. OFF means it can be turned off, that is, turning off the protection function.
    The delay action characteristic is a fixed time limit, and tTem setting range is 1-9,999s.
    The terminal and contact overtemperature protection action should meet the requirements in Table 7.

    Comparison Table of Terminal and Contact Overtemperature Protection Action

    Table 7
    Terminal and contact temperature Action
    ≤ 60℃ Normal operation
    60℃~90℃ Normal operation; actively report terminal and contact overtemperature alarms and record the data
    ≥ 90℃ Continuously observe for 60s. If the temperature of the terminal and contact still exceeds the standard limit after 60s, cut off the grid connection point and report it
    ≥ 110℃ Cut off the grid connection point after 0.2s and report it

    ◆Passive islanding protection
    ◆The passive inspection method mainly detects whether the system is in an islanding state by detecting the amplitude, frequency, phase position, and harmonic content of the common point voltage at the output terminal of the inverter, mainly including overvoltage/undervoltage protection, overfrequency/underfrequency protection, phase change detection, harmonic detection, etc. The setting values of passive islanding detection criteria;
    ◆Voltage amplitude swing (dUisI): 0.1~0.9Un, OFF; voltage frequency swing (dFisI): 0.5~25Hz, OFF;
    Voltage phase swing (dPHisl): 1~60°, OFF; voltage waveform distortion swing (dUTHDisI): 0.5~30%, OFF;
    The delay action characteristic is a fixed time limit, and tPis setting range is 0.01-9.99s;
    The passive islanding protection action should meet the requirements in Table 8.

    Comparison Table of Passive Islanding Protection Action

    Table 8
    Fluctuation value of criteria Action
    Voltage amplitude swing or swing range If the voltage amplitude swing range exceeds 20V or the swing exceeds the range of [187V, 234.5V] within 100ms, it is judged as an island
    Voltage frequency swing or swing range If the voltage frequency swing range exceeds 0.2Hz or the swing exceeds the range of [49.5Hz~50.2Hz] within 100ms, it is judged as an island
    Note:
    1.The swing range refers to the difference between the maximum and minimum swing values within a certain period of time;
    2.The above criteria are mainly based on voltage frequency swing, supplemented by voltage amplitude swing. When the voltage frequency swing criterion is established, cut off the grid connection point within 2s and report it.

    ◆Power generation quality monitoring and protection

    The monitoring and protection actions of power generation current harmonics should meet the requirements in Table 9.

    Comparison Table of Current Harmonics and Protection Action

    Table 9
    Total current distortion Action
    ≤5% Normal grid connection
    >5% Continuously observe for 60s, and if the harmonic wave still exceeds the standard limit after 60 seconds, cut off the grid connection point and report it

    Note: OFF means it can be turned off, that is, turning off the protection function.

    ◆Monitoring and protection of power generation current three-phase imbalance (applicable to three-phase grid connection)
    The three-phase imbalance protection action of power generation current should meet the requirements in Table 10.

    Negative sequence three-phase current imbalance ratio and protection action

    Table 10
    Three phase current imbalance ratio Action
    ≤ 2% Normal grid connection
    > 2% Continuously observe for 60s, and if the imbalance ratio still exceeds the standard limit after 60 seconds, cut off the grid connection point and report it
    Note: OFF means it can be turned off, that is, turning off the protection function.

    ◆Undervoltage protection function
    When the phase voltage of the line is lower than the undervoltage protection set value, the circuit breaker will trip for protection. After the line voltage returns to normal, the circuit breaker can be automatically closed and activated. The range of undervoltage protection setting value is 88V~209V, the factory setting is 187V, and users can set or turn off the protection themselves.
    ◆Open phase protection function When the phase of the outgoing line of the power end of the line is open, the circuit breaker will trip for protection. After the line voltage returns to normal, the circuit breaker can be automatically closed and activated. The range of open phase protection set value is 10V~130V, the factory setting is 30V, and users can set or turn off the protection themselves.
    ◆Automatic reclosing
    When the line voltage value exceeds the limit and the circuit breaker trips, the circuit breaker will be automatically reclosed 5s later after the line voltage returns to normal, but manual closing is not limited by time.
    ◆External control or dynamic protection function

    Communication

    Note: S1 is passive dry node;
    When the product is put into use and there is no external control, S1 needs to be shorted or the external control function of the software needs to be turned off.

    ◆Cost control function
    This product can be connected to a cost control meter and be used as an external circuit breaker for an energy meter. It is compatible with pulse type and level type cost control meters. This function requires configuring the switch to cost control mode and turning it on, and only when the cost control is enabled, can it be used. When it is working in cost control mode, the dynamic protection function can automatically exit, and when there is no energy meter cost control signal, it cannot be manually or automatically closed. If it is closed by force, the product will be automatically disconnected.

    Overall and installation dimensions - 3P

    Overall and installation dimensions - 3P
    Model Overall dimensions (mm) Installation dimensions(mm) Dimensions of wiring block (mm) Mounting screw Model
    L L1 L2 L3 W1 W2 H H1 H2 a b d A B C t1 t2 h1 h2 M
    CBRM5E-125CYJ/4 150 108.7 24.7 88.7 60 92 120 117 65.5 30 129 Φ4.5 18 17 8.5 3 3 23 26 M8x20 M4x45
    CBRM5E-250CYJ/4 165 109 30.5 99 70 107 120 117 69.5 35 126 Φ4.5 22 21 10.5 3 3 24 24 M8x20 M4x45
    CBRM5E-400CYJ/4 258 177 40.5 148 96 150 160 157 98.5 44 195 Φ7 33 28.5 16.5 5 4 36.5 37.5 M10X35 M5X100
    CBRM5E-630CYJ/4 270 177 46.5 145.8 116 182 163.5 160.5 102 58 200 Φ7 44 30.5 17.7 6 6 41.5 43.5 M12x35 M6x65

    Overall and installation dimensions - 4P

    Overall and installation dimensions - 4P
    Model Overall dimensions (mm) Installation dimensions(mm) Dimensions of wiring block (mm) Mounting screw Model
    L L1 L2 L3 W W1 W2 H H1 H2 a b d A B C t1 t2 h1 h2 M
    CBRM5E-125CYJ/4 150 108.7 24.7 88.7 122 30 92 120 117 65.5 30 129 Φ4.5 18 17 8.5 3 3 23 26 M8x20 M4x45
    CBRM5E-250CYJ/4 165 109 30.5 99 142 35 107 120 117 69.5 35 126 Φ4.5 22 21 10.5 3 3 24 24 M8x20 M4x45
    CBRM5E-400CYJ/4 258 177 40.5 148 198 48 150 160 157 98.5 44 195 Φ7 33 28.5 16.5 5 4 36.5 37.5 M10X35 M5X100
    CBRM5E-630CYJ/4 270 177 46.5 145.8 240 58 182 163.5 160.5 102 58 200 Φ7 44 30.5 17.7 6 6 41.5 43.5 M12x35 M6x65
    Frequently Asked Questions (FAQ)
    What are the main protection features of these circuit breakers?
    The circuit breakers feature comprehensive three-section protection (long delay, short delay, and instantaneous short circuit) independent of power supply voltage. They also provide overvoltage, undervoltage, open phase, null line loss, terminal and contact overtemperature, and passive islanding protections.
    How does the automatic reclosing function operate?
    The automatic reclosing function operates at a high closing speed (closing time ≤ 2s). When a trip is caused by a voltage limit event, the circuit breaker automatically recloses 5 seconds after the line voltage returns to normal. Manual closing remains unrestricted by time.
    What are the environmental requirements for installation?
    The installation site must be free of conductive dust, corrosive, flammable, or explosive gases, and protected from rain or snow. It should not exceed an altitude of 2,000m, with ambient temperatures between -5℃ and +40℃ (mean daily maximum ≤ +35℃) and relative humidity ≤ 50% at +40℃.
    Which communication protocols and modules are supported?
    These devices support both the DL/T645 protocol and Modbus protocol with automatic identification. Hardware communication options include RS-485, HPLC pluggable modules (broadband carrier), and micro-power Bluetooth wireless communication.
    How does the terminal and contact overtemperature protection function?
    The overtemperature protection range is adjustable from 80℃ to 160℃. When temperatures reach between 60℃ and 90℃, the system reports an alarm. If the temperature remains ≥ 90℃ for 60 seconds, or immediately exceeds ≥ 110℃, the breaker cuts off the grid connection point.
    What is passive islanding protection and how is it triggered?
    Passive islanding protection determines if the system is in an islanding state by monitoring voltage amplitude, frequency, phase, and harmonics. It triggers a grid cutoff within 2 seconds if the voltage amplitude swing exceeds 20V or the frequency swing exceeds 0.2Hz within a 100ms window.