CBRM5K Compact Lockable Molded Case Circuit Breaker (MCCB)
Model and Meaning

Meets Standards
The products conform to the following standards:
GB/T14048.1-2012 Low-voltage switchgear and controlgear - Part 1: General;
GB/T14048.2-2008 Low-voltage switchgear and controlgear - Part 2: Circuit breakers; GB/T17701-2008 Circuit breakers for equipment.
Main Functions and Features
1.It adopts a high-performance 32-bit ARM microprocessor for real-time signal processing and intelligent control;
2.The LCD Chinese display provides a user-friendly interface and simple operation;
3.It features residual current (leakage current) protection with online adjustment of the residual current level and reclosing function;
4.It monitors and tracks the residual current of the line in real time and automatically adjusts the level to ensure the product's operational rate and reliability;
5.It offers three-stage protection: long-delay, short-delay, and instantaneous, using electronic tripping that is independent of power supply voltage;
6.It has high breaking capacity to ensure the reliability of line short-circuit protection;
7.Over-voltage protection, under-voltage protection, phase loss protection;
8.Real-time display of line residual current, three-phase power supply voltage, and load current; 9.Protection functions and parameters can be set and modified online;
10.The tripping type (residual current, lockout, overload, undervoltage, overvoltage, phase loss) can be identified, displayed, stored, queried, and deleted;
11.Network-type models have communication capabilities, enabling remote signaling, telemetry, remote control, and remote adjustment;
12.Pluggable surge protection modules (optional) ;
13.feature infrared communication (optional).
Main Technical Parameters
|
Specifications and Models |
CBRM3EL-125CY |
CBRM3EL-250CY |
CBRM3EL-400CY |
CBRM3EL-630CY |
CBRM3EL-800CY |
|
|
Frame rating rated current (A) |
125 |
250 |
400 |
630 |
800 |
|
|
Extreme number |
3P+N |
3P+N,2P |
3P+N |
3P+N |
3P+N |
|
|
Rated operating voltage Ue (V) |
AC 400/50HZ |
|||||
|
Rated insulation voltage Ui (V) |
1000 |
|||||
|
Rated impulse withstand voltage Uimp (V) |
8000 |
|||||
|
Flight arc distance (mm) |
≯50 |
≯100 |
||||
|
Ultimate short-circuit breaking capacity Icu(kA) |
50(H type 70) |
65(H type 85) |
65 |
|||
|
Operating short-circuit breaking capacity Ics(kA) |
35(H type 50) |
42(H type 65) |
42 |
|||
|
Rated residual short circuit connection (disconnection)Ability I△m(kA) |
12.5(H type 17.5) |
16.25(H type 21.5) |
16.25 |
|||
|
Rated short-time withstand current Icw (kA)/s |
1.5 |
3 |
5 |
8 |
10 |
|
|
Residual current operating characteristics |
AC type |
|||||
|
Rated residual operating current IΔN(mA) |
50/100/200/300/400/500/600/800 |
100/200/300/400/500/600/800/1000 |
||||
|
Remaining motion time characteristics |
Delayed/Non-delayed |
|||||
|
Delay-type limit of non-drive time (s) |
0.06/0.1/0.2 optional: 2IAn |
|||||
|
Break time (s) |
I△n≤0.5; 2I△n≤0.2; 5I△n≤0.15 |
|||||
|
Automatic reclosing time (s) |
20-60 |
|||||
|
Operational performance (times) |
power ups |
1500 |
1000 |
1000 |
500 |
|
|
No power |
8500 |
7000 |
4000 |
2500 |
||
|
Total number of times |
10000 |
8000 |
5000 |
3000 |
||
|
Overload and short-circuit characteristics |
Three-stage protection, electronically adjustable; see "Protection Feature Description" for details. |
|||||
|
Overvoltage protection value (V) |
Set value (250~300) ± 5% |
|||||
|
Undervoltage protection value (V) |
Set value (145~200) ± 5% |
|||||
|
Joint control delay time (ms) |
≤40ms |
|||||
|
Communication delay time (ms) |
≤200ms |
|||||
Protection Features Description
◆Overload long delay protection
Action value setting range
Table 1: Overload Long Delay Parameter Settings
|
parameter |
Frame current |
Setting value |
Factory setting value |
|
Action setting value Ir1 |
125 |
50A、63A、80A、100A、125A |
125A |
|
250 |
100A、125A、140A、160A、180A、200A、225A、250A |
250A |
|
|
400 |
160A、180A、200A、225A、250A、315A、350A、400A |
400A |
|
|
630 |
250A、315A、350A、400A、500A、630A |
630A |
|
|
800 |
315A、350A、400A、500A、630A、700A、800A |
800A |
|
|
Delay time setting value tL |
3s,4s,6s,8s,10s12s,16s,18s,OFF |
12s |
|
◆Action characteristics
Table 2: Protective Action Characteristics
|
Ambient temperature |
Current Name |
Setting current multiple |
Agreed Time |
|
+40℃ |
Non-tripping current agreed upon |
1.05lr1 |
≥2h |
|
Conventional tripping current |
1.3lr1 |
<2h |
◆Delay characteristics
Overload protection operates based on inverse time characteristics:
T=(6Ir1/I)2tL Delay accuracy: ±10% Where T is the action time value, lr1 is the long delay protection setting value, I is the fault current, and TL is the long delay time setting value.
◆Short circuit short delay protection
Short-circuit short-delay protection prevents impedance short circuits in power distribution systems, and the tripping delay is for selective protection. Short-circuit short-delay protection parameter settings.
Table 3: Short-circuit short-delay parameter settings
|
Parameter settings |
Setting value |
Factory setting value |
|
Short-delay operating current setting value Ir2 |
2lr1,2.5lr1.3lr1.4lr1.5lr16lr1.7lr1,8lr1.10lr1.12lr1 |
6lr1 |
|
Short delay time setting value ts |
0.1s.0.2s.0.3s.0.4s.0.6s.0.8s,1.0s ,OFF |
0.4s |
Short-circuit short-delay protection operation characteristics
Table 4: Short-circuit short-delay action characteristics
|
characteristic |
Fault current multiple |
Tripping characteristics |
Delay error |
|
Non-action characteristics |
≤0.85 lr2 |
No action |
/ |
|
Action characteristics |
>1.15 1r2 |
Delayed action |
±40ms |
◆Instantaneous protection Short-circuit instantaneous protection related parameter settings
Table 5: Instantaneous Parameter Settings
|
Parameter settings |
Setting value |
Factory setting value |
|
Instantaneous operating current setting value Ir3 |
4 lr1,6 lr1,7 lr1,8 lr1.10 lr1.11 lr1,12 lr1,13 lr1,14 lr1.OFF |
10 lr1 |
Short circuit instantaneous protection operation characteristics
Table 6: Instantaneous motion characteristics
|
characteristic |
Current multiple (I/Ir3) |
Tripping characteristics |
Tripping time |
|
Non-action characteristics |
≤0.85 |
No action |
≥200ms |
|
Action characteristics |
>1.15 |
Instantaneous action |
<200ms |
◆Residual current protection characteristics
Gear setting range
|
parameter |
Setting values (125, 250, 400) |
Setting values (630, 800) |
Factory setting value |
|
Residual operating current IΔn |
50, 100, 200, 300, 400, 500, 600, 800 (Auto) |
100, 200, 300, 400, 500, 600, 800, 1000 Automatic |
500 |
External Shape and Installation Dimensions

Note: The auxiliary contact is on the left and the surge protection module is on the right in the diagram; the dimensions of the accessories are the same for all models.




Characteristic Curves

-
CBRM3EL-125
-
CBRM3EL-160、250
-
CBRM3EL-400
-
CBRM3EL-630
-
CBRM3EL-800

CBRM5EL Automatic Reclosing MCCB
CBRM3EL Remote Reclosing MCCB
CBRM5E Intelligent MCCB
CBRM5EKd Electronic MCCB
CBRM5Kd Compact MCCB
CBRM5K Lockable MCCB
CBRM5EN Primary-secondary Separated MCCB
CBRECB Meter Remote Control MCCB
CBRB7BL Type B Smart RCBO
CBRB7 Compact MCB
CBRB7-AP PV Grid-connected MCB
CBRW3 4000A ACB
CBRW3 2500A ACB
CBRW3 1600A ACB