Inquiry Now
Leave Your Message
Products Categories
Featured Products

CBRM3EL Automatic Reclosing Circuit Breaker with Residual Current Protection(MCCB)

The residual current circuit breaker has a rated insulation voltage of 1000V, suitable for three-phase AC systems with solid frequency, 400V rated voltage, and rated current up to 80A. The four-wire neutral point is directly grounded (T) in the distribution network, to provide indirect contact protection, prevent fire hazards caused by ground fault currents due to equipment insulation damage, and distribute electrical energy to protect lines and power equipment from hazards such as overload, under-voltage, short circuit, and single-phase grounding faults.

    CBRM3EL Leakage Circuit Breaker

    Product Model and Meaning

    ScreenShot_2026-08-07_143340_397.png

    Meets Standards

    The product meets the following standards:
    GB/T14048.1-2012 Low voltage switchgear and control equipment Part 1: General principles;
    GB/T14048.2-2008 Low-voltage switchgear and control equipment Part 2: Circuit breakers;
    GB/T17701-2008 <Equipment circuit breakers>.

    Main Functions and Features

    Adopt high-performance 32-bit ARM microprocessor, real-time signal processing and intelligent control;
    LCD Chinese display, user-friendly interface, easy operation;
    The residual current (leakage current) protection can be adjusted online, and has the function of reclosing;
    Real-time monitoring and tracking of the residual current of the line, automatic adjustment of the range, to ensure the operation rate and reliability of the product;
    Three-stage protection, long delay, short delay and instantaneous, using electronic trip, independent of power supply voltage;
    High breaking capacity to ensure the reliability of line short circuit protection;
    Over-voltage protection, under-voltage protection, phase loss protection;
    The residual current of the line, the three-phase power supply voltage and the load current are displayed in real time;
    Protective functions and parameters can be set and modified online.
    Trip types (residual current, lockout, overload, under-voltage, over-voltage, phase loss) are identified and displayed, and can be stored, queried, and deleted.
    The network type has communication functions, which can realize remote signaling, remote measurement, remote control and remote adjustment.
    Plug-and-play lightning protection module (optional)
    Supports infrared communication (optional)

    Key Technical Specifications

    Specifications and models

    CBRV3F-125CY
    CRRV3EL-125CS

    CBRM3FI.-250CY
    CBRM3EL-250CS

    CBRM3EI.-400CY
    CBRM3EL-400CS

    CBRV3EL-630CY
    CBRM3EL 630CS

    CBRM3EL 800CY
    CBRM3EL-800CS

    Rated current of the shell frame class (A)

    125

    250

    400

    630

    800

    Number of poles

    3P+N

    3P+N

    3P+N

    3P+N

    3P+N

    Rated working voltage Ue (V)

    AC 400/50HZ

    Rated insulation voltage Ui (V)

    1000

    Rated impulse withstand voltage Uimp (V)

    8000

    Flash-over distance(mm)

    <=50

    <=100

    Maximum short-circuit breaking capacity (lcu, kA)

    50 (H-type 70)

    65 (H-type 85)

    85

    65

    Operating short-circuit breaking capacity (lcs, kA)

    35 (H-type 50)

    42 (H-type 65)

    65

    42

    Rated residual short-circuit breaking capacity I△m (kA)

    12.5 (H-type 17.5)

    16.25 (H-type 21.5)

    16.25

    Rated short-time current Icw (kA)is

    1.5

    3

    5

    8

    10

    RCD trip characteristics

    AC type

    Rated residual operating current I△n (mA)

    50/100/200/300/400/500/600/800(MCU auto-tracking or manual setting)

    100/200/300/400/500/600/800/1000
    (MCU auto-tracking or manual setting)

    Residual Operating Time Characteristic

    Time delay type / Non-time-delay type

    Delay-type limit non-drive time (s)

    0.06/0.1/0.2 Optional:21△n

    Break-time (s)

    I△≤0.5;2I△n≤0.2;51△n≤0.15

    Automatic reclosing time (s)

    20-60

    Operation performance (times)

    Set up an electric circuit

    1500

    1000

    1000

    500

    No power

    8500

    7000

    4000

    2500

    Total

    10000

    8000

    5000

    3000

    Overload and short-circuit characteristics

    Three-stage protection with electronic adjustment. See "Protection Characteristics" for details.

    Over-voltage protection value (V)

    Set value(250~300)±5%

    Under-voltage protection value (V)

    Set value (14S--200)±5%

    Control delay time (ms)

    ≤40ms

    Communication delay (ms)

    ≤200ms

    Protection Feature Description

    ◆Overload and long delay protection

    Action value range
    Table 1:Overload Long Delay Parameter Settings

    Parameter

    Shroud current

    Set value

    Factory set value

    Action set-point Irl

    125

    50A、63A、80A、100A、125A

    125A

    250

    100A、125A、140A、160A、180A、200A、225A、250A

    250A

    400

    160A、180A、200A、225A、250A、315A、350A、400A

    400A

    630

    250A、315A、350A、400A、500A、630A

    630A

    800

    315A、350A、400A、500A、630A、700A、800A

    800A

    Delay time setting value tL

    3s,4s,6s,8s,10s,12s,16s,18s,OFF

    12s

    ◆performance characteristic
    Table 2:Protection Action Characteristics

    Ambient temperature

    Current name

    Set current multiplier

    Appointed time

    +40℃

    Conventional non tripping current

    1.05Ir1

    ≥2h

    Conventional tripping current

    1. 3Ir1

    <2h

    ◆time-delay characteristics
    The overload protection is based on the inverse time characteristic .
    The delay time T is calculated as (6rll, with a tolerance oft10%.Here,T represents the action time Irl is he long delay protection setting,I denotes the fault current. And tL is the long delay time setting.

    ◆Short circuit short delay protection
    Short delay protection prevents impedance short circuit in the distribution system, and the trip delay is to achieve selective protection.
    Short-circuit short delay protection parameter settings
    Table 3: Short-circuit delay parameter setting

    Parameter setting

    Set value

    Factory set value

    Short delay action current setting lr2

    2Ir1,2.5lr1,3lr1,4lr1,5lr1,6lr1,7lrl,8lrl,10lr1,121r1

    6lr1

    Short delay time setting value ts

    0.1s,0.2s,0.3s,0.4s,0.6s,0.8s,1.0s,OFF

    0.4s

    Short-circuit short delay protection action characteristics
    Table 4:Short Delay Action Characteristics of Short Circuit

    Characteristic

    Fault current multiple

    Trip characteristics

    Delay error

    No action feature

    ≤0.85 Ir2

    Failure to actuate

    /

    Performance characteristic

    >1.15Ir2

    Deferred action

    ±40ms

    ◆Instant Protection
    Set parameters for instantaneous short-circuit protection
    Table 5: Instantaneous parameter setting

    Parameter setting

    Set value

    Factory set value

    Instantaneous action current setting lr3

    4 Irl,6 Irl,7 Irl,8 Irl, 10 Irl,11 Ir1,12 Irl,13 rl,14 rl,0FF

    10 Ir1

    Short-circuit instantaneous protection action characteristics
    Table 6:Instantaneous motion characteristics

    Characteristic

    Current ratio (I/r3)

    Trip characteristics

    Trip time

    No action feature

    ≤0.85

    Failure to actuate

    ≥200ms

    Performance characteristic

    >1.15

    Instantaneous operation

    <200ms

    Setting range for residual current protection characteristics

    Parameter

    Set value (125,250,400)

    Set value (630,800)

    Factory set value

    Remaining motion current I△n

    50,100,200,300,400,500,600,800automatic

    100,200,300,400,500,600,800,1000automatic

    500

    Outline Overall and Installing Dimensions

    Outline Overall and InstallingDimensions.1.jpg

    Note: The left side of the attachment in the diagram is the auxiliary contact, and the right side is the lightning protection module. All models have the same attachment dimensions.

    Outline Overall and InstallingDimensions.2.jpgOutline Overall and InstallingDimensions.3.jpgOutline Overall and InstallingDimensions.4.jpgOutline Overall and InstallingDimensions.5.jpg

    Characteristic Curve

    Characteristic Curve.jpg

    Leave Your Message